Jumper “LED ind”/“No start” (LED)
Position “On”:
The LED flashes when movement is
detected.
Position “Off”:
The LED does not show when movement is
detected.
Without jumper: “No start” is a feature that prevents the
detector from switching on the lighting
automatically.
The LED can be disconnected once adjustment is complete, to
reduce the risk of tampering.
“Occupancy Activity” jumper / 5- or 30-minute
low-level delay
•
“High”:
For use in premises where people are only present
briefly, e.g. corridors and underpasses, i.e. clearly defined
passageways. Gives five minutes of base-level lighting.
•
“Low/Office”:
For use in premises where people sit for
long periods of time, e.g. in offices, some warehouse
premises and libraries. The sensitivity increases when the
detector has previously detected no presence. Gives five
minutes of base-level lighting.
•
Without jumper:
Gives 30 minutes of base-level lighting.
Signals are handled in the same way as for “Low/Office”.
“Mode” jumper
Extronic:
Control using scenes
•
Uses scene 10 while presence is detected.
•
Uses scene 14 during low-level delay.
•
Uses scene 15 when no-one is present.
Direct level:
Turns on, dims and turns off lighting by direct
control.
•
When presence is detected the lighting level is immediate-
ly switched to 100%.
•
When presence is no longer detected the light level is im-
mediately switched to 10% during the low-level delay.
•
After the low-level delay (5 or 30 minutes) the lighting is
switched off completely.
Without jumper:
Provides special features in combination
with the “Selection number” mode selector.
”
Selection number”:
0:
Broadcast 1.5% base-level during low-level delay.
1-5: Groups 1 to 5 get 1.5% lighting level during low-level
delay.
F:
Used with level selectors NP-2T DL and NP- 3T DL.
6 - E: Not used.
Mode selector (Selection number) 0–9 A–F
Choice of control by broadcast or groups 1 to 15.
Selection number determines which group is used.
•
Selection number 0 is used for Broadcast.
•
Selection numbers 1 to 9 send DALI commands to the re-
spective group.
•
Selection numbers A–F give groups 10, 11, 12, 13, 14 and
15 respectively.
•
Group 16 cannot be accessed.
NOTE!
If NP-2T DL or NP-3T DL level switches are used,
the mode selector should be set to F and the “Mode” jumper
should be removed.
EXTR ONIC
HE
R
S
P
A
IN
PIH
ER
SP
A
IN
0 1 2
3
4
5
67
89
A
B
C
D
E F
Selection
number
Mode
Group
Extronic
DA-1
(Group 0=Broadcast)
(no jumper see manual)
Min
Max
Sens.
Time
2s
2,5m
5m
10m
20m
LED Ind.
On
Off
Occupancy
Activity
R30CD
High
Low/Office
PD-33DL
v 1.0
DA-2
DALI
Further, to light
fittings or other
DALI equipment
Occupancy
Activity
jumper
Mode
jumper
Selection
number
Function selector
LED Ind.
LED indication
Detector settings
Opening the enclosure
The enclosure is opened by
twisting with a screwdriver
at the centre top or centre
bottom.
Potentiometers
Time (red):
delay between time when presence was last detect-
ed until time when lighting is dimmed. Adjustable from 2 sec-
onds to 20 minutes.
Sensitivity (yellow):
this potentiometer is used to adjust sensi-
tivity.
DALI terminals
PD-33 DL is only connected to the DALI bus and is intended for
detecting presence in lighting control systems. It has dual termi-
nal blocks (DA-1 and DA-2) that can be used to connect the in-
coming and outgoing buses.
The DALI terminals are polarity independent. DA-1 and DA-2
are wired in pairs.
The detector is powered by the DALI bus.
Extronic Elektronik AB +46 8 609 29 00
2