This allows you to select the

minimum number of minutes 

that the fan will run per IAQ mode 

cycle. The thermostat will keep 

track of fan runtime from normal 

heat and cool operation. If addi-

tional fan runtime is needed, the 

thermostat will run the fan to 

satisfy the IAQ mode minutes.

IAQ Mode 

Minutes

Select 1, 5, 10, 15, 20, 30 or 

45 minutes.
When IAQ fan mode is 

enabled, it will ensure the 

fan runs at least the selected 

number of minutes per IAQ 

Mode Cycle. 

This step will not appear if 

previous step is set to “OFF”.

This feature allows a delay to 

occur if an additional stage is 

needed. This allows the previous 

stage extra time to satisfy the 

setpoint.

Staging 

Delay

Use the         or         key to 

turn on or off.

OFF

1

IAQ 
MODE
MINUT

Satisfy 

Setpoint

This feature allows the 

thermostat to keep multiple 

stages of heat or cool energized 

until the setpoint is satisfied.

SS STAGING

Use the         or         key to 

select OFF, 5, 10, 15, 30, 45, 

60, or 90 minutes.

OFF

STAGING dl

The cooling fan delay setting will 

delay the fan from coming on in 

cool mode and keep it running 

after the compressor shuts off 

for a short time to save energy in 

some systems.

Cooling Fan

Delay

OFF

You can set the cooling fan 

delay to OFF, 15, 30, 60 or 90 

seconds. If 15, 30, 60, or 90 is 

selected the fan will not turn 

on for that many seconds 

when there is a call for cool 

and will run for that many 

seconds after satisfying a call 

for cool.

COOL 
FAN DL

IAQ Mode 

Cycle

This feature will configure the fan 

to run a selected number of cycles 

per hour.

Note: This mode can be enabled 

or disabled at anytime during 

normal operation by selecting IAQ 

mode with the fan key.

Select OFF, 1, 2, 3 or 4 with the  

         or         keys.

This sets the number of cycles 

per hour that the IAQ fan mode 

will operate.

OFF

IAQ 
MODE
CYCLES

Tech Setup Steps

Adjustment Options

Default

LCD Will Show

Technician Setup Menu

For Dual Fuel applications (Gas/

Fossil fuel Auxiliary Heat), turn 

this setting ON to LOCKOUT the 

Heat Pump (Y) when Auxiliary 

Heat (W2) is on. If desired - This 

can also be used with Electric 

Auxiliary.

You can configure the system 

switch for the particular appli-

cation.

Heat - Off - Cool, Heat - Off, Cool - 

Off, Heat - Off - Cool - Auto

Note: EM. Heat will show if in 

heat pump mode.

System Set

Use the         or         key until 

the desired application is 

flashing.

Auto= Auto changeover* 

See note below.

You can configure this thermostat 

to operate up to a 2H/2C con-

ventional, or up to a 4H/2C heat 

pump system.

This step is shown only if heat 

pump is set to ON.

Stages of 

Heat + Cool

Use the         or          key to 

first select stages of heat, 

press next- then select 

stages of cool.

3 or 4 heat will use Y1 and Y2 

as 1st and 2nd stage of heat.

Dual Fuel 

Auxiliary for 

Heat Pump

Will only appear if 

Heat Pump setting is 

turned ON

OFF

 Will allow Y(1st stage of 

Heat) and W2 (Aux Heat) to   

run together if called for.

ON

 Will de-energize Y termi-

nal 45 seconds after a call for 

Auxiliary Heat (W2).

Heat Pump

When turned on the thermostat 

will operate a heat pump.

1. EM. Heat will show as an option 

in the system switch.

2. Y will be first stage of heat 

& cool, W/E will be emergency 

heat relay & W2 will be auxiliary 

heat relay.

OFF configures the thermostat 

for non heat pump systems.

ON configures the thermostat 

for heat pump systems.

OFF

HEAT

OFF

COOL

A6

OFF

OFF

2H2C

2

STAGES

Tech Setup Steps

Adjustment Options

Default

LCD Will Show

Technician Setup Menu

This feature allows the installer 

to change the calibration of the 

room temperature display. For 

example, if the thermostat reads 

70˚ and you would like it to read 

72˚ then 2.

OFF

This feature will flash a reminder 

after the elapsed run time to 

remind the user to change the 

filter. A setting of  “OFF” will 

disable this feature.

Filter Change

Reminder

You can adjust the filter 

change reminder from “OFF” 

to 2000 hours of runtime in 

50 hour increments.

Tech Setup Steps

Room

Temperature

Calibration

0˚F

This feature allows the installer 

to select the minimum run 

time for the compressor. For 

example, a setting of 4 will force 

the compressor to run for at 

least 4 minutes every time the 

compressor turns on, regardless 

of the room temperature.

You can set the minimum 

compressor run time to “OFF”, 

“3”, “4”, or “5” minutes. If 3,4 

or 5 is selected, the 

compressor will run for 

at least the selected time 

before turning off.

Minimum 

Compressor 

On Time

OFF

You can adjust the room 

temperature display to read 

up to 4˚above or below the 

factory calibrated reading.

Adjustment Options

Default

LCD Will Show

OFF

SE

CAL

0

O

F

OFF

Technician Setup Menu

This thermostat has a technician setup menu for easy installer 

configuration. To set up the thermostat for your particular application:

1.  Press the 

MENU

 button.

2.  Press and hold the  

TECH

 button for 3 seconds. This 3 second

     delay is designed so that homeowners do not accidentally access

     the  installer settings.

3. Configure the installer options as desired using the table below.

      Use the             or               keys to change settings and the 

NEXT 

      

or 

PREV

 key to move from one step to another.  

      

Note:

 Only press the 

DONE

 key when you want to exit the 

      Technician Setup options.

4. Press the 

DONE

 key to exit.

Keypad Lockout Note:

 The selected keypad lockout functionality must 

be activated after exiting tech setup. If you do not perform this 

procedure, all keys will function freely. To lock the keypad hold down 

the        and        keys for 3 seconds.  You will see a lock in the display. To 

unlock the display hold down the         and         keys for 3 seconds.

The compressor short cycle delay 

protects the compressor from 

“short cycling”. This feature will 

not allow the compressor to be 

turned on for 5 minutes after it 

was last turned off.

Compressor

Short Cycle

Delay

ON

Selecting “ON” will not allow 

the compressor to be turned 

on for 5 minutes after the 

last time the compressor was 

on. Select “OF” to remove 

this delay.

ON

OF

Tech Setup Steps

Adjustment Options

Default

LCD Will Show

Keypad 

Lockout

Keypad lockout allows you to 

configure the thermostat so that 

some or all of the keys don’t 

function.

OF= keypad lockout has been 

disabled.

PA= partial keypad lockout, 

which locks all the keys except 

the         or          keys.

FU= full keypad lockout, 

which locks out all the keys.

PA

See Keypad Lockout Note

PA

The swing setting often called 

“cycle rate”, “differential” or

“anticipation” is adjustable. A 

smaller swing setting will cause 

more frequent cycles and a larger 

swing setting will cause fewer 

cycles.

Cooling 

Swing

The cooling swing setting 

is adjustable from 0.2˚ to 

2˚. For example: A swing 

setting of 0.5˚ will turn the 

cooling on at approximately 

0.5˚ above the setpoint 

and turn the cooling off at 

approximately 0.5˚ below 

the setpoint.

The swing setting often called 

“cycle rate”, “differential”, or 

“anticipation” is adjustable. A 

smaller swing setting will cause 

more frequent cycles and a larger 

swing setting will cause fewer 

cycles.

Heating 

Swing

dFCO

0.5˚

The heating swing setting is 

adjustable from 0.2˚ to 2˚. 

For example: A swing setting 

of 0.5˚ will turn the heating 

on at approximately 0.5˚ 

below the setpoint and turn 

the heating off at 0.5˚ above 

the setpoint.

0.4˚

dFHE

Swing Setting Tip

The second stage will turn on at 2x the swing setting.  The second stage 

will turn off when 1x the swing is reached. For example, if the swing 

setting is .5 degrees for heating and the thermostat is set at 70

˚

F, the first 

stage will turn on at approximately 69.5

˚

F.  The second stage will turn on 

at 69

˚

F. The second stage will turn off at 69.5

˚

F and the first will turn off 

at 70.5

˚

F.  If the third stage is used, it will turn on at 68.5

˚

F and turn off at 

approximately 69

˚

F.

Technician Setup Menu

HEAT OFF
COOL

SE

OFF

10

OFF

OFF

OFF

Auto Changeover Note:

 When using Auto Changeover you must 

maintain at least a 3° differential with the Heat and Cool setpoints.

Содержание EWT-855i

Страница 1: ...provided 3 Drywall anchors should be flush with the wall 4 Wires should be pushed into the wall Installation Tips The thermostat should be installed approximately 4 to 5 feet above the floor Select an area with average temperature and good air circulation Close to hot or cold air ducts That are in direct sunlight With an outside wall behind the thermostat In areas that do not require conditioning ...

Страница 2: ... electrical shock or equipment damage Note In many heat pump systems with no emergency heat relay a jumper can be installed between E and W2 to turn thermostat into a single stage control for Emergency Heat Operation Thermostat Quick Reference Indicates the current room temperature Time and day of the week Staging Indicators Indicates stages of heat or cool running The compres sor delay feature is...

Страница 3: ...or2H 1CHeatPumpSystem TypicalHeat OnlySystem TypicalHeatOnlySystemWithFan TypicalCool OnlySystem HEAT RELAY RC RH Y C W E G C R L2 L1 HOT FAN RELAY HEAT RELAY RC RH Y C W E G C R L2 L1 HOT FAN RELAY COMPRESSOR RELAY C R L2 L1 HOT RC RH Y C G Power supply Factory installed jumper Remove only when installing on 2 transformer systems Use either O or B terminals for changeover valve A24VACcommonconnec...

Страница 4: ...rom OFF to 2000 hours of runtime in 50 hour increments Tech Setup Steps Room Temperature Calibration 0 F This feature allows the installer to select the minimum run time for the compressor For example a setting of 4 will force the compressor to run for at least 4 minutes every time the compressor turns on regardless of the room temperature You can set the minimum compressor run time to OFF 3 4 or ...

Страница 5: ...ccupancy fan settings will energize the fan before the occupied time to provide ventilation prior to scheduled occupancy This feature only shows if the technician setup step for time periods is set to 2 Pre Occupancy Fan You can select the pre occupancy fan from OFF 1 2 or 3 hours If 1 2 or 3 is selected the fan will turn on that many hours prior to the scheduled occupied time period Tech Setup St...

Страница 6: ... day s SLEEP time period To customize your 7 day Program schedule follow these steps Monday WAKE LEAVE RETURN or SLEEP Repeat steps 4 through 8 for the remaining days of the week A Note About Auto Changeover In Auto you have the ability to switch between Auto Heat or Auto Cool by pressing the system key This can be done once the current mode has reached its setpoint For example if in Auto Heat the...

Страница 7: ... for any time period 1 Select HEAT or COOL with the SYSTEM key Note You have to program heat and cool each seperately 2 Press the MENU button If menu does not appear first press RUN 3 Press SCHED Note Monday is displayed and the OCCUPIED text is shown You are now programming the OCCUPIED time period for that day 4 Time is flashing Use the or key to make your time selection for that day s OCCUPIED ...

Страница 8: ... replace the temporary setpoint Permanent Hold With a temporary hold set If you press the HOLD key at the bottom of your screen you will see HOLD appear below the setpoint temperature in the display The thermostat will now permanently stay at this setpoint and can be adjusted using the or keys To Return To Program Press the RUN key at the bottom of the screen to exit temporary and permanent holds ...

Отзывы: