Programming Gate Run Times
In this stage, your control board will memorize where your limits are (identified by limit
switches, positive stops or both) in both opening and closing phases. Also if the auto-close fea-
ture is activated it will learn the user specified pause time.
FOR SAFETY PURPOSES—your opener will not run until this step is completed
1)
Release the operator gears using the manual release
process. Once released, manually move the gate(s) half
way between the open and close stop points.
2)
Relock the
operator gears at the half way point
through its cycle. Verify your operator control
board is showing on the LED display.
3)
Press and hold down
P2
until the LED display shows
the A parameter and the relevant number appear in the
LED display.
4)
Give an
OPEN A
command. This can be done with any
opening device (keypad, push button, etc…) wired into OPEN A and COM or using the transmit-
ter. You can also briefly (one second or less) jump OPEN A and COM with a wire. This will begin
your gate in the
CLOSING DIRECTION and the LED display will read “Pr”.
IMPORTANT:
If the gate(s) begin to open ra-
ther than close, the gate(s) must be stopped with a
reset pulse.
You can either
:
Touch the TWO pins of the JMP “RESET” using a screwdriver
OR
Disconnect all power (transformer and backup battery)
Then switch the wires leading into APM1-CHM1 (if Dual Operator APM2-CHM2 also) and then
begin programming again.
5.4
Example:
Single Leaf