ES2030 CV
Display and modification of the basic settings
26
18. ‘Flow pulse’ output
If the flow pulse function is selected, the relevant additional relay is activated after
a set amount of water. Values from 1 to 9999 litres can be entered. The next
program step determines how long the relay remains active for each pulse.
This function can be used to control a dosage pump, a dosage controller or as a
flow monitor contact.
Water meter pulses following each other in rapid sequence are recorded and if
necessary passed on at an interval of 0,5 seconds after each other.
Values between 0,5 and 999,9 seconds can be entered for the pulse duration.
19. ‘Warning’ output
During the service and regeneration of the system of the system various signals
occur which can be switched to additional relay 1 or 2.
(‘ | ’ = selected, ‘ - ‘ = not selected).
If more than one signal is selected, the relevant relay functions as a combined
warning relay.
M =
Minimum regeneration distance
Note: Only where ‘minimum regeneration distance’ has been set.
Wa =
Waiting for regeneration to resume
Note: Only where ‘delayed regeneration’ has been set.
P =
Power loss
Ce =
Capacity exceeded
Note: Only in two filters systems with water meter.
S =
Stop during service
Note: Only where an input with Stop function is selected.
C =
Chemicals shortage
Note: Only where an input for monitoring the chemicals is selected.
H =
Stop during regeneration
Note: Only where an input with Stop function is selected.
Where signals cannot be selected in the LCD display, the appropriate program
step(s) must be altered; e.g. input functions with ‘water meter’, ‘minimum
regeneration distance’ etc.
Step no.: 18.1
imp.succes 100l
Step no.: 18.2
i.duration 1.0s
Step no.: 19.1
M|Wa-P-Ce-S-C-H-
15.* / 16.*
20.1-21.1
Litres
18.1
seconds
18.2
M Wa
S
19.1
P Ce
C H