Contact Closure Input and Relay Connections

Contact closure input connections

The IPL T CR48 can be connected to any relay providing a closure to ground 
(closed = logic 1 and open = logic 0). The contact closure inputs are connected to 5 VDC 
via a 1k ohm pull-up resistor and must be wired with a ground. This allows the input to be 
tied to devices such as motion detectors and alarms. You can define what this input triggers 
via control software.

1. 

Connect one end of the input cable to a 3.5 millimeter, 5-pole captive screw connector, 
wired appropriately, and plug it into the rear panel input port connector of the unit.

2. 

Connect the other end of the input cable to the input relay device that will provide a 
triggering signal.

Relay connections

The IPL T CR48 can be connected to any device that can be activated by a relay closure. 
This allows the relay to be tied to devices such as lights (preset recall), projector lifts, and 
screen or drape controllers. You can define what triggers this action via control software.

1. 

Connect one end of the relay cable to an 8-pole captive screw connector, wired 
appropriately, and plug it into the rear panel relay port connector of the unit.

2. 

Connect the other end of the relay cable to the device that will be activated when the 
triggering signal is received.

Configuring the Hardware

To function together properly, both the controlling PC and the IPL T CR48 must be 
configured correctly. The PC must be network-capable, with the proper protocols installed 
and the hardware configured correctly. The IPL T CR48 must be set to recognize and 
accept commands and pass them through to the projector lift, screen lift, or other controlled 
device.

PC Configuration

This guide assumes that you have a Microsoft

®

 Windows

®

 PC equipped with an operating 

network adapter. To allow your PC to work with Extron Ethernet-controlled products, the 
TCP/IP protocol must be installed and properly configured.
For use on an existing Ethernet LAN intranet, your network administrator can provide you 
with a unique IP address or confirm whether you need to set up the IPL T CR48 for DHCP 
(Dynamic Host Configuration Protocol) to have an address assigned automatically when you 
sign on.

Initial start up

When you power on the IPL T CR48 for the first time, there are two ways to set up the 
IP address:

• 

Use the ARP (Address Resolution Protocol) command method.

• 

Use the direct PC method.

The default web pages that are preloaded on the IPL T CR48 provide a way to reconfigure 
the unit once it has an active network connection with IP access. These web pages are 
compatible with Internet Explorer

®

 (version 6.0 or higher). See 

Communication with the 

Interface

 on page 17 for information on accessing and configuring the controller.

Once the unit has been reconfigured, an Ethernet (intranet or Internet) connection can 
subsequently be used to contact or control it (see 

Ethernet Connection

 on page 11 for 

additional information).

IPL T CR48 • Connection and Configuration

12

Содержание IP Link IPL T CR48

Страница 1: ...User Guide IPL T CR48 IP Link IP Link Ethernet Control Interface 68 738 05 Rev D 08 19...

Страница 2: ...a en el producto avisa al usuario de la presencia de importantes instrucciones de uso y mantenimiento recogidas en la documentaci n proporcionada con el equipo Para obtener informaci n sobre directric...

Страница 3: ...PoleVault PowerCage PURE3 Quantum Show Me SoundField SpeedMount SpeedSwitch StudioStation System INTEGRATOR TeamWork TouchLink V Lock VideoLounge VN Matrix VoiceLift WallVault WindoWall XTP XTP System...

Страница 4: ...ence must be corrected at the expense of the user NOTE For more information on safety guidelines regulatory compliances EMI EMF compatibility accessibility and related topics see the Extron Safety and...

Страница 5: ...examples of computer or device responses used in this guide the character 0 is the number zero and O is the capital letter o Computer responses and directory paths that do not have variables are writ...

Страница 6: ......

Страница 7: ...d Configuration 11 Connecting the Hardware 11 Ethernet Connection 11 Contact Closure Input and Relay Connections 12 Configuring the Hardware 12 PC Configuration 12 IPL T CR48 Interface Configuration 1...

Страница 8: ...IPL T CR48 Contents viii...

Страница 9: ...hosts its own web pages stored in blink memory within the device The IPL T CR48 supports Telnet SMTP Simple Mail Transfer Protocol ICMP Internet Control Message Protocol or Ping and DHCP Dynamic Host...

Страница 10: ...enabled AV devices NOTE Ethernet driver support requires Global Configurator 3 0 and firmware version 1 15 or higher Easily connected Provides RJ 45 auto sense 10 100 Mbps Ethernet LAN connection Easi...

Страница 11: ...PL T CR48 through Telnet then access the unit using an Internet browser Mounting the IPL T CR48 Optional rack shelves and an assortment of mounting kits furniture and projector mount are available for...

Страница 12: ...rthing grounding Reliable earthing of rack mounted equipment should be maintained Particular attention should be given to supply connections other than direct connections to the branch circuit such as...

Страница 13: ...figure 4 Figure 3 Furniture Mounting the IPL T CR48 Projector PMK 100 Mounting Bolt Figure 4 Projector Mounting the IPL T CR48 Rear Panel Features and Cabling All connections including power input an...

Страница 14: ...ical Code ANSI NFPA 70 article 75 and the Canadian Electrical Code part 1 section 16 The power supply shall not be permanently fixed to building structure or similar structure L installation doit touj...

Страница 15: ...AN activity Link LED A green LED lights to indicate a good LAN connection A cable that is wired as T568A at one end and T568B at the other Tx and Rx pairs reversed is a crossover cable A cable wired t...

Страница 16: ...ons to and from the unit A Reset button 2 is also available from the front panel in a small recess next to the Power LED IPL T CR48 R 4 2 3 1 INPUT 100 LINK ACT 4 2 3 1 RELAY 8 6 7 5 1 2 3 4 5 6 7 Fig...

Страница 17: ...ecycled If you want to use the factory default firmware you must upload that version again The IPL T CR48 reverts to the factory default firmware Event scripting does not start if the unit is powered...

Страница 18: ...9 seconds until the Power LED blinks three times once at 3 seconds again at 6 seconds again at 9 seconds Then release and press Reset momentarily for 1 second within 1 second Mode 5 performs a complet...

Страница 19: ...9 Example Application Ethernet Connection This type of connection is used on an ongoing basis to connect the IPL T CR48 to a LAN and to control switching and display devices through the unit 1 Plug o...

Страница 20: ...e IPL T CR48 must be configured correctly The PC must be network capable with the proper protocols installed and the hardware configured correctly The IPL T CR48 must be set to recognize and accept co...

Страница 21: ...d and is still set for factory defaults go to step 4 If not perform a Mode 4 system reset see Resetting the Controller on page 9 for detailed information on reset modes NOTE The IPL T CR48 unit must b...

Страница 22: ...event of a complete system reset the passwords convert to the default which is no password see Setting and changing passwords on page 19 to change a password 1 Plug one end of a CAT 5 crossover Ether...

Страница 23: ...r web browser Internet Explorer and type http 192 168 254 254 index html in the Address field of the browser The IPL T CR48 default web page is displayed See IPL T CR48 Interface Configuration on page...

Страница 24: ...ither side of the external switch or relay from the IPL T CR48 Relay Ports The relay ports can be used for remote switching of low level signals The relays can be activated via software in three ways...

Страница 25: ...ry configured passwords for all accounts on this device have been set to the device serial number In the event of a complete system reset the passwords convert to the default which is no password see...

Страница 26: ...es or switchers To configure system or port settings 1 Select the Configuration tab and the System Settings page see figure 14 is displayed Figure 14 System Settings Page 2 Make changes to the IP sett...

Страница 27: ...passwords convert to the default which is no password To set or change the passwords 1 Click the Passwords link on the menu on the left side of the window The Passwords page is displayed see figure 1...

Страница 28: ...ach e mail address and file name 1 Enter the e mail address of the alert recipient in one of the numeric mailboxes under Email Address 2 Enter the name of the file containing the alert message under F...

Страница 29: ...A file with any other extension is not a firmware upgrade for this device and could cause the device to stop functioning Les fichiers firmware valides doivent contenir l extension fichier S19 Un fichi...

Страница 30: ...oad 3 Click Upload File to upload the file The file is added to the list of files under the Files column After ten files have been loaded additional file management pages appear in the page navigation...

Страница 31: ...ugh a web browser the URL reference is used below to shorten the examples This would in practice be the full URL of the control interface and web page reference including all path information for exam...

Страница 32: ...age return and line feed Carriage return no line feed Space hard character Copyright information c COPYRIGHT 2009 EXTRON ELECTRONICS IPL T CR48 Vx xx 60 544 x5 Tue 10 Aug 2010 16 29 10 The copyright m...

Страница 33: ...s of characters do not require encoding in a URL Alphanumerics 0 9 a z or A Z Special characters _ _ Reserved characters When used for their reserved purposes these characters do not require encoding...

Страница 34: ...d unsafe The following table lists unsafe characters Characters Hex Dec Space 20 32 Quotation marks 22 34 Less than symbol 3C 60 Greater than symboi 3E 62 Pound 23 35 Percent 25 37 Miscellaneous Chara...

Страница 35: ...ver desc UL date and time Query updated firmware version 4Q 4Q X1 plus web ver desc UL date and time NOTE An asterisk placed after the version number indicates which version is currently running A que...

Страница 36: ...d local date and time format Day of week date month year HH MM SS X3 Daylight saving time 0 off or ignore 1 on use in northern hemisphere USA 2 on Europe 3 on Brazil X4 Default Name combination of mod...

Страница 37: ...ress X2 Verbose or tagged response mode status 0 clear default for Telnet connections 1 verbose mode is enabled 2 send tagged responses for queries 3 verbose mode is enabled and tagged responses are s...

Страница 38: ...024 or higher Reset web port map24 E80MH W80MH Pmh00080 Disable web port map24 E0MH W0MH Pmh00000 Read web port map24 EMH WMH port Web Browser Specific Read response from last URL cmd EUB WUB response...

Страница 39: ...n set to the device serial number In the event of a complete system reset the passwords convert to the default which is no password see Setting and changing passwords on page 19 to change a password E...

Страница 40: ...e IPL T CR48 on a network Once connected via Telnet you can send ASCII serial commands see Programmer Guide for the Telnet and Web Browser on page 23 to control devices connected to the IPL T CR48 Acc...

Страница 41: ...omputer should be solid green if a network connection is detected If these LEDs are not lit either the cable is faulty or not plugged in or the wrong type of cable is being used see Connecting the Har...

Страница 42: ...protocol that enables network administrators to locally and automatically manage the assignment of IP addresses in a network for an organization Driver A GC compatible package It includes the event sc...

Страница 43: ...o the Internet a table see ARP on page 34 relates the IP address of the device to its corresponding physical MAC address on the LAN Pass through Allows control systems to work with the IPL T CR48 and...

Страница 44: ...n South Africa South Tower 160 Jan Smuts Avenue Rosebank 2196 South Africa This Limited Warranty does not apply if the fault has been caused by misuse improper handling care electrical or mechanical a...

Отзывы: