Preventing draughts in spaces with two doors, thermal interlock

If  there is a problem with draughts, doors can be blocked so that only one can be opened at a time. The door will not 

open before the other linked door is closed.

Configuration for the above example with programmable input INP1:

• 

Door 1, C614 = 1, P160 = 1, P190 = 1, C500/C501 = suitable automatic closing time.

• 

Door 2, C614 = 1, P160 = 1, P190 = 1, C500/C501 = suitable automatic closing time.

Channel C615 is used to choose whether the door concerned is to remember an opening signal when the door concerned 

cannot be opened because the other door is blocking opening.

Directional thermal interlock

A thermal interlock can also be directional, i.e. the interlock works from one direction but not the other.

Example: When door 1 is operated using the programmable input, door 1 opens and then closes using the automatic 

closing time, then door 2 opens automatically and closes using the automatic closing time. When approached from the 

other direction, however, doors 1 and 2 open at the same time.

Setting for the above example with programmable input INP1:

• 

Door 1, C614 = 1, P190 = 1, P196 = 1.

• 

Door 2, C614 = 1, P190 = 1.

Channel list

Interlock block

No. 

Name

Range

Factory Setting

C600

Choice of communication

0 – 2

0

0

Disabled

1

Interlock

2

Simply connect

C610

Choice of unit address

1 – 2

2

C614

Block of local door

0 – 3

0

0

No blocking, opens and closes independently of the position of the remote door 

1

Blocking of open on local door until remote door is closed

2

Blocking of open on local door until remote door is open

3

Blocking of close on local door until remote door is closed

C615

In blocking of local door

0 – 3

3

0

Local door does not remember open, stop does not cancel blocking of remote door

1

Local door remembers open, stop does not cancel blocking of remote door

2

Local door does not remember open, stop cancels blocking of remote door

3

Local door remembers open, stop cancels block of remote door

Programmable input, INP1-6

No. 

Name

Range

Factory Setting

Pn90

Interlock opening

0 - 1

0

n=1-6

0

Disabled

1

Opens the local door if Pn60 is set to open, and passes the signal on to the remote door

Pn96

Blocking disabled for local and remote doors. Works only 

with a constant signal.

0 - 1

0

n=1-6

0

Disabled, function according to channel C614

1

Blocking disabled

Pn98

Automatic closing switched off for remote door. 

Only works if there is a constant signal 

0 - 1

0

n=1-6

0

Disabled, function according to channel C500

1

Automatic closing switched off