DC power redundancy provisioning
The platform supports one to four DC power supplies. Each slot is provisioned to draw up to 600W; therefore,
one power supply can support two blade slots with no redundancy. This table shows some of the possible
blade and power supply redundancy configurations.
Table 3: DC power provisioning recommendations
1 + 1 redundancy
No redundancy
Blade quantity
2 (2600W available)
1 (2600W available)
1 (600W)
2 (2600W available)
1 (2600W available)
2 (1200W)
2 (2600W available)
1 (2600W available)
3 (1800W)
4 (5200W available)
2 (5200W available)
4 (2400W)
4 (5200W available)
2 (5200W available)
5 (3000W)
4 (5200W available)
2 (5200W available)
6 (3600W)
4 (5200W available)
2 (5200W available)
7 (4200W)
4 (5200W available)
2 (5200W available)
8 (4800W)
DC platform power consumption
The actual amount of power draw from the DC power source depends on the type and number of blades
and the redundancy configuration. This table shows several possible configurations, and the typical and
maximum power draw measured at the output of the power supply (at an input voltage of 48 VDC).
F5
®
recommends that you add 10% to the numbers in the table due to conversion loss in power supplies
when you are provisioning power and cooling.
Table 4: DC mains total system power draw
Minimum
number of
power
supplies
installed, no
redundancy
Maximum
system heat,
including power
supply losses
(BTU/hr)
Typical system
heat, including
power supply
losses (BTU/hr)
Maximum
system
power draw
(W)
4
Typical
system
power draw
(W)
3
Blade
quantity
and type
1
4825
4515
1315
1230
1 x B4300
1
6715
6095
1830
1660
2 x B4300
1
8605
7670
2345
2090
3 x B4300
2
10495
9250
2860
2520
4 x B4300
2
12385
10825
3375
2950
5 x B4300
2
16165
13980
3890
3380
6 x B4300
2
16165
13980
4405
3810
7 x B4300
4
At 100% load and a temperature of 40°C.
3
At 50% load and a temperature of 25°C.
81
Platform Guide: VIPRION
®
4800 Series
Содержание VIPRION 4800 Series
Страница 1: ...Platform Guide VIPRION 4800 Series MAN 0423 05 ...
Страница 2: ......
Страница 6: ...Legal Notices 103 Legal Notices 103 6 Table of Contents ...
Страница 76: ...Figure 21 Airflow in the VIPRION 4800 platform 76 Environmental Guidelines ...
Страница 86: ......
Страница 88: ...88 China RoHS Requirements ...
Страница 89: ...89 Platform Guide VIPRION 4800 Series ...
Страница 90: ...90 China RoHS Requirements ...
Страница 94: ...94 Repackaging Guidelines ...
Страница 97: ...10 Close and seal the outer shipping box 97 Platform Guide VIPRION 4800 Series ...
Страница 98: ......
Страница 102: ......
Страница 109: ...W warnings warnings continued environmental 71 109 Index ...
Страница 110: ...110 Index ...