6
© 2017 OJ Electronics A/S
• The heating valve should be connected to terminals 24, 25 & 26 (see fig. 16)
• The cooling valve should be connected to terminals 27, 28 & 29 (see fig. 16A)
Connection of temperature sensor in inlet duct
(see figs 3 & 15)
It is possible to connect a sensor located in the inlet duct. The actual value recorded by
the sensor is shown on the zone's webpage. The temperature is used to control inlet
temperature.
NOTE!
The sensor must be of PT1000 type.
• The sensor should be connected to terminals 30 & 31 (see fig. 15).
Display “G”
(see figs 3 and 17)
OJ GreenZone™ Module A is equipped with a 2-digit display (fig. 3, pos. “G”).
The display indicates various things as shown in table 3 below.
The display alternates (flashes) between the activated functions and readouts.
Example:
If the OJ GreenZone™ Module A is configured as follows:
• Connected to OJ GreenZone™ Master 1
• Allocated zone 13 by OJ GreenZone™ Master
• A PT1000 temperature sensor is installed in the inlet duct
• A combined temperature/humidity sensor (HTH-6202) is installed in the exhaust duct
- the display will alternate between the following readouts:
Table 3
Display
readout
Comments
Actual OJ GreenZone™ Module A is integrated in zone section 1 (ZoneMaster1)
Actual OJ GreenZone™ Module A is integrated in zone section 2 (ZoneMaster2)
Actual OJ GreenZone™ Module A is integrated in zone section 3 (ZoneMaster3)
English / Instruction
OJ GreenZone™ Module A