3
E550
SLAVE
ENGLISH
5 ELECTRICAL CONNECTIONS
MOTOR
Fig. 3
Fig. 2
5.1.1 TERMINAL BOARD J1 (high voltage)
Terminal board for 230V~ 50Hz (L= Phase N=Neutral)
power supply.
Connect earth of electrical system and earth cable of the
operator to terminal “PE”.
5.1.2 TERMINAL BOARD J2 (high voltage)
230V~ Terminal board for connection of:
Motor:
connect the motor phases (Black and Brown ca-
bles) to the OP and CL terminals. Connect the
common contact (Blue cable) to terminal COM.
Connect the thrust condenser in parallel with
respect to the phases.
Flashing lamp:
connect a flashing lamp with max power
of 60W between terminals 15 and 16.
Courtesy light
: connect the courtesy light of the SLAVE board
between terminals 14 and 16, or connect the
external lights with max. overall power of 250W
between these terminals.
5.1.3 TERMINAL BOARD J3 (low voltage)
1 = = inputs common contact /Negative of accessories supply
2 = = inputs common contact /Negative of accessories supply
3 = = Positive for powering 24Vdc ( ) accessories.
Max accessories load: 300mA.
To calculate absorption values, refer to the
instructions for individual accessories.
4 = -FSW TX = Negative for power supply to photocell transmitters.
Separate connection of the negative pole of the transmitters
makes it possible to use the Failsafe control on the photocells,
thus increasing the system’s safety level. If the Failsafe control
is disabled, the terminal is a negative for supply to accessories.
5 = FCA = Opening Limit switches contact (N.C.).
The opening limit switch consists of a micro-pushbutton
which, activated by the cam when the door reaches open
position, stops movement immediately or, according to
programming, after 3 sec.
6 = FCC = Closing limit switches contact (N.C.).
The closing Limit switch consists of a micro-pushbutton
which, activated by the cam when the door reaches clo-
sed position, stops movement immediately or, according
to programming, after 3 sec.
For control unit operation, both the limit switches
MUST BE connected.
7 = FSW OP = Opening Safety devices contact (N.C.)
Safety devices are all devices (photocells, sensitive ed-
ges,…) with N.C. contact, which, if there is an obstacle in
the area they protect, operate by stopping or reversing
the door opening movement (see chap.7.4 - Advanced
programming).
They have no effect during the closing stage.
If the opening safety devices are engaged while the door
is closed, they inhibit any Open pulse.
To install several safety devices, connect the N.C. contacts
in series.
If no opening safety devices are connected,
jumper connect “FSW OP” to terminal 4.
5.1 DESCRIPTION OF CONNECTIONS
MOTOR
MOTOR
THRUST
CAPACITOR
Single motor
Double motor
EXTERNAL
COURTESY LIGHT
O P E N I N G
SAFETY DEVICE
CONTACT
FLASHING LAMP
THRUST
CAPACITOR
FLASHING LAMP
ENCODER
BROWN
BLUE
BL
ACK
THRUST
CAPACITOR