If Density mode is selected the tank should be full in normal operation and user must determine
the level unit, density unit, transmitter position (h₀), the tank total height (H), low density value
equivalent to 4.0mA output (LRV) and high density value equivalent to 20.0mA output (HRV).
Configuration of tank application is performed via following parameters:
3.2.6.1
Level unit
User can select the tank level unit using this parameter.
parameter
display
Parameter tuning structure
Level Unit
(set the unit of
level)
Press <M> until this page is appeared on LCD. Then press
<Z> to access the units (programing mode). You can select
the unit by pressing <S>. After that, press <Z> until all
characters blink. Then press <M> for the saving new
parameter and switching from programing mode to
operation mode.
The available units for tank level are:
CM
[centimeter]
FEET
[feet]
INCH
[inch]
METER
[meter]
MM
[millimeter]