4.4.
Rack Grounding
Ground terminals of racks in one room should be separately connected to protective are copper bar
provided by side board. And ground wire should be as far as possible short. If the wire is too long
when installing, please cut off to avoid ground wire coiling. The sectional area of guide line of ground
terminal row must be greater than or equal to 25mm2.
4.5.
Equipment Grounding
When grounding, use guide line to connect protective area binding post to the protective ground wire
row of assembly rack.