During this operation, the gate moves very slowly at the minimum speed rate as factory pre-set.

- Press and hold  the button        (or give an Open command): the automation operates to Open on deadman control mode.

- Let the gate travel to the limit switch Open, release the button and press 

ENTER

  to confirm. (To reduce the gate travel on to the Open limit switch, should the gate

  over travel the limit position, press the button        and then confirm).

NOTE WELL

:

- Should the gate run into an obstacle ( eg. stones, etc. ...) during the open or close cycles, the automation stops on expiring of the pre-set time. Any new

  command will reverse the gate motion to the next limit switch, at the minimum speed as factory pre-set. The subsequent operations are carried on following

  the settings that are pre-set during the installation.

- After a power failure, when the board is powered back with voltage supply, the automation carries on the first operation at the minimum speed as factory

  pre-set, provided that none of the limit switches is engaged. No memorizing is required. All previous settings are retained.

11

   Function Automatic-Semiautomatic

- Deadman control

DISPLAY

SCREEN 5

DISPLAY

SCREEN 6

mode of use................

Automatic

Ø

Ø.ØHz     Ø sp

door Closed! ....

Button 

ENTER

 , to enter the function

Button

, to select the operating mode

Ø = Automatic

, on an opening comand impulse, the gate Opens, stops for a pre-set Dwell time (see screen 7),

when it’s expired It closes automatically.

1 = Semiautomatic

, on an opening command impulse the gate opens and stays open. A closing command

impulse is needed to close it.

2 = Deadman control

, Open and Close operations are by “hold on switched” control (no relay self-holding is

involved). The automation is to be attended and  the command unit is required to be held switched to achieve

gate operation. Any operation is stopped on releasing the button or key.
Once selected the mode press 

ENTER

 to confirm

radio:   

REVERSES

Ø

   Radio function

Button 

ENTER

 to enter the function

Button

to select the operating mode:

0 = Radio reverses on opening

1 = Radio step-by-step with intermediate Stop

2 = Radio doesn’t reverse on opening

Once selected the mode press the 

ENTER

 button to confirm

   Status of the automation

It is visualized the status of the automation when power is supplied: door in stop (closed) position.

DISPLAY

SCREEN 4

   Memorizing

   the gate travel

Once all the electrical connections are completed, with the 

gate in closed position

 (limit switch Close engaged) make sure the

electric motor turns in the correct direction in  relation to the limit switches. During this phase, it is advisable to set the torque

at a suitable rating to prevent the clutch from slipping while the unit is learning ie storing this setting (a high rating is advisable).

SCREEN 4.1

RESET

ENTER

RESET

ENTER

Max course quote

   Ø

   1ØØØ

DISPLAY

RESET

ENTER

RESET

ENTER

RESET

ENTER

7

3

COMMON

RADIO

Drwg. No.

4534

GB

220

THREE-PHASE

THREE-PHASE FOR AUTOMATIONS WITH

HEAVY SLIDING GATES - DIGITAL PROGRAMMING

®

Содержание Elpro 220

Страница 1: ...IGNALISIERUNG DES ZUSTANDS DER AUTOMATION GESCHWINDIGKEITSEINSTELLUNG GEHTÜRFUNKTION BETRIEBSANLEITUNG FÜR DREIPHASIGE AUTOMATIONEN AUF SCHIEBETOREN MIT DIGITALER PROGRAMMIERUNG 220 Seite 1 3 19 20 21 22 23 MANUEL D INSTRUCTION 220 page 1 2 14 15 16 17 18 INSTRUCTIONS 220 page 1 2 9 10 11 12 13 LIBRETTO DI ISTRUZIONI 220 PER AUTOMAZIONI TRIFASE SU CANCELLI SCORREVOLI A PROGRAMMAZIONE DIGITALE AUTO...

Страница 2: ...ico Uomo Presente Schermata 6 Funzione Radio Schermata 7 Tempo di pausa in modalità Automatico Schermata 8 Fotocellule 1ª coppia morsetti 1 e 2 Schermata 9 Regolazione Forza a bassa velocità Schermata 10 Regolazione Forza alla velocità di lavoro Schermata 11 Fotocellule 2ª coppia morsetti 25 e 26 Schermata 3 Stato dell impianto Schermata 12 Impostazione velocità Schermata 13 Passaggio pedonale Sch...

Страница 3: ...e control panel with a 0 03A high performance magnetic thermal circuit breaker Verify that the power supply to the electronic control panel is 230V 10 50Hz For power supply to the electric motor 230V 10 50Hz use 2 5 mm section wires to 50 m distances and set the motor terminal board for 230V power supply Power supply Flashing lamp use cables with 1 5 mm section wires up to 50m of distance for limi...

Страница 4: ...ence of an obstacle Cs2 Safety rubber strip 2 on closing zero Ø 1 presence of an obstacle Safety strips reverse gate travel in case of an obstacle the gate stops and waits for a new command DISPLAY SCREEN 2 Status of the system O Open Open button zero Ø 1 during the impulse C Close Close button zero Ø 1 during the impulse S Stop Stop button zero Ø 1 during the impulse SwO Opening limit switch zero...

Страница 5: ...see screen 7 when it s expired It closes automatically 1 Semiautomatic on an opening command impulse the gate opens and stays open A closing command impulse is needed to close it 2 Deadman control Open and Close operations are by hold on switched control no relay self holding is involved The automation is to be attended and the command unit is required to be held switched to achieve gate operation...

Страница 6: ... travel on Closing This function is operating in Automatic and Semi automatic modes screen5 Once selected the mode press ENTER button to confirm boost HIGH boost 80 photo2 mode Immediate STOP DISPLAY DISPLAY MAX motor speed SPEED 40 0 Hz DISPLAY SCREEN 10 SCREEN 11 SCREEN 12 Photocells 1st pair terminals 1 and 2 Button ENTER to enter the function Button to select the operating mode Ø Photocell doe...

Страница 7: ...facturer not controllable by user Insert Password Ø 13 Visualization display Voltage motor absorption temperature on dissipator plate It may happen that the control board enters a thermal protection phase and the electric motor is no longer powered until the fan has sufficiently cooled it down to normal functioning condition Check proper fan operation it must turn with gate moving and temperature ...

Страница 8: ...ité de Meccanica Fadini Vor der Installation durch qualifiziertes tecnisches Personal wird empfohlen das Handbuch zu den Sicherheitsvorschriften durchzulesen das die Meccanica Fadini zur Verfügung stellt Antes de la instalación por parte del personal técnico cualificado se aconseja consulter el Libreto con las Normativas de Seguridad que Meccanica Fadini pone a disposición Vor der Installation dur...

Отзывы: