INSTALLATION INSTRUCTIONS

800.533.3948 • www.barronltg.com 

10070210 Rev 2 - 04/19

3

 RMW Series

Manual Testing

Multiple durations can be selected as follows:

 

Instant Test:             Press and hold Test Switch for more than 3 seconds
5 Minutes Test:        Press Test Switch 2 times within 3 seconds. 
90 Minutes Test:      Press Test Switch 3 times within 3 seconds.
Momentary Test:     Useful during installation, connect battery only (without AC connected), press and 

                                hold Test Switch. 

To CANCEL            

any Manual Test:    Press and hold Test Switch for 5 seconds.

Battery or Charger Diagnostics

Charger:

During normal operation, the onboard microcontroller constantly monitors the charger performance. Should the charger 

output vary from design parameter values, the DIAGNOSTIC LED will indicate a flashing red condition.

Transfer:

A failure of the unit to transfer to battery power during a power outage will cause the DIAGNOSTIC LED to flash red.

Battery:

Disconnection of the batteries from the charger will cause the DIAGNOSTIC LED to flash red. If the battery voltage 

drops too low or the unit fails to provide battery power for the required duration during a manual/automated test, the 

DIAGNOSTIC LED will display steady red. 

To prevent battery damage:

 Do not connect the battery until constant AC power can be supplied to the unit.

Self-test/Self-diagnostics (G2)

Automated Testing:

 

The Auto-Test scheduling counter will start when both AC and battery are first applied. When automatic testing is in 

progress the DIAGNOSTIC LED will flash yellow. A steady green DIAGNOSTIC LED indicates normal operation.

Automated Diagnostic Routine

The Auto-Test automatically initiates a five-minute discharge/diagnostic test every month with two 90-minute discharge/

diagnostic tests every 6 months. 

Twenty-four hours following the first 6-month test, the unit will retest again to ensure that the charger has completely 

recharged the battery. The lamps will be activated during these tests. The tests exercise the battery to optimize its 

capacity and analyze the unit’s emergency operation. Any malfunction of the transfer circuit, batteries or emergency 

lamps will cause the multi-color DIAGNOSTIC LED on the unit to indicate the fault. The 

DIAGNOSTIC indications will remain latched (stay on) in the system until corrected or reset.

Diagnostics Display

The Auto-test/Self-diagnostics provides a visual indication of unit status via a multi-colored 

LED. The LED may indicate just one or any combination of the various conditions as follows:

Steady Green:  Normal Operation

Flashing Green: AC Interruption in Last 48 Hours

Steady Yellow: Lamp Circuit Malfunction

Flashing Yellow: Auto-Test or Manual Test in Progress

Steady Red: Battery Failed Testing

Flashing Red: Battery Disconnected or Charger Malfunction

DIAGNOSTIC

CHARGE

TEST

Battery Unit LEDs

and Test Switch 

Configuration 