ISOLATING 24vac SHORTS

Dampers not responding and THE

BMPLUS 3000 LED’s are off.

HVAC system not responding and

BMPLUS 3000 LED’s are off.

DETECTING 24vac SHORTS

Check HVAC & BMPlus system transformer supply voltage.
Check HVAC & BMPlus system 24vac transformer voltage, fuse & the BMPlusB 
circuit breaker.
Check HVAC & BMPlus system wiring for shorts/miswiring.

Check HVAC system wiring for shorts/miswiring.
Check HVAC system wiring for proper connections. 
Check HVAC thermostat for proper connections.
Refer to Technical Bulletin for correct Setup/Wiring/Dip Switch settings.

Check HVAC system wiring for proper connections. 
Check HVAC system wiring for shorts/miswiring.
Check HVAC System.
Refer to Technical Bulletin for correct Setup/Wiring/Dip Switch settings.

SOLUTIONS

T R O U B L E S H O O T I   N  G

REFER TO THE DAMPER MOTOR TESTING PAGE 9

LED’s illuminate and HVAC system 

functions normally but dampers do 

not respond.

Check damper motor wiring for proper connections.
Check damper motor 24vac transformer voltage/fuse/BMPlus circuit breaker.
Check damper motor wiring for shorts/miswiring.
Refer to Technical Bulletin for correct Setup/Wiring.

F1 circuit breaker protects the 

BMPlus 3000 and reacts to a short in 

the damper motor or thermostat 

component and field wiring. 

CHECK YOUR WIRING

EWC Controls provides superior toll free Troubleshooting Support for the BMPlus 3000 when you are on the job site! 

 

Call 1-800-446-3110  Monday - Friday 8am to 5pm EST
Otherwise call 1-732-446-3110 for information on the BMPlus 3000 and other ULTRA-ZONE products..

When calling for Technical Support, please have a multi-meter, pocket screwdriver, and wire cutter/stripper handy. 

TECHNICAL SUPPORT

LED’s do not illuminate and HVAC 

system does not respond.

LED’s are not responding properly 

and HVAC system is malfunctioning.

LED’S are responding properly but 

HVAC system is malfunctioning.

SYMPTOM

Disconnect  the wire(s) from the ‘R’

 terminals on the BMPlus 3000 thermostat 

terminal blocks , 

and the 

“M2/M4/M6’’ terminals

 on the BMPlus 3000 damper 

motor terminal blocks.  Restore power.  If the short is no longer present, Ohm 
out the thermostat and damper field wiring for shorts/misconnections. Replace 
or repair wires as necessary. Restore power. Module(s) will resume operation.

SOLUTIONS:

 

Remove 24vac power from BMPlus 3000 and allow circuit breaker to cool!

                  Find and repair short(s) in damper and/or thermostat field wiring. Restore 24 vac power.

If 24vac short has occurred, 24vac will be present at the

 BMPlus 3000 Module 

Input terminals R & C;

 but 24vac will not be present at the 

Thermostat R&C.

 

SYMPTOMS: Module(s) appear to be dead!

TESTING THERMOSTATS

Check to make sure that the thermostat Rc and Rh terminals are connected together, unless your application requires 
separation of these circuits.

Use the (C) Common  terminal provided at each thermostat terminal block to wire up full 24 vac hard-wired thermostats. 

You should reference the (C) Common terminal when troubleshooting incoming thermostat demand signals, even if no wire is 
connected there. 

Make sure that you wire and configure your thermostats for the correct application. Most thermostats built today can be field 
configured to operate as regular Heat/ Cool type or as Heat Pump type. Remember that you can use regular Heat/Cool 
thermostats on the BMPlus 3000 for Heat Pump applications.

EWC Controls Inc.   385 Highway 33    Englishtown, NJ 07726   800-446-3110   FAX 732-446-5362      E-Mail- [email protected]

16

Содержание BMPlus 3000

Страница 1: ...or fan and only the dampers in zones calling for continuous fan operation will open Continuous fan operation will only occur when there are no active or pending heat or cool demands A dip switch is provided to enable automatic fan operation in heat mode Useful for straight electric heat or hydronic heat applications Zone Capacity Compatible HVAC Systems Compatible Thermostats Automatic Heat Cool C...

Страница 2: ...e heat supply air temperature at which the heating is cycled off and the fan continues to run allowing the heat exchanger or coil to cool down NOTE Allows the supply air sensor to be installed in the supply air plenum regardless of the coil heat exchanger configuration Allows the installer to fine tune virtually any multi stage heating system RESET EM NORM An On Board Switch is provided that allow...

Страница 3: ...t want to use the supply air sensor included with the BMPlus Zone Control system Select ON if you intend to use the included supply air sensor Refer to the data sheet included with the supply air sensor for details Select GAS if your HVAC system is a gas or oil forced air furnace Select HYDRONIC if your HVAC system has a hot water coil or straight electric heat with no indoor blower support Useful...

Страница 4: ...uit board when removing the knockouts and making wire connections NOTE The 24vac power supply should be supplied by a separate transformer DO NOT use the 24vac power supply from the HVAC system unless there is no other alternative 2 zones and 2 dampers is the limit when stealing voltage from the HVAC system NOTE The BMPlus 3000 allows the user to install Heat Pump thermostats on all zones You may ...

Страница 5: ...Forced Air heat is controlled through the zone panel ZONE2 T STAT Y R G O B W E C G W1 RH RC Y W2 C To Radiant floor Baseboard heat zone valve or pump relay SPST 24vac Isolation Relay HEAT COOL THERMOSTAT MULTISTAGE HEAT COOL THERMOSTAT Thermostat should be battery powered Figure 3 ZONE T STAT C W E Y R G O B C W E B W2 Y1 O RC RH MODEL EWT 955WH H D Y2 Model EWT 955WH Wireless Thermostat Configur...

Страница 6: ... the thermostat auxiliary heat demand is satisfied the BMPlus 3000 will stage down unless DF or OAS has been selected and the outdoor temperature is lower than the OAS changeover setting In that case the system will continue in FUEL mode until all current heating demands are satisfied Note Your Air Handler may include a W terminal That means it may have it s own isolation circuit If you can confir...

Страница 7: ...F OUTSIDE AIR CHANGEOVER OPERATES WITH MULTI STAGE HEATPUMPS STATUS LED s ARE INCLUDED ON ALL MODULES 1 ZONE MODE COMPLIES WITH CALIFORNIA TITLE 24 SIMPLIFIED WIRING AND EASY SYSTEM SETUP The BMPlus 3000 is compatible with Dual Fuel Heat Pumps Dual Fuel kits are not required Select staging based on Adjustable Time Delay or an Optional Outside Air temperature Sensor The intelligent firmware does th...

Страница 8: ... All Models RSD Damper Wiring All Models ND URD and SID Damper Wiring Figure 14 On all these dampers and most older style dampers including competitor s dampers always wire up number to number or designation to designation Do not overload your transformer Contact EWC Controls Technical Support when you are on the job site for assistance with damper wiring Have a Multi Meter pocket screw driver and...

Страница 9: ... DAMPER MOTORS SR ESR RSD Power Open Spring Close Dampers Connect 24vac common hot to the two motor M terminals Damper should Open Remove 24vac hot Damper should Close ND URD SMD BMD Dampers Connect 24vac common to terminal 1 and 24vac hot to terminal 4 Damper should Open Remove 24vac hot from terminal 4 and apply to terminal 6 Damper should Close RDN SMDL BMDL Dampers Connect 24vac common to term...

Страница 10: ... indicate that damper s is energized open and the Zone is active The ZONE 1 LED will illuminate solid to indicate that damper s is energized open and the Zone is active The FAN LED will illuminate solid to indicate a demand for fan operation during COOLING HEATING PURGE or CONTINUOUS FAN operations Y1 Y2 W1 B RED W2 E RED The Y2 LED illuminates solid to indicate the 2nd stage of DX COOLING or DX H...

Страница 11: ...it Breaker Isolated Common terminal Useful when HVAC troubleshooting System Status LED s Figure 19 J1 ZONE3 MOTOR ZONE2 MOTOR MOTOR ZONE1 24 T FORMER VAC SYSTEM M6 M4 M2 M1 M6 M4 M2 M1 M6 M4 M2 M1 R C G Y2 Y1 O RH RC W1 B W2 E LINK RH RC D4 3 D C1 C2 SAS SAS OAS OAS C W E O B Y R G ONE ZONE EM NORM SW4 ZONE1 STAT T D11 D12 D13 D10 2ND STAGE HEAT DIFFERENTIAL LIMIT HIGH TEMP LOW TEMP LIMIT TIMER OA...

Страница 12: ...5 28 21 14 7 OFF W2 EM B 1 W 1 2 Y Y ZONE ZONE ZONE FAN 1 2 3 STATUS OAS SAS 38 39 R R R 37 R 36 R76 77 R 72 R 73 R R70 69 R 67 R 68 R 65 R R64 71 R R63 62 R R61 60 R 59 R 58 R R57 56 R 55 R 54 R R78 79 R 53 R 52 R R51 50 R 49 R 48 R R47 46 R 45 R 81 R R40 43 R R42 41 R 10 LED 9 LED 8 LED 7 LED 6 LED 5 LED 4 LED 3 LED 2 LED 1 LED 11 LED 6 U U7 U8 5 U 4 U U2 3 U U1 1 K 2 K 3 K 4 K 5 K 6 K 7 K 8 K R...

Страница 13: ...MIT TIMER OAS STAGING 47 5 40 33 26 19 12 110 120 130 140 150 160 170 52 49 46 43 40 37 34 42 35 28 21 14 7 OFF W2 EM B 1 W 1 2 Y Y ZONE ZONE ZONE FAN 1 2 3 STATUS OAS SAS 38 39 R R R 37 R 36 R76 77 R 72 R 73 R R70 69 R 67 R 68 R 65 R R64 71 R R63 62 R R61 60 R 59 R 58 R R57 56 R 55 R 54 R R78 79 R 53 R 52 R R51 50 R 49 R 48 R R47 46 R 45 R 81 R R40 43 R R42 41 R 10 LED 9 LED 8 LED 7 LED 6 LED 5 L...

Страница 14: ...D 13 D 10 2 ND STAGE HEAT DIFFERENTIAL LIMIT HIGH TEMP LOW TEMP LIMIT TIMER OAS STAGING 47 5 40 33 26 19 12 110 120 130 140 150 160 170 52 49 46 43 40 37 34 42 35 28 21 14 7 OFF W 2 EM B 1 W 1 2 Y Y ZONE ZONE ZONE FAN 1 2 3 STATUS OAS SAS 38 39 R R R 37 R 36 R 76 77 R 72 R 73 R R 70 69 R 67 R 68 R 65 R R 64 71 R R 63 62 R R 61 60 R 59 R 58 R R 57 56 R 55 R 54 R R 78 79 R 53 R 52 R R 51 50 R 49 R 4...

Страница 15: ...10 2 ND STAGE HEAT DIFFERENTIAL LIMIT HIGH TEMP LOW TEMP LIMIT TIMER OAS STAGING 47 5 40 33 26 19 12 110 120 130 140 150 160 170 52 49 46 43 40 37 34 42 35 28 21 14 7 OFF W 2 EM B 1 W 1 2 Y Y ZONE ZONE ZONE FAN 1 2 3 STATUS OAS SAS 38 39 R R R 37 R 36 R 76 77 R 72 R 73 R R 70 69 R 67 R 68 R 65 R R 64 71 R R 63 62 R R 61 60 R 59 R 58 R R 57 56 R 55 R 54 R R 78 79 R 53 R 52 R R 51 50 R 49 R 48 R R 4...

Страница 16: ...t screwdriver and wire cutter stripper handy TECHNICAL SUPPORT LED s do not illuminate and HVAC system does not respond LED s are not responding properly and HVAC system is malfunctioning LED S are responding properly but HVAC system is malfunctioning SYMPTOM Disconnect the wire s from the R terminals on the BMPlus 3000 thermostat terminal blocks and the M2 M4 M6 terminals on the BMPlus 3000 dampe...

Отзывы: