Extech Instruments 382252 Скачать руководство пользователя страница 6

382252-en-GB_V1.5   1/17 

6

4

5

1 2

3

200k

 Resistance Measurement 

1. 

Connect the red test lead to the V



(C) connector and the black test lead to the COM (E) 

connector. 

2. 

Set the function selector switch to the 200k



position. 

3. 

Connect the test probes to the circuit under test. 

4. 

Note the displayed Resistance value. 

 

 

AC Voltage Measurement 

5. 

Connect the red test lead to the V



(C) connector and the black test lead to the COM (E) 

connector. 

1. 

Set the function selector switch to the 750V AC position. 

2. 

Connect the test probes to the circuit under test. 

3. 

Note the displayed Voltage value. 
 

DC Voltage Measurement 

1. 

Connect the red test lead to the V



(C) connector and the black test lead to the COM (E) 

connector. 

2. 

Set the function selector switch to the 1000V DC position. 

3. 

Connect the test probes to the circuit under test. 

4. 

Note the displayed Voltage value. 

 

Three terminal Ground Resistance Measurement 

1. 

Using the Red and Green (1.5m) test leads with the alligator clips,  
Connect one of the banana jacks of the red test lead to the V



(C) connector (Red) and the 

other to the P (Yellow) connector on the meter. 

2. 

Connect the Green test lead (1.5m) with the alligator clip to the COM (E) (Green) connector on 
the meter. 

3. 

Set the function selector switch to the one of the Earth resistance positions. (20, 200, 2000

4. 

Perform the Zero adjustment as described above. 

5. 

Connect the Red and Green test clips to the ground rod or other item to be measured. 

4.    Press TEST button.  The “   “ icon will flash and the audible signal will sound. 
5. 

Note the resistance reading on the display. 

6. 

Press the TEST button to stop the test.  

 

Содержание 382252

Страница 1: ...User Manual Earth Ground Resistance Tester Kit Model 382252 Additional User Manual Translations available at www extech com ...

Страница 2: ...anual Environmental safety information Do not use meter outdoors when precipitation is likely Installation Category III Pollution degree 2 Altitude 2000 meters max Ambient conditions 32 to 104o F 0 to 40o C RH 80 max Observe the following international safety warning symbols Safety Symbols Caution Refer to this manual before using this meter Dangerous Voltages Meter is protected throughout by doub...

Страница 3: ...EST key Enables Earth Resistance and Earth Voltage Tests 6 Function Selector switch Selects desired range and function Top View 1 V C Input Red 2 P Input Yellow 3 COM E Input Green Display Description 1 Test status Icon 2 Battery Charge indicator 3 Voltage Unit indicator 4 Audible Signal Icon 5 k Units Indicators 6 Measurement Value 7 AC DC Voltage Indicators 8 Low Battery Icon 9 HOLD Icon 1 2 3 4...

Страница 4: ...rm this adjustment for each range Test Connection Diagram 1 382252 Meter 2 Green Test Lead E 3 Yellow Test Lead P 4 Red Test Lead C 5 Existing Ground rod 6 P1 Auxiliary Earth Bar 7 C1 Auxiliary Earth Bar Earth Voltage Test 1 Set the Function selector switch to the EARTH VOLTAGE position AC or DC 2 Connect the 2 Voltage test leads to the meter Connect the black and red leads connect the black lead ...

Страница 5: ...ow lead 3 to Earth Bar P1 6 Red lead 4 to the Earth Bar C1 7 4 Set the meter s function switch to the desired resistance range 20 200 2000Ω 5 Zero the range as described in the Zero adjustment procedure above 6 Press the TEST button The icon will flash and the audible signal will sound 7 Note the displayed reading 8 If high resistance is detected note the value and take appropriate steps to correc...

Страница 6: ...ector 2 Set the function selector switch to the 1000V DC position 3 Connect the test probes to the circuit under test 4 Note the displayed Voltage value Three terminal Ground Resistance Measurement 1 Using the Red and Green 1 5m test leads with the alligator clips Connect one of the banana jacks of the red test lead to the V C connector Red and the other to the P Yellow connector on the meter 2 Co...

Страница 7: ...pect of the disposal of the device at the end of its lifecycle Cleaning and Storage Periodically wipe the meter s case with a damp cloth and mild detergent do not use abrasives or solvents If the meter is not to be used for a period longer than 60 days remove the batteries and store them separately Specifications General Specifications Measurements Earth Ground Resistance in 3 ranges Earth Voltage...

Страница 8: ...0 Vrms Input Impedance 10M DC Voltage 0 to 1000V 1V 0 8 reading 3 digits Overload Protection 1000 Vrms Input Impedance 10M Kit contents 382252 Earth Ground Resistance Meter 2 Ground rods zinc plated iron 22cm 6 AA alkaline batteries 3 Ground rod test cables Red 15m Yellow 10m Green 5m 2 Test leads for Ground Resistance with alligator clips Red and Green 1 5m 2 Test leads for Voltage Resistance Bla...

Отзывы: