5. Installation Place and Installation drawing
5-1. Installation Place
1.Detection device shall be installed in the place where the leaked
gas easily stays, as the place where gas is easily leaked among
storage facilities and gas facilities.
2.The location where detection device is installed, shall be decided
as per the conditions such as characteristics of gas, instructions,
structure of each device and etc.
3.As for installation height of detection device, if the gas heavier than
air, it shall be installed within 30cm above the floor while if the one
lighter than air, it shall be installed within 30cm below the ceiling.
4.Installation place for receiver device of gas leak alarm device shall
be installed in the proper place to take every measure after alarm is
sounded, as the place where the relevant person resides or the alarm
can be identified.
TONGPRASERTCHAI CO.,LTD.