Settings
The EFC18 is set initially so that the temperature sensor starts and stops the chimney fan at either 20 °C,
40 °C or 80 °C. The factory setting is 40 °C.
Setting the temperature
Step
Action
1
The control must be standby (shows ”–” in display).
2
Press and hold the button in for 5 seconds and the figure displayed will change to 0,1, 2 or 3.
3
When the required number is displayed, hold down the button until a horizontal line appears (“—”).
Setting options:
0 = Fitted without sensor
1 = Automatic start / stop of chimney fan, 20 °C (open fire / closed stove / boiler)
2 = Automatic start / stop of chimney fan, 40 °C (open fire / closed stove / boiler)
3 = Automatic start / stop of chimney fan, 80 °C
(alternative setting for closed stove / boiler: delayed start / rapid stop)
Daily use
Start
The fire place is made ready for lighting and the button on the EFC18 is activated by pressing once.
The fire is lit and the chimney fan runs at full speed for 7 mins., and then slows down to the previous
level. The speed of the chimney fan can be changed at any time from 1 – 9 by holding down
the button.
Refuelling
When the sensor is active (red dot in display), the refuelling option can be activated by pressing the
button briefly. The chimney fan increases speed to maximum for 3 mins.
Automatic stop
When the temperature falls below 20 °C, 40 °C or 80 °C depending on the setting, the 45 minutes post
purge period will start. The red dot in the display will start to flash.
Automatic operation
When the red dot in the display is illuminated, the temperature around the sensor is above the set
temperature, meaning that the chimney fan can only be stopped by switching off the electric supply.
Sensor error
If there is an error with the sensor, an “E” flashes on the display. Check the installation.