3

Recommended Setup

A

B

1
2

3
4

1
2

3
4

Blue Timer Test Button

DIP Switches (B)

DIP Switches (A)

Ultrasonic (US) Green LED

(status indicator)

Infrared (PIR) Red LED

(status indicator)

Blue Photocell

Sensitivity Dial

Green Ultrasonic

Sensitivity Dial

Red Infrared

Sensitivity Dial

Notch

Figure 3. 

OCS 100W Front Panel Features and Controls

With the OCS in the default or recommended settings (A2 OFF), the OCS requires 

both

 the IR sensor 

AND

 the US sensor to 

detect occupancy to turn ON. Only one sensor (PIR or US) needs to trigger to reset the timer for the OCS to remain ON while the 
room is still occupied. When the OCS is in the OFF state, no occupancy is detected.
Follow these steps to setup the OCS to detect occupancy with minimal false detection:

NOTE:

  We recommend using the OCS 100W in the default settings when beginning the setup or the test mode. If needed, 

adjust slightly from the default sensitivity settings.

1. 

Keep all the DIP switches and rotary dials in the default positions.

2. 

Set the OCS in Test Mode.

3. 

Enter the room several times to verify if the 

IR detector

 is detecting movement (red LED flashes). 

• 

If the red LED flashes when entering the room, the default red infrared sensitivity dial is set correctly. 

• 

Verify the red LED flashes with movement throughout the room.

• 

If the red LED 

does not

 flash, turn the red infrared sensitivity dial to decrease or increase IR sensitivity, until the red LED 

always flashes when entering the room or making movements throughout the room.

• 

To avoid false detections when the room is unoccupied, do not adjust the sensor too sensitively.

4. 

Enter the room and verify if the 

US detector

 is detecting movement (green LED flashes). 

• 

If the green LED flashes when entering the room, the default green ultrasonic range dial is set correctly. This sensor is 
very sensitive. 

• 

Verify the green LED flashes with movement throughout the room.

• 

If the green LED 

does not

 flash, turn the green ultrasonic range dial to decrease or increase US sensitivity, until the green 

LED always flashes when entering the room or making movements throughout the room.

• 

To avoid false detections when the room is unoccupied, do not adjust the sensor too sensitively.

5. 

Leave the room and close the door. Wait until the Digital output state, relay or red and green LEDs stay OFF. Wait several 
minutes to ensure there are no false detections.

• 

If the door remains open, the US sensor may detect changes.

• 

If possible, wait longer, to confirm no IR or US change is registered.

6. 

Enter the room again, to confirm the Digital output state, relay, red, or green LEDs turn ON.

NOTE:

  After going through these steps and verifying the OCS is setup to accommodate the room, do not adjust the DIP 

switches or dials.

Automatic Mode

Out of the box, the OCS 100W can be setup in Automatic Mode, where no manual sensitivity adjustments are needed and 
sensitivity learning and adjustments are made automatically. For simple setup, we recommend keeping the OCS in the default 
settings and flipping the B4 Dip switch to the OFF (Auto) position. The OCS is ready to mount (see 

Installation

 on page 5

)

.

3  

Содержание OCS 100W

Страница 1: ...nic US Green LED status indicator Flashes when the ultrasonic sensors detect occupancy Infrared Photocell Sensor and Fresnel Lens The fresnel lens diffracts the incoming light and directs the light to the infrared sensor behind it The Infrared PIR sensor detects the presence of people based on the difference between the heat generated by moving people versus the ambient room temperature Infrared P...

Страница 2: ...too long for the OCS to turn off when the room is unoccupied adjust the timer to 8 or 4 minutes and extend the timer via the configuration of the connected control processor This setup reduces false detection Blue Timer Test Button To enable an 8 second timer test mode push the blue button once The test mode will last for 1 hour and then automatically resets to the dip switch settings To cancel th...

Страница 3: ... the room or making movements throughout the room To avoid false detections when the room is unoccupied do not adjust the sensor too sensitively 4 Enter the room and verify if the US detector is detecting movement green LED flashes If the green LED flashes when entering the room the default green ultrasonic range dial is set correctly This sensor is very sensitive Verify the green LED flashes with...

Страница 4: ...f reflected ultrasonic waves caused by movement within the space NOTE See Troubleshooting on page 7 if you experience false triggers Installation Options Rotation 60 80 Ceiling Mount Wall Mount Top View Corner Mount Sensor Placement Wrong Correct Hallway Figure 4 Sensor Placement and Installation Diagrams NOTE Mount the OCS 6 to 8 feet 1 8 to 2 4 m away from HVAC vents and high air flow areas Sens...

Страница 5: ...n de sécurité TBTS de classe III Pull Cover Body Bracket Cover Wiring Harness Mounting Bracket Mounting Bolt Washer and nut 2 Insert wiring through Mounting Bracket Wall Building Wiring 1 POP Snap sensor onto mounting post 5 SNAP Push Replace Cover 7 Wall Wiring Harness Secure Mounting Bracket to the wall Connect building wiring to Wiring Harness with included wire nuts 2 3 Position Locking Screw ...

Страница 6: ...P PRO 250 Control Processor Extron PC 1224 Power Module Extron OCS 100W Occupancy Sensor Occupancy Control Signal Blue Ground Black Ground Black 24 V Red 12 V Red Power Module 1 25 A MAX 75 mA MAX 1 5 A MAX PC 1224 33 2665 01 B www extron com 24V OUT 12V OUT 12V IN Ground all Devices External Power Supply 12 VDC 12 V Red Ground Black Extron ol Figure 8 OCS 100W Wiring Diagram Wire Connections Note...

Страница 7: ... related topics see the Extron Safety and Regulatory Compliance Guide on the Extron website Power Attention ATTENTION These products are intended for use with a UL Listed LPS type power source Ces produits doivent être utilisés avec une source d alimentation de type LPS certifiée UL Use of a non LPS or unlisted power supply will void all regulatory compliance certification L utilisation d une sour...

Страница 8: ...ity and related topics see the Extron Safety and Regulatory Compliance Guide on the Extron website 2017 2019 Extron Electronics All rights reserved www extron com All trademarks mentioned are the property of their respective owners Worldwide Headquarters Extron USA West 1025 E Ball Road Anaheim CA 92805 800 633 9876 ...

Отзывы: