pro CONTROL BASIC Manual
page 24
7 segm.
display
•
Description / Causes
Notification
contact
No current flow
•
When controlling the outputs with an output level
> 0% no current flows
Alarm is
displayed
-
Cable or plug defective
-
Heating defective
-
Triac defective, does not switch through
-
No heating connected
Relay
•
Internal hardware error - Output relay of the zone
defective
•
Message must be acknowledged
Alarm is
displayed
-
Defect of the device hardware
Current deviation
•
The rated current set in zone parameter
devi-
ates from the current monitoring tolerance set in
zone parameter
.
Alarm is
displayed
-
Heating defective or partially failed
-
Correct rated current set under zone
parameter
?
-
Tolerance band (zone parameter
) too small
Load short circuit
•
An impermissibly high current flows through a short
circuit in the heating circuit
•
Message must be acknowledged
Alarm is
displayed
-
Wiring error
-
Cable or plug defective
-
Line pinch
CAN-Bus fault
•
Communication error of the internal power card
Alarm is
displayed
-
Identical address assigned twice
-
Cable not connected correctly
-
Missing final resistance of the last participant
pro CONTROL BASIC Manual
page 25
7 Functions and parameterization
7.1
Basic settings
(see chapter 5.6.2 System parameter)
7.1.1 Access authorizations
Description
System parameter
: Password
The control unit is protected against unauthorized settings by a password
= identification code
. The password can be individualized after it has
been entered.
System parameter
: User level
The
parameter determines the degree of locking, with which the de-
vice is locked against inputs.
0= No interlock
1= Only setpoints and operating modes free
2= All parameters locked
is always only accessible via the code
System parameter
: Pin Code
If the password
has been changed and is subsequently unknown, the
password can be reset via the parameter
. A master password must
be generated by the manufacturer via the pin shown.
Parameter
System parameter
Settings
ID Code
0…999,
Default value = 22
ID Level
0
…
2, Default value =1
ID Pin Code
(read only, value cannot be
changed)
The release is done
with code "22"
25
pro CONTROL BASIC hot runner controllers – Operating manual