10 OPERATION

Make the electrical connections on the 950 I/O control board 
as shown in section 8, connect the electrical mains supply 

to the corresponding terminal (ig.l-ref.

 j

 ) and ensure that 

the earthing cable is crimped to the terminal (ig.1-ref. 

) screwed on to the support proile (ig.l-ref. 

b

 ). Finally, 

tighten the terminal (ig.l-ref. 

)

Set the trimmer (see ig.5) and program the micro-switches 

(see fig.4 and 6) depending on need. To access the 
equipment, run the cables through the provided conduit 

(ig.l-ref. 

) or open the tabs on the sides of the housing.

   IMPORTANT:  When installing a sliding 

arm or for opening greater than 90° , before 
powering the system, set micro-switch nr. 
2 of the 950 MPS to ON.

2) Place the door in close position.
3) Power the operator.
4) Ensure that green LEDs LD1 and LD3 on the 950 MPS 
board are ON.
5) Ensure that the status LEDs on the 950 I/O board are in 

default status, as shown in the table in igure 6.

6) Perform a SET-UP cycle, as described in paragraph 10

10.1 SET-UP  PROCEDURE

  It is advisable to repeat the set-up 

procedure after having modified the 
opening and closing speed.

With the automated system powered, press SW1 (950 I/0)  
for at least 5 sec. until the red LED LD2 located on the 950 

MPS board is ON. The LED will begin lashing indicating 

that the SET UP procedure is in progress. During this 
procedure the following parameters are adjusted:
- door mass measurement;

- identiication of the limit switch positions;

The door will open at reduced speed and will close 
approximately half way and then reverse to opening.
Closing is determined by the spring return action.
The process is inhibited in one of the following conditions:
1.  Mode selector switch in position 2 (MANUAL/NIGHT) or 

KP-CONTROLLER programmer in  MANUAL or NIGHT 
position

2.  Accessories connected incorrectly (electric lock, command/

safety elements);

3.  Incorrect position of the programming unit micro-switches.

  To repeat the set-up process, press SW1 for 

more than 5 seconds. Once the procedure is completed, 
ensure that the door opens and closes correctly.

  If a KP controller is used, the procedure can be 

performed directly from it.

Содержание 950N

Страница 1: ...950 N...

Страница 2: ...950N 1 732708 Rev B BRACCIO ARTICOLATO ARTICULATED ARM BRAS ARTICUL BRAZO ARTICULADO GELENKARM KNIKARM a a b c d e f f h a g a c c a OPEN OPEN...

Страница 3: ...o increase the distance between the operator and the arm use the optional extensions dimension with 50 mm shaft 87 mm with 80 mm shaft 117 mm Cote avec arbre standard de 20 mm S il est n cessaire d au...

Страница 4: ...operador y el brazo utilizar los alargues opcionales Cota con rbol 50 mm 87mm Cota con rbol 80 mm 117 mm Ma mit Standardwelle 20 mm Wenn der Abstand zwischen dem Antrieb und dem Arm erh ht werden muss...

Страница 5: ...950N 4 732708 Rev C BRACCIO A PATTINO SLIDING ARM BRAS PATIN BRAZO DE PAT N GLEITKUFENARM ARM MET GLIJSCHOEN a a b e d d f f g i h j k OPEN...

Страница 6: ...necessary to increase the distance between the operator and the arm use the optional extensions dimension with 50 mm shaft 107 mm with 80 mm shaft 137 mm Cote avec arbre standard de 20 mm S il est n c...

Страница 7: ...ssary to increase the distance between the operator and the arm use the optional extensions dimension with 50 mm shaft 107 mm with 80 mm shaft 137 mm Cote avec arbre standard de 20 mm S il est n cessa...

Страница 8: ...st be checked as speciied in the Standards indicated at point 10 16 The safety devices EN 12978 standard protect any danger areas against mechanical movement Risks such as crushing dragging and sheari...

Страница 9: ...seconds Closing time adjustable from 4 to 10 seconds Accessories power supply Electric lock power supply 24 V 1000mA max Operating modes by selector switch Open Automatic Manual or Night Pause time a...

Страница 10: ...80 mm optional 3 APPLICATION LIMITS LEAF LENGTH mm MAX LEAF WEIGHT Kg ARTICULA TED PUSH ARM SLIDING ARM L 330 mm SLIDING ARM L 430 mm 700 367 286 750 320 249 800 281 219 850 249 194 900 222 173 950 1...

Страница 11: ...mplates 4 2 INSTALLING THE TRANSMISSION ARMS It is always advisable to adjust the mechanical stops inside the opening closing operator so that they are occupied when the leaf reaches its mechanical st...

Страница 12: ...LLER programming unit optional 6 KP CONTROLLER locking key switch optional 7 Electric lock 24V max 0 5 A 8 Shunt box In case of operator on door installation make all electrical connections using a sh...

Страница 13: ...n opening direction it will open 5 Leaf delay at opening master slave application Disabled Enabled 6 Not used 7 STOP safety detection space Terminal 14 950 I O board Active during the entire stroke Ac...

Страница 14: ...rogress Slow lashing active fault LD3 Green LED for 5 V power supply 950 MPS BOARD TRIMMERS TR 1 Opening time adjustment 4 10 seconds TR 2 Closing time adjustment 4 10 seconds TR 3 Pause time adjustme...

Страница 15: ...nput 13 LD7 Closing phase safety not occupied Closing phase safety occupied Signals the status of input 14 LD8 Key command active Key command not active Signals the status of input 15 LD9 Fire prevent...

Страница 16: ...pen door 12 Emergency command normally closed contact If open it commands door closing the mode can be modiied using the KP controller 13 Safety command during closing phase normally closed contact If...

Страница 17: ...OMMAND n o EMERGENCY COMMAND n c SAFETY COMMAND DURING CLOSING n c STOP COMMAND DURING OPENING AND CLOSING n c KEY COMMAND n o FIRE PREVENTION COMMAND n o CARD READER COMMAND GND GND 8 950 I 0 BOARD E...

Страница 18: ...Tx Rx J4 J5 J4 ENGLISH ITALIANO PB SENSOR PHOTOCELLS ELECTRIC LOCK 24 V 8 2 SAFETY INPUTS 8 3 ELECTRICAL LOCK COMMAND OUTPUT TX PHOTOCELLTRANSMITTER RX PHOTOCELL RECEIVER PB SENSOR STOP SENSOR N O 950...

Страница 19: ...es when the door is open CLOSED DOOR N O CONTACT Closes when the door is closed BOARD FAULT OUTPUT N O CONTACT It closes when an automated system fault is active 8 4 ELECTROMAGNET COMMAND OUTPUT 8 5 D...

Страница 20: ...the pause time 2 DIP N 3 ON MANUAL The door can be opened manually the lock if present will remain inactive 2 DIP N 3 OFF NIGHT The external and internal commands are inactive Door opening can be com...

Страница 21: ...ET UP cycle as described in paragraph 10 10 1SET UP PROCEDURE It is advisable to repeat the set up procedure after having modified the opening and closing speed With the automated system powered press...

Страница 22: ...21 732708 Rev C 530 105 160 mm 530 107 121 mm ENGLISH 11 ASSEMBLINGTHEHOUSING 11 1 ASSEMBLINGTHEPLASTICHOUSING HOUSING FIXING SCREWS 11 2 ASSEMBLINGTHEALUMINIUMHOUSING HOUSING FIXING SCREWS Fig 18 Fi...

Страница 23: ...s done by pressing the keys located on the ixed section of the programmer the mode is identiied by the lighting of the corresponding LED Note once the Night or Manual modes have been set the correspon...

Страница 24: ...LIA PTY LTD Homebush Sydney Australia tel 61 2 87565644 www faac com au INDIA FAAC INDIA PVT LTD Noida Delhi India tel 91 120 3934100 4199 www faacindia com SWITZERLAND FAAC AG Altdorf Switzerland tel...

Отзывы: