05(0x05) Set WDT timeout /Clear WDT timeout status
Request
00 Address
1
Byte
1-247
01 Function
code
1
Byte
0x05
02~03 WDT timeout
2 Bytes 0x0104 Set WDT timeout
enable/disable
0x010D Clear WDT timeout status
04~05 WDT timeout
2 Bytes 0xFF00 for WDT timeout enable
0x0000 for WDT timeout disable
0xFF00 for Clear WDT timeout
status
Response
00 Address
1
Byte
1-247
01 Function
code
1
Byte
0x05
02~03 WDT timeout
2 Bytes The value is the same as byte 02 and
03 of the Request
04~05 WDT timeout
2 Bytes The value is the same as byte 04 and
05 of the Request
Error Response
00 Address
1
Byte
1-247
01
Function code
1 Byte 0x85
02
Exception code
1 Byte Refer to the Modbus standard for
more details.