Reminders
Once a reminder has been turned on and set, the elapsed time can be
checked by navigating to its tech setup step. The elapsed time will then
appear in the text field. It can also be reset at that time by holding down
the set time/run sched button for 3 seconds. Resetting an expired
reminder can be done without entering tech setup, by holding down
the set time/run sched button for 3 seconds from the home screen.
A Note about IAQ Mode
This programmable/selectable mode will operate the fan 1-4 cycles per
hour, 1-45 minutes per cycle. Once programmed in tech setup, to enable
this mode select “IAQ” with the fan key. Disable this mode by selecting
“ON” or “AUTO” with the fan key.
Enables a reminder for the user to
change the humidity pad.
Humidity Pad
Reminder
Enables a reminder for the user to
change the UV light bulb.
UV Lamp
Reminder
OFF
Use the or key to
select OFF, 600, 1000, 1500,
or 2000. These represent
hours of heat operation.
Enables a reminder for the user
to change the PHI Cell after
25,000 hrs.
IAQ Cell
Reminder
Use the or key to
select OFF, or 250 (stands for
25,000 hours).
OFF
HUM PAD 2000
OFF
UVLAMP 00000
Use the or key to
select OFF, 1YEAR, 2YEAR.
OFF
OFF
250
Tech Setup Steps
Adjustment Options
Default
LCD Will Show
Technician Setup Menu
Programming
Set Time
Follow the steps below to set the day of the week and current time:
1.
Press the
MENU
button.
2.
Press
SET TIME.
3.
Day of the week is flashing. Use the or key to
select the current day of the week.
4.
Press
NEXT.
5.
The current hour is flashing. Use the or key to
select the current hour. When using 12-hour time, make sure
the correct a.m. or p.m. choice is selected.
6.
Press
NEXT.
7.
Minutes are now flashing. Use the or key to
select current minutes.
8.
Press
DONE
when completed.
(If using programming)
All our programmable thermostats are shipped with an energy saving default
program. You can customize this default program by following the
instructions in the
set program schedule section
starting on page 24.
Programming
Your thermostat can be programmed to have each day of the week
programmed uniquely (7 days), all the weekdays the same with a separate
program for Saturday and a separate program for Sunday (5+1+1), or
non-programmable. For the 7-day and 5+1+1 programming modes, there are
three time period options.
1. “4” Residential
(WAKE, LEAVE, RETURN, SLEEP)
2. “2C” Commercial
(OCCUPIED, UNOCCUPIED)
3. “4C” Commercial
(OCCUPIED 1, UNOCCUPIED 1, OCCUPIED 2, UNOCCUPIED 2)
This thermostat has a programmable fan feature, which allows you to run the
fan continually during any time period.
This feature allows you to set a
minimum cooling setpoint limit.
The setpoint temperature cannot
be lowered below this value.
This feature allows you to set a
maximum heating setpoint limit.
The setpoint temperature cannot
be raised above this value.
Heating
Temperature
Setpoint
Limit
Use the or key to
select the maximum heat
setpoint.
This feature allows you to display
temperatures in either Fahrenheit
or Celsius.
˚F or ˚C
˚F
˚F for Fahrenheit
˚C for Celsius
You can select either a 12 or 24
hour clock setting.
12 or 24
Hour Clock
Select GAS for systems that
control the fan during a call for
heat. Select ELEC to have the
thermostat control the fan during
a call for heat.
Fan
Operation
90
78
12H
12
HOUR CLOCK
GAS
ELE
Cooling
Temperature
Setpoint
Limit
Use the or key to
select the minimum cool
setpoint.
44
44˚F
90˚F
HE
CO
O
F
Use the or key to
select 12 or 24 hour clock.
GAS or ELEC
This feature will start heating
early to bring the building
temperature to its programmed
setpoint by the beginning of the
WAKE, OCCUPIED time period.
Morning
Recovery
ON
Use the or key to
turn on or off.
You can configure this thermostat
to have a 7 day program, a
5+1+1 program or as
nonprogrammable.
Program
Options
5d
Use the or key to
select
7d
for 7 day,
5d
for
5+1+1, or
0d
for
nonprogrammable.
5d
The display light can be
configured to stay on all the
time or come on when any key
is pressed.
NOTE: HARDWIRE ONLY
Keeping the display light
continually “ON” will greatly
reduce battery life.
The pre-occupancy fan settings
will energize the fan before
the occupied time to provide
ventilation prior to scheduled
occupancy.
This feature only shows if the
technician setup step for time
periods is set to 2C or 4C.
Pre-Occupancy
Fan
You can select the
pre-occupancy fan from OFF,
1, 2, or 3 hours.
If 1, 2, or 3 is selected, the
fan will turn on that many
hours prior to the scheduled
occupied time period.
Tech Setup Steps
Allows you to put your phone
number in the display.
You can choose ON or OFF.
Contractor
Call Number
If selected ON, you will
see the input screen after
pressing
NEXT STEP
.
Use the or key to
select the desired number
and the
FAN
or
SYSTEM
key
to move from one character
to another. See note below
for operation.
Adjustment Options
Default
LCD Will Show
When any key is pressed an
audible beep will sound.
You can choose ON or OFF.
Beep
PRE
OCCUPY
FAN
Display Light
Use the or key to to
turn on or off.
OFF configures the display
light to come on when the
light key or any button is
pressed.
ON configures the display
light to stay on.
Time Periods
You can configure this thermostat
to have 2 or 4 programmable time
periods per day. 4 time periods
are Wake, Leave, Return & Sleep.
2C time periods are Occupied
& Unoccupied. 4C time periods
are Occupied 1, Unoccupied 1,
Occupied 2, & Unoccupied 2.
Use the or key to
select
4
,
2c
, or
4c
time periods
per day.
4
OFF
OFF
dL
If ON is selected the beep
will sound.
If OFF is selected there is no
sound.
4
OFF
OFF
ON
b
Tech Setup Steps
Adjustment Options
Default
LCD Will Show
Contractor Call Number Note
If contractor call number is selected ON, the phone number entered will
show in the display if there has been a continuous call for heating or
cooling for 24 hours or if the light button is held down for 3 seconds. To
remove the phone number from the display, hold the light button down
for 3 seconds.
Technician Setup Menu
Technician Setup Menu
OFF
4
MORN RECOV
PROGRAM
TIME PERIOD