23
2.12 ~AAO(Data)
Description:
Set Module Name
Syntax:
~AAO(Data)[CHK](cr)
~ delimiter character
AA address of setting/response module(00 to FF)
O command for set module name
(Data) new name for module, max 6 characters
Response:
Valid command:
!AA
Invalid command:
?AA
Example:
Command:~01O9017 Receive :!01
Set address 01 module name 9017, return success.
Содержание EX-9017F