Reminders

Once a reminder has been turned on and set, the elapsed time can be 

checked by navigating to its tech setup step.  The elapsed time will then 

appear in the text field.  It can also be reset at that time by holding down 

the set time/run sched button for 3 seconds.  Resetting an expired 

reminder can be done without entering tech setup, by holding down 

the set time/run sched button for 3 seconds from the home screen.

A Note about IAQ Mode

This programmable/selectable mode will operate the fan 1-4 cycles per 

hour, 1-45 minutes per cycle. Once programmed in tech setup, to enable 

this mode select “IAQ” with the fan key.  Disable this mode by selecting 

“ON” or “AUTO” with the fan key.

Enables a reminder for the user to 

change the humidity pad.

Humidity Pad

Reminder 

Enables a reminder for the user to 

change the UV light bulb.

UV Lamp

Reminder

OFF

Use the         or         key to 

select OFF, 600, 1000, 1500, 

or 2000. These represent 

hours of heat operation.

Enables a reminder for the user 

to change the PHI Cell after 

25,000 hrs.

IAQ Cell 

Reminder

Use the         or         key to 

select OFF, or 250 (stands for 

25,000 hours).

OFF

HUM PAD 2000

OFF

UVLAMP 00000

Use the         or         key to 

select OFF, 1YEAR, 2YEAR.

OFF

OFF

250

Tech Setup Steps

Adjustment Options

Default

LCD Will Show

Technician Setup Menu

Programming

Set Time

Follow the steps below to set the day of the week and current time:

1. 

 Press the 

MENU

 button.

2.

  Press 

SET TIME.

3.

  Day of the week is flashing. Use the              or              key to 

      select the current day of the week.

4.

  Press 

NEXT.

5.

  The current hour is flashing.  Use the              or               key to  

      select the current hour.  When using 12-hour time, make sure

      the correct a.m. or p.m. choice is selected.

6.

  Press 

NEXT.

7.

  Minutes are now flashing.  Use the              or              key to 

      select current minutes.

8.

  Press 

DONE

 when completed.

(If using programming)

All our programmable thermostats are shipped with an energy saving default 

program. You can customize this default program by following the 

instructions in the 

set program schedule section

 starting on page 24.

Programming

Your thermostat can be programmed to have each day of the week 

programmed uniquely (7 days), all the weekdays the same with a separate 

program for Saturday and a separate program for Sunday (5+1+1), or 

non-programmable. For the 7-day and 5+1+1 programming modes, there are 

three time period options. 

1. “4” Residential 

(WAKE, LEAVE, RETURN, SLEEP) 

2. “2C” Commercial 

(OCCUPIED, UNOCCUPIED) 

3. “4C” Commercial 

(OCCUPIED 1, UNOCCUPIED 1, OCCUPIED 2, UNOCCUPIED 2)

This thermostat has a programmable fan feature, which allows you to run the 

fan continually during any time period.

This feature allows you to set a 

minimum cooling setpoint limit. 

The setpoint temperature cannot 

be lowered below this value.

This feature allows you to set a 

maximum heating setpoint limit. 

The setpoint temperature cannot 

be raised above this value.

Heating 

Temperature 

Setpoint 

Limit

Use the         or         key to 

select the maximum heat 

setpoint.

This feature allows you to display 

temperatures in either Fahrenheit 

or Celsius.

˚F or ˚C

˚F

˚F for Fahrenheit

˚C for Celsius

You can select either a 12 or 24 

hour clock setting.

12 or 24

Hour Clock 

Select GAS for systems that 

control the fan during a call for 

heat. Select ELEC to have the 

thermostat control the fan during 

a call for heat.

Fan 

Operation

90

78

12H

12

HOUR CLOCK

GAS

ELE

Cooling 

Temperature 

Setpoint 

Limit

Use the         or         key to 

select the minimum cool 

setpoint.

44

44˚F

90˚F

HE

CO

O

F

Use the         or         key to 

select 12 or 24 hour clock.

GAS or ELEC

This feature will start heating 

early to bring the building 

temperature to its programmed 

setpoint by the beginning of the 

WAKE, OCCUPIED time period. 

Morning 

Recovery

ON

Use the         or         key to 

turn on or off.

You can configure this thermostat 

to have a 7 day program, a 

5+1+1 program or as

nonprogrammable.

Program 

Options

5d

Use the         or         key to 

select 

7d

 for 7 day, 

5d

 for 

5+1+1, or 

0d

 for 

nonprogrammable.

5d

The display light can be 

configured to stay on all the 

time or come on when any key 

is pressed.

NOTE: HARDWIRE ONLY

Keeping the display light 

continually “ON” will greatly 

reduce battery life.

The pre-occupancy fan settings 

will energize the fan before 

the occupied time to provide 

ventilation prior to scheduled 

occupancy.

This feature only shows if the

technician setup step for time 

periods is set to 2C or 4C.

Pre-Occupancy 

Fan

You can select the 

pre-occupancy fan from OFF, 

1, 2, or 3 hours.

If 1, 2, or 3 is selected, the 

fan will turn on that many 

hours prior to the scheduled 

occupied time period.

Tech Setup Steps

Allows you to put your phone 

number in the display.

You can choose ON or OFF.

Contractor 

Call Number

If selected ON, you will 

see the input screen after 

pressing

 NEXT STEP

.

Use the          or         key to 

select the desired number 

and the 

FAN

 or 

SYSTEM

 key 

to move from one character 

to another. See note below 

for operation.

Adjustment Options

Default

LCD Will Show

When any key is pressed an 

audible beep will sound.

You can choose ON or OFF.

Beep 

PRE 
OCCUPY 
FAN

Display Light

Use the         or         key to to 

turn on or off.

OFF configures the display 

light to come on when the 

light key or any button is 

pressed.

ON configures the display 

light to stay on.

Time Periods

You can configure this thermostat

to have 2 or 4 programmable time 

periods per day. 4 time periods 

are Wake, Leave, Return & Sleep. 

2C time periods are Occupied 

& Unoccupied. 4C time periods 

are Occupied 1, Unoccupied 1, 

Occupied 2, & Unoccupied 2.

Use the          or          key to 

select 

4

2c

, or 

4c

 time periods 

per day.

4

OFF

OFF

dL

If ON is selected the beep 

will sound.

If OFF is selected there is no 

sound.

4

OFF

OFF

ON

b

Tech Setup Steps

Adjustment Options

Default

LCD Will Show

Contractor Call Number Note

If contractor call number is selected ON, the phone number entered will 

show in the display if there has been a continuous call for heating or 

cooling for 24 hours or if the light button is held down for 3 seconds.  To 

remove the phone number from the display, hold the light button down 

for 3 seconds. 

Technician Setup Menu

Technician Setup Menu

OFF

4

MORN RECOV

PROGRAM

TIME PERIOD

Содержание EWT-855

Страница 1: ...to a flat wall 2 Use screws provided 3 Drywall anchors should be flush with the wall 4 Wires should be pushed into the wall Installation Tips The thermostat should be installed approximately 4 to 5 feet above the floor Select an area with average temperature and good air circulation Close to hot or cold air ducts That are in direct sunlight With an outside wall behind the thermostat In areas that ...

Страница 2: ... to install this product can cause electrical shock or equipment damage Note In many heat pump systems with no emergency heat relay a jumper can be installed between E and W2 to turn thermostat into a single stage control for Emergency Heat Operation Thermostat Quick Reference The low battery indicator is displayed when the AA battery power is low If the user fails to replace the battery within 21...

Страница 3: ...rmer Typical2H 2CSystem 2Transformer Typical3H 2Cor2H 1CHeatPumpSystem TypicalHeat OnlySystem TypicalHeatOnlySystemWithFan TypicalCool OnlySystem HEAT RELAY RC RH Y C W E G C R L2 L1 HOT FAN RELAY HEAT RELAY RC RH Y C W E G C R L2 L1 HOT FAN RELAY COMPRESSOR RELAY C R L2 L1 HOT RC RH Y C G Power supply Factory installed jumper Remove only when installing on 2 transformer systems Use either O or B ...

Страница 4: ...You can adjust the filter change reminder from OFF to 2000 hours of runtime in 50 hour increments Tech Setup Steps Room Temperature Calibration 0 F This feature allows the installer to select the minimum run time for the compressor For example a setting of 4 will force the compressor to run for at least 4 minutes every time the compressor turns on regardless of the room temperature You can set the...

Страница 5: ...t This feature allows you to display temperatures in either Fahrenheit or Celsius F or C F F for Fahrenheit C for Celsius You can select either a 12 or 24 hour clock setting 12 or 24 Hour Clock Select GAS for systems that control the fan during a call for heat Select ELEC to have the thermostat control the fan during a call for heat Fan Operation 90 78 12H 12 HOURCLOCK GAS ELE Cooling Temperature ...

Страница 6: ...th the FAN key 5 Press NEXT 6 The setpoint temperature is flashing Use the or key to make your setpoint selection for that day s WAKE OCC1 period 7 Press NEXT 8 Repeat steps 4 through 7 for that day s LEAVE UNOCC1 time period for that day s RETURN OCC2 time period and for that day s SLEEP UNOCC2 time period To customize your 7 day 4 time period Program schedule follow these steps Monday Repeat ste...

Страница 7: ...tpoint and can be adjusted using the or keys To Return To Program Press the RUN SCHED key at the bottom of the screen to exit temporary and permanent holds Temporary Permanent Hold Feature Custom Program Day of the Week Events Time Setpoint Temperature HEAT Setpoint Temperature COOL Weekday Saturday Sunday Wake OCC1 Leave UNOCC1 Return OCC2 Sleep UNOCC2 Wake OCC1 Leave UNOCC1 Return OCC2 Sleep UNO...

Страница 8: ...on condensing maximum Dimensions of thermostat 4 7 W x 4 3 H x 0 9 D Specifications Features If the filter change reminder is enabled you will see a reminder in the display when your air filter needs changed The reminder will be shown in the display after your system has run long enough to require an air filter change Resetting The Filter Change Reminder When the reminder is displayed you should c...

Отзывы: