background image

Rev. 3 

Select HART port A, B or C 
Port A 

 

82 62 E6 D7 18 49 

0F

 00

 -> 

 
<- FF FF FF FF FF 86 22 E6 D7 18 49 0F 13 00 41 01 00 2D3F 80 00 003F 00 00 0100 
0000 00FB 62 AD 

 

5.3

 

Transparent Mode (HART over TCP) 

 

This  function  allows  the  EGW1-MB-HT  to  be  used  as  a  HART  converter  over  TCP  to  HART.  This 
allows the configuration software of each transmitter to be used remotely, arriving at the location 
through  a  TCP  connection.  Probably  it  is  necessary  to  use  a  virtual  COM  port  software  (such  as 
Serial IP) to get from the software to EGW1-MB-HT. 
 

 

Each  device  HART  port  has  an  assigned  TCP  port  assigned  to  the  transparent  mode.  Port 
HART A: 

10001

, Port HART B: 

10002

, Port HART C: 

10003

 

 

 

The device will stop sending its own HART queries, while the connection to this port lasts 
 

 

The communication in transparent mode cannot be monitored on port 999 
 

 

No additional byte type is added to the frame 

 
Please refer to Appendix E to see how to do it using PACTware. 
 
 
 
 
 
 
 
 

 

 

Содержание EGW1-MB-HT

Страница 1: ...Rev 3 ...

Страница 2: ...____________________________ 10 3 2 Configuration web page________________________________________________________ 11 3 3 Modbus Configuration _________________________________________________________ 12 3 4 HART Configuration ___________________________________________________________ 13 3 5 Administrator Settings _________________________________________________________ 13 3 6 WEB Monitoring ___...

Страница 3: ...peration of the device is detailed below 1 2 Product Overview EGW1 MB HT module is a device used to connect any instrument with HART communication to one or more Modbus Masters Modbus TCP or Modbus Serial RTU ASCII Device has 3 independent Modbus ports One Ethernet for Modbus TCP one RS232 and the other RS485 opto isolated for Modbus RTU ASCII 1 3 Ordering Codes Ordering Code Description EGW1 110 ...

Страница 4: ...ated port Pluggable Terminal Block connection Supported devices Any HART Device Device Management HTTP Server password protected RS 232 Serial Console Firmware Update From Web Page Led Indicators Status Data Link Measurements 100mm x 22 5mm x 112mm Height x Width x Length Power Supply 10 to 30 VDC Consumption 12VDC 80mA 24VDC50mA Temperatures Operation Temperature 15 C to 65 C Storage Temperature ...

Страница 5: ...sed as Modbus Slave 2 2 1 RS232 port wiring Port A To connect the device RS232 serial port to PC serial port or any other serial device to set and monitor it must be connected as can be shown in the following figure You should consider EGW1 MB HT is a DTE device that means it must cross wire with those of the PC 2 2 2 RS485 port wiring Port B To connect the device RS485 opto isolated serial port t...

Страница 6: ...fferent HART address to each one Each loop must be closed with an external resistance of 250 ohms The resistance must dissipate a power equivalent to the square of the maximum current of each instrument multiplied by the value of the resistance 250 ℎ Example for 3 instruments generating up to 4 mA in Multidrop mode 3 4 250 ℎ 36 Connection diagram for3 transmitters in Multidrop mode to the HTa port...

Страница 7: ...Rev 3 2 2 1 One passive transmitter to HTa port wiring diagram 2 2 2 One active transmitter to HTa port wiring diagram 2 2 3 Three passive transmitters to HTa port in Multidrop mode wiring diagram ...

Страница 8: ...Rev 3 2 2 4 Three active transmitters to HTa port in Multidrop mode wiring diagram 2 2 5 Three passive transmitters to in NO Multidrop mode to ports HTa HTb and HTc wiring diagram ...

Страница 9: ... ping and or waiting serial console 90 of a second off and the remaining time on Device has an IP address and a connection bearer link This is the normal operating state 10 of a second off and the remaining time on It has no IP address and cannot find the DHCP server It will search the DHCP server for in 60 seconds Flashing very fast Lack of Ethernet link Cable disconnected On Modbus TCP connectio...

Страница 10: ... using the Exemys Device Locator software which allows us searching identifying and configuring the basic network parameters The rest of the configuration is done from the configuration web page of the device In case you do not have a DHCP server the Exemys Device Locator will find the device with IP address 0 0 0 0 as shown in the figure below If you do not have a DHCP server give it an IP addres...

Страница 11: ...oxy server disable this option Type the EGW1 MB HT IP address in the address field of your browser or from the Exemys Device Locator press the Configure button If you configured a password the computer will ask for it when entering the web page In this case you must enter admin as the user and then the password that was set If you want to change it you can do it from the Administrator menu ...

Страница 12: ...II Modbus TCP The only possible configuration is to define the connection port of the Modbus TCP slave The TCP slave responds to all IDs and responds to exceptions Serial Ports RS232 RS485 Advance Configuration It is possible to determine some specific parameters of the Modbus map so that it adapts to our needs Among the different configurations we have the order of the floating point values if th...

Страница 13: ... show NaN or a predefined value that is useful 3 4 HART Configuration Basic Configuration We can define the number of retries on the HART ports Table of device It is the table that tells us which devices we have connected and which short address they have Each port has its table It is important not to repeat addresses in the same port 3 5 Administrator Settings In the Administrator menu you can fi...

Страница 14: ...ginal factory settings This option can be executed from the web page or from the Exemys Console see Appendix A Firmware Update The device s firmware can be updated in case new versions with improvements arise By pressing the Update button the web page will request you select the update file Then press the Download button and through informative messages you can follow the update process The device...

Страница 15: ...Rev 3 ...

Страница 16: ...ess HART A HART B HART C 1 40001 40321 40641 2 40021 40341 40661 3 40041 40361 40681 4 40061 40381 40701 5 40081 40401 40721 6 40101 40421 40741 7 40121 40441 40761 8 40141 40461 40781 9 40161 40481 40801 10 40181 40501 40821 11 40201 40521 40841 12 40221 40541 40861 13 40241 40561 40881 14 40261 40581 40901 15 40281 40601 40921 16 40301 40621 40941 Holding Register Input Register Value Format 400...

Страница 17: ...s of each device Example To read the 2nd variable of the device number 8 connected to the HART Port C 40781 7 40788 Add Value Format 0 Status 0 1 3 Current mA Float 5 1st variable Float 7 2nd variable Float 9 3rd variable Float 11 4th variable Float ...

Страница 18: ... to make adjustments in the configuration of the HART transmitters once they are already installed in the field For this you must establish a TCP connection to port 998 with some TCP client terminal software for example Putty or HyperTerminal When connecting to port 998 the user must select the HART port to which it wishes to send the manual command by pressing the letters A B or C Select HART por...

Страница 19: ...ng at the location through a TCP connection Probably it is necessary to use a virtual COM port software such as Serial IP to get from the software to EGW1 MB HT Each device HART port has an assigned TCP port assigned to the transparent mode Port HART A 10001 Port HART B 10002 Port HART C 10003 The device will stop sending its own HART queries while the connection to this port lasts The communicati...

Страница 20: ...ww exemys com console Once the serial terminal program is installed connect the EGW1 MB HT to a RS232 port on the PC and execute the Exemys Console 1 Click on Connection Serial Port it will open a window with name of all COM Serial port Select with double click the port where device is connected Verify Baud rate in the serial por is 9600 2 Turn on the EGW1 MB HT and in the first 7 seconds type CFG...

Страница 21: ...sword must have a maximum of 10 characters or empty to delete it LIST Request the current device configuration HELP Displays the list of all available commands with syntax and descriptive text FACTRESET Reset to the factory settings This command must be entered 2 times for this to begin working END It saves the changes made and it ends the command console To finish and save all the changes type th...

Страница 22: ...s an alternative method 1 On Microsoft Windows open the Command Prompt with Administrator permissions 2 Enter an ARP table with the following command arp s 192 168 0 213 00 90 C2 XX XX XX Where 192 168 0 213 is the Device IP address to set and 00 90 C2 XX XX XX is the Device MAC address you can find the address on the label that is located on the back of the device With arp a you can check the new...

Страница 23: ...device IP address The t option will cause the command to be sent continuously ping 192 168 0 213 t 4 Wait for a few seconds until the PINGs start responding Once the IP address has been set enter the Configuration web page to set the other parameters ...

Страница 24: ...D Modbus 247 Modbus Protocol RTU Exceptions Enable Baud rate 9600 Data Bits 8 Parity No Stop Bits 1 Modbus COM B RS485 ID Modbus 247 Modbus Protocol RTU Exceptions Enable Baud rate 9600 Data Bits 8 Parity No Stop Bits 1 Modbus Advanced Modbus Floating point standard Valuewith HART in failure Last value Predefined Value 0 0000 HART Basic Configuration Retries 2 HART Ports A B y C All disable ...

Страница 25: ...To assembly the module to the rail make the upper side of the device fit the DIN rail and then push gently until you hear a Click As shown in the figure To disassemble the device of the rail DIN pull down the metallic clip and then remove it as shown in the figure ...

Страница 26: ...ction 5 3 on this manual For this example we ll use the PACTware software the CodeWrights HART Communication FDT 1 2 DTM V1 0 52 and the serial port redirector software SerialIP Steps 1 Install the SerialIP redirector add a COM port and configure the EGW1 MB HT IP address the TCP port 10001 10002 o 10003 for ports A B or C in Raw TCP Connection mode 2 Install the CodeWrights HART Communication FDT...

Страница 27: ...TM 4 Add a new port using the new DTM and open the Paramenter tab 5 Select the COM port previously added in SerialIP In the Address scan section change the Start and End address in case you have multiple devices with different addresses connected to the EGW1 MB HT port ...

Страница 28: ...Rev 3 6 Add the the HART devices to the new COM port on PACTware Then you will be able to monitor and configure the devices remotely ...

Отзывы: