Menu 8.3.2 Recovery
8.3.2 Recovery
Rotor motor
Rotation guard
Error on unit
0%
0
No
If there are no current faults for the rotor motor ("Fault on unit" shown as "No"),
forced start may be activated.
Rotation control
check
If the rotor is not running:
● Turn the rotor one revolution by hand. The value shown for rotation control
should change each time rotation control is activated
Menu 8.3.3 Heating unit
8.3.3 Heating unit
HCE
Supply air
Min. flow
Measured flow
Run on
Error on unit
0%
0%
No
No
0l/s
0l/s
For electric heating coil HCE:
If there are no current faults for the heating coil ("Fault on unit" shown as "No"),
forced start may be activated:
● Start the supply air fan and increase its speed until the measured flow is
greater than the min. flow
● Then start HCE
Note
To avoid the electric heating coil dropping out due to an overheating alarm when
the electric heating coil is stopped:
● Do not exit the menu or stop the supply air fan until
Run-on is shown as
"No"
.
8.3.3 Heating unit
HCW
Error on unit
0%
No
For water heating coil HCW
:
If there are no current faults for the heating coil ("Fault on unit" shown as "No"),
forced start may be activated:
● Enter an output level for HCW to start the motor valve and pump for the water
heating coil
Menu 8.3.4 Cooling unit
8.3.4 Køleenhed
CU 0%
Fejl på enhed Nej
(The menu screen is different depending on which cooling unit is selected - CH,
CU, CCW, MXCU)
If there are no current faults for the cooling unit ("Fault on unit" shown as "No"),
forced start may be activated:
● Set the output level for the cooling unit
NB: for CU
Only the cooling unit starts. Operating time is limited (until the unit drops out via
the overpressure sensor - automatic reset). There must be a 10-minute interval
between starts.
3005167-2022-02-02
Operation
59/108