Connection

To optimise communication between two EP105s, it is important to choose the right cable and to route it correctly. A 

suitable cable is FQAR-PG 2X0,5, E0182120. Otherwise use a twisted pair shielded cable with a conductor cross sectional 

area of at least 0.2 mm

2

 and a capacitance of 50-70 pF/m. 

Connect the shield at one end onlyto DB512 terminal 1. At the other hand, trim off the shield after the cable insulation. 

The cable length must not exceed 1000 metres. 

 

Connection must be performed by a qualified technician. 

 

 

When the card has been installed and connected, the power supply to EP105 can be switched 

on.