TROUBLE SHOOTING 

 

 

PROBLEMS 

CAUSES 

REMEDIES 

ALTERNATOR EXCITATION 

FAILURE

 

1.

 

Low Speed

 

 

2.

 

Faulty capacitor

 

3.

 

Faulty winding

 

1.

 

Check RPM and set at nominal 

value. 

2.

 

Check and replace. 

3.

 

Check that winding resistance is 

as shown in the tables. 

 

HIGH NO-LOAD VOLTAGE

 

1.

 

Speed too high. 

2.

 

Capacitor with high capacity.

 

1.

 

Check and adjust RPM’s 

2.

 

Check and replace

 

LOW NO-LOAD VOLTAGE

 

1.

 

Speed too low. 

2.

 

Faulty rotary diodes. 

3.

 

Breakdown in windings.

 

 

4.

 

Capacitor with high capacity.

 

 

1.

 

Check and adjust RPM’s 

2.

 

Check and replace. 

3.

 

Check winding resistance, as 

per tables. 

4.

 

Check and replace. 

 

PROPER NO-LOAD BUT LOW 

LOADED VOLTAGE

 

1.

 

Low loaded speed. 

2.

 

Load too large. 

3.

 

Rotary diodes short-circuited 

 

1.

 

Check and regulate RPM. 

2.

 

Check and change. 

3.

 

Check and replace. 

 

UNSTABLE VOLTAGE

 

1.

 

Loose contacts. 

2.

 

Uneven rotation.

 

 

1.

 

Check connections. 

2.

 

Check for uniform rotation 

speed. 

 

NOISY GENERATOR

 

1.

 

Broken bearings. 

2.

 

Poor couplings.

 

 

1.

 

Replace. 

2.

 

Check and repair. 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Содержание HYDRO 350X-50HZ

Страница 1: ...er Instruction Manual for Model HYDRO 350X 50HZ 2 WIRE Hydraulic Generator Manufacturing of Vehicle Mounted Generators Hydraulic Generators P O Box 582 Chester NY 10918 845 469 9151 Fax 845 469 7871 W...

Страница 2: ...120 240 MOTOR STARTING 300 SURGE VOLTAGE REGULATOR INHERENT OUTPUT 3500 WATTS CONTINUOUS AT 100 F OIL TEMPERATURE HYDRAULIC MOTOR GEAR TYPE WITH BUILT IN FLOW CONTROL FLOW CONTROL PRESSURE COMPENSATIO...

Страница 3: ...gh back pressure can be caused by spikes sent back through the return from other equipment on a common return line Another potential problem can develop if several pieces of equipment are connected to...

Страница 4: ...cal load on the generator By using this setting you will have approximately 50HZ cycles or 3000 RPM when you are running at full rated load One way this can be accomplished is by using a Photo Tachome...

Страница 5: ...at the load Drive motor speed control systems generally have a small drop in speed between no load and loaded conditions We therefore recommend setting no load speed 3 4 above nominal speed CHECKING V...

Страница 6: ...OV25 ERLOAD SELF RE SETTING GROUND SCREW ON GENERATOR FRAME USE GREEN WIRE FOR GROUND IF USING GFCI OUTLETS U2 V2 V1 W1 CONNECT NEUTRAL TO GROUND IF USING GFCI OUTLETS NEUTRAL WHITE 240 RED OR BLACK W...

Страница 7: ...572066 Coupling 24mm 22 572067 Spider 23 572068 Coupling 24 572173 Motor w Flow Control 25 572128 Rails 26 572154 Mounts 27 572206 Flow Control Cartridge 28 572261 Stud Cover PART OPTIONAL CONTROL PA...

Страница 8: ...lace LOW NO LOAD VOLTAGE 1 Speed too low 2 Faulty rotary diodes 3 Breakdown in windings 4 Capacitor with high capacity 1 Check and adjust RPM s 2 Check and replace 3 Check winding resistance as per ta...

Страница 9: ...INE FILTER 8 OIL COOLER 9 HYDRAULIC FLUID RESERVOIR Some units may be equipped with integral priority flow control refer to specific model number External case drain line may be required on some units...

Страница 10: ...Fabco Power Instruction Manual Page 10 BRUSHLESS GENERATOR WIRING...

Страница 11: ...Fabco Power Instruction Manual Page 11 HYDRAULIC MOTOR HOSE HOOK UP Fabco Power...

Страница 12: ...Fabco Power Instruction Manual Page 12...

Страница 13: ...Fabco Power Instruction Manual Page 13...

Отзывы: