Pneumatic Connections 

Clean all pipelines to remove dirt and scale before instal­
lation. 
Apply a minimum amount of pipe compound to the male 
threads of the fitting only. 

Do Not use teflon tape as a 

sealant. 

Start with the third thread back and work away 

from the end of the fitting to avoid the possibility of 
contaminating the transducer.  Install the transducer in the 
air line. 

NOTES: 

Instrument quality air, per ISA Standards 
D7.3-1981, is required.  Use a filter to re­
move dirt and liquid in the air line ahead of 
the transducer for correct performance.  If 
an air line lubricator is used, it MUST be 
located downstream, beyond the trans­
ducer. 

The user is responsible for insuring that the 
environment in which the unit  will be 
installed, and the operating gas, are com­
patible with the materials in the trans-

WARNING:  To prevent possible ignition of hazardous 

atmosphere, DO NOT REMOVE COVER from 
the TXPD5220 Transducer while current is 

Electric Connection

For the T5220 Transducer, make connections to the Termi­
nal Block through a 1/2 NPT Conduit Connector (not 
supplied) and a plastic sleeve as shown below in Figure 7. 
“Electrical Connections”. 

For the TXPD5220 Transducer, make connections from the 
Sealed Connector Wires to an external Terminal Block.  The 
TXPD5220 Transducer has an additional ground wire that is 
used.  For more information, see Figure 7. “Electrical 
Connections” below. 

NOTE: The T5220 & TXPD5220 should be wired in 

accordance with the wiring diagram inside of 
cover. 

Wiring in Hazardous Areas 

Wiring in hazardous areas should be performed in accor­
dance with the Table 1. and any local codes that apply. 

Table 1. 

Hazardous Location Wiring Practices. 

Country 

Agency 

Code 

U.S. 
Canada 

FM 
CSA 

ANSI/ISA RP 12.6 & ANSI/NFPA 70 
CEC Part 1 

Intrinsically Safe Connections 

Refer to the latest revision of the indicated drawing. 

on. 

To maintain Explosion-Proof capability, DO 
NOT DAMAGE mating surfaces between 
cover and base.  NEVER ADD GASKETS. 

Table 2. 

Intrinsically Safe Installation Drawings. 

Underwriting Group 

Drawing Number 

FM (Factory Mutual) 
CSA (Canadian Standards) 

EC-14007 
EC-16097 

Figure 6. 

Electrical Connections. 

4

Содержание T5220

Страница 1: ...Mounting Kit 15268 Sold Separately INSTALLATION TheModelT5220canbemounteddirectlyontoaflatsurface The Model T5220 can be Panel Mounted using the usingthetwo10 32tappedmountingholesinthebaseofthe mount...

Страница 2: ...or use mount the T5220 in an upright Optional Mounting Kit 14596 For more information see position This will help prevent rain water from Figure 3 below entering into the unit For more information see...

Страница 3: ...ns below Mounting Kit surfaceusingthefour1 4 20x7 16 tappedmountingholes 14140 is available for Panel or 2 Pipe Mounting For inthebaseofthehousing Formoreinformation seeFigure more information see Fig...

Страница 4: ...nection FortheT5220Transducer makeconnectionstotheTermi nal Block through a 1 2 NPT Conduit Connector not supplied and a plastic sleeve as shown below in Figure 7 ElectricalConnections FortheTXPD5220T...

Страница 5: ...ApplythemaximuminputsignalandadjusttheSpan screw on the potentiometer for maximum output pressure Turn screw clockwise to increase pres sure and counterclockwise to decrease pressure 4 Repeat steps 2...

Страница 6: ...fore reas 4 Place Magnet 11 over Coil 10 and tighten with three Screws 12 sembling To clean the Inner Valve Assembly use the following 5 Using a non matalic rod Raise up on the arm to make procedure s...

Страница 7: ...PC Board 1 5 VDC PC Board 1 9 VDC PC Board 1 9 VDC PC Board 1 2 For T5220 TFI5220 TFN5220 TFNI5220 TXPD5220 TXPDI5220 Units Only For TCI5220 Only Table 4 Trouble Shooting Problem Solution check NoOut...

Страница 8: ...IS 500T5220 Litho in USA Rev M 06 07...

Отзывы: