2. DIMENSIONS

3. ELECTRIC EQUIPMENT (standard system)

To make the connections efficiently, allow the cables to
project by about 40 cm from the hole (Figs.5-6 ref.

) of the

foundation plate.

4. INSTALLATION OF THE AUTOMATED SYSTEM

4.1.

PRELIMINARY CHECKS

To ensure safety and an efficiently operating automated system,
make sure the following conditions are observed:

The gate structure must be suitable for automation. The following
are necessary in particular: wheel diameter must be in proportion
to the weight of the gate to be automated, an upper guide must
be provided, plus mechanical stop limits to prevent the gate
derailing.

The soil must permit sufficient stability for the foundation plinth.

There must be no pipes or electric cables in the plinth excavation
area.

If the gearmotor is exposed to passing vehicles, install, if possible,
adequate means of protection against accidental impact.

Check if an efficient earthing is available for connection to the
gearmotor.

4.2.

MASONRY FOR FOUNDATION PLATE

1) Assemble the foundation plate as shown in figure 4.
2) The foundation plate must be located as shown in figure 5 (right

closing) or figure 6 (left closing) to ensure the rack and pinion
mesh correctly.

3) Prepare a foundation plinth as shown in fig.7 and wall the

foundation plate, supplying one or more sheaths for routing
electric cables. Using a spirit level, check if the plate is perfectly
level. Wait for the cement to set.

4) Lay the electric cables for connection to the accessories and

power supply as shown in figure 3.

4.3.

MECHANICAL INSTALLATION

1) Assemble the securing corners and anti-vibration spacers on

the operator as shown in Fig. 8.

2) Open the cover, unscrewing the securing screws.
3) Place the operator on the plate, using the supplied washers and

nuts as shown in Fig. 9.
During this operation, route the cables through the duct inside
the lower half-casing of the operator (Fig.10 - Ref. A).
To access the electronic equipment, route the cables through
the appropriate hole, using the supplied rubber cable-clamp.
Make absolutely sure to unsheathe all the cables so that the
clamp holds single cables only (Fig.10 - Ref. B).

Operator 746
with 780D equipment

Photocells

Key-operated push-button

Flashing lamp

Radio receiver

Содержание 746 ER CAT

Страница 1: ...ta 100 per la natura for nature recycled paper 100 ist umweltfreundlich 100 Altpapier para la naturaleza 100 papel reciclado papier recyclÈ 100 pour la nature voor de natuur 100 kringlooppapier 746ER 780D 746ER 780D ...

Страница 2: ...its tripping threshold must be checked as specified in the Standards indicated at point 10 16 The safety devices EN 12978 standard protect any danger areas against mechanical movement Risks such as crushing dragging and shearing 17 Use of at least one indicator light e g FAACLIGHT is recommended for every system as well as a warning sign adequately secured to the frame structure in addition to the...

Страница 3: ...refore nolockneedstobe installed The gearmotor is equipped with a mechanical clutch which combinedwithanelectronicdevice offersthenecessaryadjustable anti crushingsafetyandguaranteesstoppingorreversingthegate movement Ahandymanualreleasemakesitpossibletomovethe gate in the event of a power cut or malfunction The electronic control equipment is equipped with a gearmotor and is housed insidetheopera...

Страница 4: ...ION PLATE 1 Assemble the foundation plate as shown in figure 4 2 Thefoundationplatemustbelocatedasshowninfigure5 right closing orfigure6 leftclosing toensuretherackandpinion meshcorrectly 3 Prepare a foundation plinth as shown in fig 7 and wall the foundation plate supplying one or more sheaths for routing electriccables Usingaspiritlevel checkiftheplateisperfectly level Waitforthecementtoset 4 La...

Страница 5: ...n and place the spacer between the rack and the gate positioningitatthetopoftheslot 3 Markthedrillingpointonthegate Drill a Ø 6 5 mm hole and apply thread with a Ø 8 mm male tap Screwthebolt 4 Movethegatemanually checking if the rack is resting on the pinion andrepeattheoperationsatpoint 3 5 Bringanotherrackelementneartothepreviousone usinga pieceofrack asshowninfigure16 tosynchronisetheteethof th...

Страница 6: ... 5 1 MOD 746 ER CAT Figs 18 19 1 Insert the spring pin on the shaft using a hammer 2 Fit the chain pinion on the shaft making the pinion seats coincide with the spring pin and tighten the screw with the appropriate washers Fig 17 4 5 2 MOD 746 ER RF Figs 20 21 1 Insert the spring pin on the shaft using a hammer 2 Fit the idle transmissions bracket on the gearmotor flange using the four screws M5 x...

Страница 7: ...rom 0 to 4 1 min Thrust force Adjustableover50levels Terminal board inputs Open PartialOpen Openingsafetydevices Closingsafety devices Stop Edge Powersupply Earth On connector inputs Opening and closing limit switch Motorcapacitor Terminal board outputs Flashinglamp Motor 24Vdcaccessoriespowersupply 24Vdcindicator light Timedoutput Electriclockcommand trafficlights Fail safe Rapid connector 5 pinc...

Страница 8: ...retrippedduringthegateopening and closing movements They cause immediate reversal of motion and stopping after two seconds Encoder it is tripped if there is an obstacle during gate opening and closing movements It causes immediate reversal of motion and stopping after two seconds N B If two or more safety devices have the same function opening closing opening and closing edge the contacts must be ...

Страница 9: ...g 33 Fig 32 Fig 29 Connection of a pair of closing photocells Connection of a pair of opening photocells Connection of a pair of opening photocells a pair of closing photocell and an edge safety device Connection of a pair of closing photocells a pair of opening photocells and a pair of opening closing photocells Connection of two pairs of closing photocells and two edge safety devices ...

Страница 10: ...erminal5 anydevice e g apush button which byopeningacontact stopsgatemovement ToinstallseveralSTOPdevices connecttheN C contacts in series fig 25 NB IfSTOPdevicesarenotconnected jumperconnect the STOP and terminals SAFE EDGEsafetydevicecontact terminal6 Thepurposeofthe edge safetydeviceistoprotecttheleafmovementarea duringopening closing Inalllogics duringopeningand closing the safety device rever...

Страница 11: ... ref to the equipment 5 5 PROGRAMMING To program operation of the automated system access the PROGRAMMING modewith keysF and andusingthedisplay ontheequipment Attention before attempting to power up the system we advise you to re position the equipment s cover to avoid coming into contact with high voltage parts and to use the push buttons on the cover to activate the keys fig 39 BASICPROGRAMMING ...

Страница 12: ...thisfunctionisactivated itenablesafunction test of the photocells before any gate movement If the test fails photocells not serviceable signalled by value on the display thegatedoesnotstartmoving Active Disabled PRE FLASHING 5s Activatestheflashinglampfor5secondsbefore startofmovement Disabled Only before opening Only before closing Before every movement CLOSINGPHOTOCELLSLOGIC Select the tripping ...

Страница 13: ...ecision Deceleration disabled from to Deceleration enabled Post limitswitchDECELERATION You can select gate deceleration after the openingandclosinglimit switcheshavebeen tripped Time can be adjusted from to in 0 1 secondsteps If an encoder is used the adjustment is not determined by time but by motor revs thus obtaining greater deceleration precision Deceleration disabled from to Deceleration ena...

Страница 14: ...p point If necessary correct the position of the magnets andcheckifthestoppointiscorrect 9 Mark the position of the magnets on the rack and remove them 10 Clean the rack on its fitting points remove the film on the adhesivepartsofthemagnets fig 41ref 1 andre positionthe magnetswiththeadhesivestripincontactwiththerack fig 41 ref 2 6 3 2 Inductivelimit switch Operator 746 has an inductive limit swit...

Страница 15: ...rface of the nylon rack Therefore drill until you reach the steel core and screwwiththeself tappingscrews 6 5 CHECK OF MOTOR CONNECTION Check if the motor wiring is as shown in Fig 43 stan dard connection LEDS LIGHTED OFF OP A Commandactivated Command inactive OP B Commandactivated Command inactive FC1 Limit switch free Limit switchengaged FC2 Limit switchfree Limit switch engaged FSW OP Safety de...

Страница 16: ...ntrol unit to it Fig 50 Forconnectionandoperation refertothespecificinstructions 11 SPECIALAPPLICATIONS Therearenospecialapplications 12 MAINTENANCE Check the operational efficiency of the system at least once every 6 months especially as regards the efficiency of the safety and release devices including operator thrust force 12 2 OIL TOP UPS Periodically check oil level inside the operator Aonce ...

Страница 17: ... i t n o c e s a e l e r n o d n a s k c o L g n i n e p o 2 2 r o f e s o l c o t s e s r e v e R D E K C O L 3 f a e l e h t s e s o l C t c e f f e o N d e l b a s i d N E P O t c e f f e o N t c e f f e o N d e l b a s i d N E P O Tab 3 c E c i g o L S E S L U P S U T A T S E T A G A N E P O B N E P O P O T S S E C I V E D Y T E F A S G N I N E P O S E C I V E D Y T E F A S G N I S O L C E C I...

Страница 18: ...o f n e p o o t s e s r e v e R G N I N E P O n o i t a r e p o s p o t S n o i t a r e p o s p o t S d e l b a s i d A N E P O t c e f f e o N 2 2 r o f e s o l c o t s e s r e v e R Tab 3 f B c i g o L S E S L U P S U T A T S E T A G g n i n e p o A N E P O g n i s o l c B N E P O P O T S S E C I V E D Y T E F A S G N I N E P O S E C I V E D Y T E F A S G N I S O L C E C I V E D Y T E F A S L C ...

Страница 19: ...mentreceivesanopening command by radiocontrol or from another suitable device it activatesthemotoruntiltheopeningpositionisreached If automatic operating mode was set the gate re closes automaticallyaftertheselectedpausetimehaselapsed Ifthesemi automaticmodewasset asecondpulsemustbesent toclosethedooragain Anopeningpulseduringre closing alwayscausesmovementto bereversed Astoppulse ifsupplied alway...

Отзывы: