Remote modules. RIO5, RIOW and RIOR series.
CNCelite
8058 8060
8065 8070
RIOW REMOTE MODULES.
(CANOPEN PROTOCOL).
4.
Inst
allat
ion of
the modules.
ꞏ55ꞏ
R
EF
. 2107
4.4
Installation of the modules.
Place the modules on 1 profile, according to the European regulation EN50022 (DIN 35),
with 2 securing ends, one at each end of the group to help secure the modules. RIOW series
modules may be mounted horizontally or vertically; when mounting them vertically, use
additional mounting blocks at the bottom to secure the modules.
Ground connection.
Modules are connected to ground via the profile. Profiles, on which the profiles are mounted,
must always be connected to the ground plate of the electrical cabinet. To connect the profiles
to ground, use a cable with a minimum section of 4 mm². To ensure contact between the
profile and the modules, the material of the profile must not be corrosive.
At the RIOW-PS24 module, the ground connection is done through the bottom pins of the
module. The ground connection is extended to the adjacent modules through the side
jumpers of the module.
Shield connection.
Proper shielding of the signal and data cables reduces interference and improves signal
quality while preventing measuring and data transmission errors. The cables must be
continuously shielded to ensure compliance with the technical specifications related to
measuring accuracy.
Ambient characteristics of the enclosure.
The temperature of the cabinet (enclosure) where the modules are mounted must not exceed
55 ºC (131ºF) when the modules are working. The heat dissipated by all the modules must
not exceed the heating capability of the cabinet where they are installed.
DO NOT make any connection or connect any module or cable if the group is under power. Before
making any connection, disconnect the power supply cable of the leading (first) module
(RIOW-CANOPEN) and, if necessary, that of the power supply module (RIOW-PS24).
Profiles with modules must always be connected to the ground plate of the electrical cabinet.
Element
Dissipated power
Leading (first) module.
2.0 watts.
Rest of modules.
0.8 W per module.
Содержание CNC 8065elite T
Страница 1: ...Ref 2107 8058 8060 8065 8070 CNCelite Remote modules RIO5 RIOW and RIOR series...
Страница 6: ...Remote modules RIO5 RIOW and RIOR series CNCelite 8058 8060 8065 8070 6 REF 2107...
Страница 12: ...Remote modules RIO5 RIOW and RIOR series CNCelite 8058 8060 8065 8070 12 REF 2107...
Страница 14: ...Remote modules RIO5 RIOW and RIOR series CNCelite 8058 8060 8065 8070 14 REF 2107...
Страница 18: ...Remote modules RIO5 RIOW and RIOR series CNCelite 8058 8060 8065 8070 18 REF 2107...
Страница 20: ...Remote modules RIO5 RIOW and RIOR series CNCelite 8058 8060 8065 8070 20 REF 2107...
Страница 22: ...Remote modules RIO5 RIOW and RIOR series CNCelite 8058 8060 8065 8070 22 REF 2107...
Страница 24: ...Remote modules RIO5 RIOW and RIOR series CNCelite 8058 8060 8065 8070 24 REF 2107...
Страница 26: ...Remote modules RIO5 RIOW and RIOR series CNCelite 8058 8060 8065 8070 1 PREVIOUS INFORMATION 26 REF 2107...
Страница 28: ...Remote modules RIO5 RIOW and RIOR series CNCelite 8058 8060 8065 8070 2 HARDWARE STRUCTURE 28 REF 2107...
Страница 125: ...Remote modules RIO5 RIOW and RIOR series CNCelite 8058 8060 8065 8070 125 User notes REF 2107...
Страница 126: ...Remote modules RIO5 RIOW and RIOR series CNCelite 8058 8060 8065 8070 126 User notes REF 2107...
Страница 127: ...Remote modules RIO5 RIOW and RIOR series CNCelite 8058 8060 8065 8070 127 User notes REF 2107...