NFO

 

Drives

 

AB

 

2021

 

2

 

201016

2

 

Quick

 

Installation

 

Guide

 

2 Electrical 

installation 

Connect 

mains power

 to terminals 

L1, L2, L3

 and 

PE

.

Connect 

motor cable

 to terminals 

U, V, W

 and 

PE

 using standard unshielded cable.

Never install contactors or switches between the inverter (terminals U, V and W) and the motor that
intentionally or unintentionally may be used to disconnect the motor from inverter output.

A motor safety switch can be mounted between the inverter (terminals U, V and W) and the motor, but it
must only be operated when the motor is not running.

First time powered up, the installer must select application, enter motor name plate data, and perform a
motor tuning (see next section).

Connect/install the necessary low voltage signalling that is required for your application, e.g. a run signal
for start/stop, analog input for setpoint, communication, etc.

Make sure run signal is not activated until installer has completed the setup of the inverter.

Make sure the low voltage signal wires have sufficient isolation when passing nearby power cables.