GMS
plus
Functions
4.
23
Measuring ranges
passive mA sensors
The passive mA sensor measuring ranges are freely scalable
between 0 – 1000.
The sensor type and unit are variably definable.
mA outputs
The sensor channel I and II gas concentrations and the
temperature I are output via analog outputs (4 – 20 mA).
Links
An RS485 interfaces is integrated to link to the Process Monitoring
System, CMS, ChemWeb server and OPC server.
As an option, a configured Wallace & Tiernan RS232 printer can
be linked via the RS485 interface, if the printer distance is <15 m.
Safety functions
The following safety functions are integrated into the control if
configured accordingly:
• Access code protection (level 1).
• Maximum value and average value over the past 8 hours are
displayed.
• Each sensor channel has two isolated alarm outputs with
adjustable switching threshold, delay and alarm mode
(latched, unlatched, etc.).
• For example, alarm 1 can be used as the preliminary alarm
and alarm 2 as the main alarm. Each alarm is assigned a
relay.
• A min and max limit value can be set for each temperature
measurement.
• The installed sensor alarm activates if there is an error on the
sensor (short circuit, line break, etc.).
• The sensor alarm is assigned a relay (K8). You may select
which sensor alarm can trigger the sensors (Sensor I, Sensor
II, Temp I, Temp II).
• Three variably definable common alarms can be configured.
Multiple assignments are possible, for example:
Alarm 1/2 of sensor I
Alarm 1/2 of sensor II
Power failure
Battery error
Temperature I Min/Max
Temperature II Min/Max
Test function
The integrated test function simulates a sensor current that
corresponds to the measuring range end value. It can be used to
test the measured value display as well as the set alarms.
Содержание WALLACE & TIERNAN GMS PLUS
Страница 1: ...WALLACE TIERNAN GAS MONITORING SYSTEM GMS PLUS INSTRUCTION MANUAL...
Страница 2: ...2 WT 050 455 000 DE IM 0319 GMS plus Please note Original instruction manual...
Страница 20: ...20 WT 050 455 000 DE IM 0319 Description GMS plus 3...
Страница 38: ...38 WT 050 455 000 DE IM 0319 Functions GMS plus 4...
Страница 76: ...76 WT 050 455 000 DE IM 0319 Operation GMS plus 6 General overview...
Страница 94: ...94 WT 050 455 000 DE IM 0319 Operation GMS plus 6...
Страница 103: ...GMS plus Wiring diagrams 9 103 9 Wiring diagrams...
Страница 104: ...104 WT 050 455 000 DE IM 0319 Wiring diagrams GMS plus 9...
Страница 105: ...GMS plus Wiring diagrams 9 105...
Страница 106: ...106 WT 050 455 000 DE IM 0319 Wiring diagrams GMS plus 9...
Страница 107: ...GMS plus Wiring diagrams 9 107...
Страница 108: ...108 WT 050 455 000 DE IM 0319 Wiring diagrams GMS plus 9...
Страница 109: ...GMS plus Declaration of conformity 10 109 10 Declaration of conformity...
Страница 110: ...110 WT 050 455 000 DE IM 0319 Declaration of conformity GMS plus 10...
Страница 114: ...114 WT 050 455 000 DE IM 0319 Index GMS plus 11...