Pneumatic Connections
Clean all pipelines to remove dirt and scale before instal
lation.
Apply a minimum amount of pipe compound to the male
threads of the fitting only.
Do Not use teflon tape as a
sealant.
Start with the third thread back and work away
from the end of the fitting to avoid the possibility of
contaminating the transducer. Install the transducer in the
air line.
NOTES:
Instrument quality air, per ISA Standards
D7.3-1981, is required. Use a filter to re
move dirt and liquid in the air line ahead of
the transducer for correct performance. If
an air line lubricator is used, it MUST be
located downstream, beyond the trans
ducer.
The user is responsible for insuring that the
environment in which the unit will be
installed, and the operating gas, are com
patible with the materials in the trans-
WARNING: To prevent possible ignition of hazardous
atmosphere, DO NOT REMOVE COVER from
the TXPD5220 Transducer while current is
Electric Connection
For the T5220 Transducer, make connections to the Termi
nal Block through a 1/2 NPT Conduit Connector (not
supplied) and a plastic sleeve as shown below in Figure 7.
“Electrical Connections”.
For the TXPD5220 Transducer, make connections from the
Sealed Connector Wires to an external Terminal Block. The
TXPD5220 Transducer has an additional ground wire that is
used. For more information, see Figure 7. “Electrical
Connections” below.
NOTE: The T5220 & TXPD5220 should be wired in
accordance with the wiring diagram inside of
cover.
Wiring in Hazardous Areas
Wiring in hazardous areas should be performed in accor
dance with the Table 1. and any local codes that apply.
Table 1.
Hazardous Location Wiring Practices.
Country
Agency
Code
U.S.
Canada
FM
CSA
ANSI/ISA RP 12.6 & ANSI/NFPA 70
CEC Part 1
Intrinsically Safe Connections
Refer to the latest revision of the indicated drawing.
on.
To maintain Explosion-Proof capability, DO
NOT DAMAGE mating surfaces between
cover and base. NEVER ADD GASKETS.
Table 2.
Intrinsically Safe Installation Drawings.
Underwriting Group
Drawing Number
FM (Factory Mutual)
CSA (Canadian Standards)
EC-14007
EC-16097
Figure 6.
Electrical Connections.