ES2030 CV 

Display and modification of the basic settings 

26 

 

18. ‘Flow pulse’ output

 

 
 
 
 
 
 
If the flow pulse function is selected, the relevant additional relay is activated after 
a set amount of water. Values from 1 to 9999 litres can be entered. The next 
program step determines how long the relay remains active for each pulse. 
 
This function can be used to control a dosage pump, a dosage controller or as a 
flow monitor contact. 
 
Water meter pulses following each other in rapid sequence are recorded and if 
necessary passed on at an interval of 0,5 seconds after each other. 
 
 
 
 
 
 
Values between 0,5 and 999,9 seconds can be entered for the pulse duration. 
 
 

19. ‘Warning’ output

 

 
 
 
 
 
 
During the service and regeneration of the system of the system various signals 
occur which can be switched to additional relay 1 or 2. 
(‘ | ’ = selected, ‘ - ‘ = not selected).  
If more than one signal is selected, the relevant relay functions as a combined 
warning relay. 
 

M   =  

Minimum regeneration distance 

 

Note: Only where ‘minimum regeneration distance’ has been set. 

Wa = 

Waiting for regeneration to resume 

 

Note: Only where ‘delayed regeneration’ has been set. 

P   =  

Power loss 

Ce =  

Capacity exceeded 

 

Note: Only in two filters systems with water meter. 

S   =    

Stop during service 

 

Note: Only where an input with Stop function is selected.  

C   =    

Chemicals shortage 

 

Note: Only where an input for monitoring the chemicals is selected.  

H   =    

Stop during regeneration 

 

Note: Only where an input with Stop function is selected. 

 

 
Where signals cannot be selected in the LCD display, the appropriate program 
step(s) must be altered; e.g. input functions with ‘water meter’, ‘minimum 
regeneration distance’ etc. 
 
 
 
 
 
 
 

Step no.:   18.1 

imp.succes  100l 

Step no.:   18.2 

i.duration  1.0s 

Step no.:   19.1 

M|Wa-P-Ce-S-C-H- 

15.* / 16.* 

20.1-21.1

 

Litres 

18.1 

 

seconds 

18.2 

M  Wa 

19.1 

P  Ce 

C  H 

Содержание ES2030 CV

Страница 1: ...Control for ion exchangers and filter systems Instruction manual Software version 2 03 ES2030 CV...

Страница 2: ...m run 5 Filter capacity 5 Water delivery 6 Input states 6 Output states 6 Service number 6 Software version 6 Programmed inputs 6 Programmed outputs 6 Last regeneration 6 Regeneration ratio 6 Messages...

Страница 3: ...ing 15 6 Delayed regeneration 17 Starting on real time clock 18 7 Interval start of regeneration 18 8 Minimum regeneration distance 19 9 Definition of input functions 20 10 Water meter input 21 Filter...

Страница 4: ...can be set to determine times when regeneration must not take place delayed regeneration A minimum regeneration distance between regenerations prevents regenerations being initiated constantly if the...

Страница 5: ...Start regeneration 12 Information 17 Output 2 LED 3 Regeneration filter 1 8 Supply water 13 Programming 18 Output 1 LED 4 Regeneration filter 2 9 Time 14 LCD display 5 Main fuse 10 Output 1 15 Input 1...

Страница 6: ...eration or The time of the next regeneration if a delayed regeneration has been initiated see program step 6 or The number of hours until the next regeneration see program step 7 or Alternating with t...

Страница 7: ...F 4 199 E 2 99 mg l CaCO3 40 1999 gpg 2 99 no unit 0 01 9999 99 m3 0 02 mmol l 0 10 D 0 13 E 0 18 F 1 79ppm 0 11gpg USA 0 13gpg UK The calculation of the soft water quantity with altered values is car...

Страница 8: ...played MinRg 4 If a minimum regeneration distance was selected during programming at step 8 the time interval in hours is shown Otherwise MinRg is displayed Additional program Bottom left the starting...

Страница 9: ...uts The programmed functions of input IN1 and IN2 if the IF2030 card is fitted are displayed Programming the outputs The programmed functions of output OUT1 and OUT2 are displayed NOTE This display is...

Страница 10: ...al activation of the regeneration e g by a water analysis device the regeneration does not follow as it can be assumed that the hardness warning occurred as a result of a standstill hardening of the s...

Страница 11: ...automatically at the end of set minimum regeneration distance or whether the next regeneration has to be started manually NOTE The message in the LCD display is not cleared until regeneration is start...

Страница 12: ...regeneration interval is reset Special functions These functions should only be used by a professional water treatment specialist as their improper use may lead to malfunctions Filter change over with...

Страница 13: ...eration without initialisation For maintenance purposes it is sometimes necessary to check the regeneration program without initialising the pulse counter or recalculating the filter capacity Simultan...

Страница 14: ...l programming changes the key has to be held down for 4 seconds before the basic values are released for change The LCD display first shows the following message After 4 seconds this changes to NOTE C...

Страница 15: ...12 14 in a four stage valve The fourth stage Service or Standby which follows on at the end of regeneration is not shown Example 4 stage alternate switching The number of stages is determined at progr...

Страница 16: ...valve used to regenerate the two sides of a double filter system alternately In its electric triggering voltage changes between terminals 5 6 and 5 7 immediately the next phase is triggered The fourt...

Страница 17: ...rminals 5 6 and 5 7 12 13 and 12 14 in a four stage valve The fourth stage Service or Standby which follows on at the end of regeneration is not shown Example 4 stage valve SIATA The number of stages...

Страница 18: ...ram step 1 must be programmed in No times are entered for the service or standby phases Enter the switch stage and the required time within the range 1 999 minutes Example for number of switch stages...

Страница 19: ...y For example quantity controlled water softening systems with a shared brine container Series switching Select series switching when the filters in a two filter system were set up in series For examp...

Страница 20: ...r system a 2 filter system connected in series and with a 2 filter system operating in parallel with sequential regeneration It can be determined whether the service valve or both service valves shoul...

Страница 21: ...ns can also be initiated at fixed intervals This periodic initiation is selected where a water meter is not necessary because the amounts of water drawn off are constant It is also used to prevent mic...

Страница 22: ...lly before the set time has elapsed by water meter time interval or analysis device the appropriate message is shown on the LCD display and the built in buzzer sounds if programmed at program step 21...

Страница 23: ...ter SP stop service ST start regeneration CH chemicals shortage HO stop regeneration Input function IN2 Place the cursor under the required input function NOTE This program step can only be selected i...

Страница 24: ...ount The pulse rate of the water meter can be entered as a pulse interval in litres pulse or as a pulse count in pulses litre Water meters without reducing gears also known as turbines emit a high num...

Страница 25: ...55350 Note the capacity for a single filter is always entered regardless of whether the system is made up of one or more filters FILTER SYSTEMS If no supply water hardness was selected at step 10 3 th...

Страница 26: ...tart signal is still present or is resent at the end of the current regeneration NOTE No program data are entered for this function 13 Chemicals shortage input This input can be used to monitor the ch...

Страница 27: ...uired output function AP additional program RG regeneration FP flow pulse WA warning PU flushing NOTE The functions flow pulse and flushing can only be selected if the system Is fitted with a water me...

Страница 28: ...e Values from 1 to 999 minutes can be entered for the switch on time of the additional program Switchover of service valve If phase 0 was entered as switch on point at program step 16 1 it has to be d...

Страница 29: ...dditional relay 1 or 2 selected not selected If more than one signal is selected the relevant relay functions as a combined warning relay M Minimum regeneration distance Note Only where minimum regene...

Страница 30: ...in two filters systems with water meter S Stop during service Note Only where an input with Stop function is selected C Chemicals shortage Note Only where an input for monitoring the chemicals is sel...

Страница 31: ...changer Dual filter Ion exchanger Single run partial desalination system Dual run partial desalination system CV1 SV1 Input1 WM CV1 SV1 Input1 F1 F2 CV2 SV2 WM CV1 SV1 Input1 H Na CV2 SV2 WM Output1 C...

Страница 32: ...e service position phase on terminal 8 15 Remote control valves or pilot distributors without automatic service position connection Two four or five stage Pulse switching Valves with integral programm...

Страница 33: ...tric wiring diagrams 30 Connection of motor valve to potential free relay output Connector OUT1 terminals 3 28 and 29 bridge from 4 to 27 Connector OUT2 terminals 3 31 and 32 bridge from 4 to 30 3 4 2...

Страница 34: ...ES2030 CV Wiring diagram 31...

Страница 35: ...ssible from cables carrying mains power Switch on the unit and carry out the basic programming with the help of this manual and the technical details supplied by the system manufacturer Set the clock...

Страница 36: ...mption 11VA Voltage carrying outputs Max total load capacity 4A Potential free outputs Max load capacity 250V 4A Inputs Load capacity 9V 8 mA Protection class IP65 Ambient temperature 0 50 C Weight Ap...

Страница 37: ...troller for water softening installation Product type ES2030 Manufacturer EWS Equipment for Water treatment Systems International B V Product environment This product is intended for use in residentia...

Страница 38: ...to the carrier e Removal or installation of the product f Any other cause which does not relate to a product defect g Cartons equipment enclosures cables or accessories uses in conjunction with the pr...

Страница 39: ...ally prohibited by applicable law EWS shall not be liable for 1 Damage to other property caused by defects in the EWS product damages based upon inconvenience loss of use of the product loss of time c...

Отзывы: