5.2 Fan Speed Control
•
Cooling with Speed Control
•
Heating with Speed Control
•
•
With fan speed control modular MCHRTF04C0, the fan motor control curve is as the chart above,
and the related parameters are set as the following (R134a design).
Display Indicator
Parameter and Description
U.O.M
Def.
/07
0= not present
1= NTC Cond. Probe
2= NTC Out. Probe
3= Differential Control Probe
Int
0
D03
Start Defrosting Temperature
°C
-2
D04
End Defrost Pressure
°C
13
F02
Fan Operating Mode
0= Always ON
1=
2=
3=
Int
2
F05
Speed temp. set point in Cooling Mode
°C
18
F06
Differential value for max. speed Cooling
°C
5
F08
Speed temp. set point in Heating mode
°C
45
F09
Max. speed diff. in Heating mode
°C
5
F13
Fan management in Defrost mode
0= Fans deactivated
1= Fans in chiller mode
2= Maximum speed after defrost
Int
2