5.3 BHB10 Malfunction Table
5.3.1 Common Failures: Causes & Solutions
Malfunction
Digital
Display
Detector
Display
Cause
Solution
System 1 exhaust
temp. failure
81
P181
The sensor is open or short circuit
Check or change the sensor
System 2 exhaust
temp. failure
81
P281
The sensor is open or short circuit
Check or change the sensor
Ambient temp. sensor
failure
4
P04
The sensor is open or short circuit
Check or change the sensor
System 1 anti-freeze
temp. failure
9
E171
The sensor is open or short circuit
Check or change the sensor
System 2 anti-freeze
temp. failure
9
E271
The sensor is open or short circuit
Check or change the sensor
System 1 economizer
inlet temp. failure
01
P101
The sensor is open or short circuit
Check or change the sensor
System 2 economizer
inlet temp. failure
01
P201
The sensor is open or short circuit
Check or change the sensor
System 1 economizer
outlet temp. failure
02
P102
The sensor is open or short circuit
Check or change the sensor
System 2 economizer
outlet temp. failure
02
P202
The sensor is open or short circuit
Check or change the sensor
System 1 anti-freeze
protection
71
P19
Water flow volume is not enough
Check the flow volume, water system
is jammed or not
System 2 anti-freeze
protection
71
P29
Water flow volume is not enough
Check the flow volume, water system
is jammed or not
Communication
Failure
\
E08
Communication failure between
remote wire controller and main
board
Check the wire connection between
remote wire controller and main board
System 1 current
protection
51
E151
Current through compressor too
heavy
Check through the power supply for
compressor or short circuit
System 2 current
protection
51
E251
Current through compressor too
heavy
Check through the power supply for
compressor or short circuit
System 1 exhaust high
temp. protection
82
P182
Compressor exhaust temp. too
high
Check through the refrigerant system
System 2 exhaust high
temp. protection
82
P282
Compressor exhaust temp. too
high
Check through the refrigerant system
Содержание EVO MAX 64
Страница 1: ...P a g e 1 ...
Страница 5: ...P a g e 5 2 2Unit Dimensions Evo Max 64 ...
Страница 6: ...P a g e 6 2 3Performance Curve COP Performance Curve R134a ...
Страница 8: ...P a g e 8 ...
Страница 9: ...P a g e 9 ...
Страница 15: ...P a g e 15 4 2 3 Stop Unit 4 2 4 Check the Data ...
Страница 16: ...P a g e 16 4 2 5 Check the Setting Data and Amend the Settings ...
Страница 17: ...P a g e 17 ...
Страница 19: ...P a g e 19 4 4Compensate Temperature Chart ...