6. Troubleshooting 

6.1 Failure Codes of the Controller – Evo Control 17 

Malfunction 

Display 

Indicator 

Reason 

Resolution 

Power on 

 

Off 

 

 

Normal working 

 

On 

 

 

Inlet temp. sensor failure 

P01 

1 on 1 off 

The temp. sensor is broken or 

short circuit 

Check or change the temp. sensor 

Outlet temp. sensor failure 

P02 

2 on 1 off 

The temp. sensor is broken or 

short circuit 

Check or change the temp. sensor 

Recovery temp. sensor failure 

P033 

3 on 1 off 

The temp. sensor is broken or 

short circuit 

Check or change the temp. sensor 

Ambient temp. sensor failure 

P04 

4 on 1 off 

The temp. sensor is broken or 

short circuit 

Check or change the temp. sensor 

Coil 1 temp. sensor failure 

P15 

5 on 1 off 

The temp. sensor is broken or 

short circuit 

Check or change the temp. sensor 

Coil 2 temp. sensor failure 

P25 

5 on 1 off 

The temp. sensor is broken or 

short circuit 

Check or change the temp. sensor 

Suction 1 temp. sensor failure 

P17 

7 on 1 off 

The temp. sensor is broken or 

short circuit 

Check or change the temp. sensor 

Suction 1 temp. sensor failure 

P27 

7 on 1 off 

The temp. sensor is broken or 

short circuit 

Check or change the temp. sensor 

Discharge 1 temp. sensor 

failure 

P181 

8 on 1 off 

The temp. sensor is broken or 

short circuit 

Check or change the temp. sensor 

Discharge 2 temp. sensor 

failure 

P281 

8 on 1 off 

The temp. sensor is broken or 

short circuit 

Check or change the temp. sensor 

Antifreezing 1 temp. sensor 

failure 

P19 

9 on 1 off 

The temp. sensor is broken or 

short circuit 

Check or change the temp. sensor 

Antifreezing 2 temp. sensor 

failure 

P29 

9 on 1 off 

The temp. sensor is broken or 

short circuit 

Check or change the temp. sensor 

High pressure 1 protection 

E11 

11 on 1 off 

The high-pressure switch is 

broken 

Check the pressure switch and cold circuit 

High pressure 2 protection 

E21 

11 on 1 off 

The high-pressure switch is 

broken 

Check the pressure switch and cold circuit 

Low pressure 1 protection 

E12 

12 on 1 off 

The low-pressure switch is 

broken 

Check the pressure switch and cold circuit 

Low pressure 2 protection 

E22 

12 on 1 off 

The low-pressure switch is 

broken 

Check the pressure switch and cold circuit 

Heat source side water flow 

failure 

E031 

13 on 1 off 

Little or no water in water 

system 

Check the pipe water flow and water 

pump 

The use side water flow failure 

E032 

13 on 1 off 

Little or no water in water 

system 

Check the pipe water flow and water 

pump 

Water flow over-low failure 

E035 

13 on 1 off 

Little or no water in water 

system 

Check the pipe water flow and water 

pump 

Electrical-heat over heat failure  E04 

14 on 1 off 

Electrical-heat is over heat 

Check or change electrical-heat 

Compressor 1 overload failure 

E101 

21 on 1 off 

The compressor is overload 

Check the compressor functionality 

Compressor 2 overload failure 

E201 

21 on 1 off 

The compressor is overload 

Check the compressor functionality 

Water inlet and outlet temp. 

difference 

E06 

16 on 1 off 

Not enough water flow and low 

differential pressure 

Check the pipe water flow and if water 

system is jammed 

The system 1 use side 

antifreezing protection 

E171 

17 on 1 off 

Not enough water flow 

Check the pipe water flow and if water 

system is jammed 

The system 2 use side 

antifreezing protection 

E271 

17 on 1 off 

Not enough water flow 

Check the pipe water flow and if water 

system is jammed 

The system 1 heat source side 

antifreezing protection 

E172 

17 on 1 off 

Not enough water flow 

Check the pipe water flow and if water 

system is jammed 

The system 2 heat source side 

antifreezing protection 

E272 

17 on 1 off 

Not enough water flow 

Check the pipe water flow and if water 

system is jammed 

The primary anti freezing 

protection 

E19 

19 on 1 off 

The ambient temp. is low 

 

The secondary antifreezing 

protection 

E29 

19 on 1 off 

The ambient temp. is low 

 

Discharge Temp. of system 1 is 

too high 

P182 

8 on 1 off 

The compressor is overload 

Check the compressor functionality 

Discharge Temp. of system 2 is 

too high 

P282 

8 on 1 off 

The compressor is overload 

Check the compressor functionality 

System protection 

E05 

8 on 1 off 

The protection system is failing  Check each protection point of the system 

Defrosting 

 

Flashing 

 

 

Содержание Evo Control 17

Страница 1: ......

Страница 2: ...HELP Button __________________________________________________________________9 5 2 2 Starting Shutting Down ________________________________________________________________9 5 2 3 Switching Modes____...

Страница 3: ...with these recommendations will invalidate the warranty This manual and all others are available for download on our website The Evo Control Series air to water heat pump is designed for multiple use...

Страница 4: ...3 Evo Control 17 25 Manual 2 2 Dimensions Evo Control 17 Evo Control 25...

Страница 5: ...Quantity 2 Fan Power Input W 120x2 200x2 Fan Rotate Speed RPM 850 750 Noise dB A 56 59 Hot water volume L h 57 Water Pump Input kW 0 2 0 75 Water Head m 13 5 24 Water Connection Inch 1 1 5 Water Flow...

Страница 6: ...off before any work is started on the unit Do not work on the electrical components if water or high humidity is present on site When the unit is being connected ensure that no impurities are introduc...

Страница 7: ...6 Evo Control 17 25 Manual 4 Installation 4 1 Application for Air Con 4 2 Application for Air Con and Super Heater for Hot Water...

Страница 8: ...leakage test must be carried out to ensure that there is no water leaking before the installation can be made The pipe must be tested by pressure separately DO NOT test it together with the unit There...

Страница 9: ...nts and that they are in good order When powering the unit on review the indicator on the controller to see if there is any indication of failure The gas gauge can be connected to the check valve to s...

Страница 10: ...clock or turn the timer on off UP Press this key to select the upwards option or increase the parameter value DOWN Press this key to select the downwards option or decrease the parameter value 5 2 Fun...

Страница 11: ...re At the main interface press the UP or DOWN key to adjust the temperature setting as desired Once complete press the button to save the settings and exit Press the ON OFF button to exit without savi...

Страница 12: ...ss to enter the timer setting interface The process is much the same as adjusting the Clock settings To cancel and return to the previous menu press the ON OFF button 5 2 7 1 Timer Each timer has an O...

Страница 13: ...ere 8am 10am Timer 3 were 1pm 5pm the unit would operate or stop accordingly 5 2 8 Keyboard Lock To lock the controller after adjusting settings at the main interface hold the ON OFF button for 5 seco...

Страница 14: ...oken Check the pressure switch and cold circuit Low pressure 2 protection E22 12 on 1 off The low pressure switch is broken Check the pressure switch and cold circuit Heat source side water flow failu...

Страница 15: ...the temp sensor System 1 2 3 4 high Pressure protection E11 system1 E21 system2 E31 system3 E41 system4 The high pressure switch is broken Check the pressure switch and cold circuit System 1 2 3 4 lo...

Страница 16: ...recharge freon Block on filter or capillary Replace filter or capillary Lack of water flow Clean the water filter and discharge the air in water loop Compressor does not run Power supply failure Chec...

Страница 17: ...illed water Installation Requests 1 The Factory only offers main unit in the legend the other modules which are indispensable fittings are to be provided by the user or installation company 2 The unit...

Страница 18: ...ndle A can return close when the system is full of water 5 Automatic filled water valve needs cleaning in a periodic time and then you must close the tap unscrew the plug D and remove the inside filte...

Страница 19: ...o the electronic boiler or warm net pipe for city accordingly 1 Water chiller and heat pump assistant gas fired boiler 2 Water chiller and heat pump assistant electronic boiler 7 5 Unit Parameters Mea...

Страница 20: ...e input 10 RO 08 Spray valve output 220VAC 31 AI 05 Ambient temperature input 11 RO 09 Alarm system output 220VAC 32 AI 06 System 1 antifreeze temperature input 12 DI DO 1 Mode indicator output 33 AI...

Страница 21: ...put 12 RO 10 Spray valve output 220VAC 38 AI 11 System 4 antifreeze temperature input 13 RO 11 Alarm system output 220VAC 39 AI 12 System 1 suction temperature input 14 DI DO 1 Emergency switch output...

Страница 22: ...23 148A 2 x 50mm2 50mm2 225A 148 186A 2 x 70mm2 70mm2 250A 186 224A 2 x 95mm2 95mm2 280A Three Phase Unit Nameplate maximum current Phase Line Earth Line MCB Creepage Protector Signal Line No more tha...

Страница 23: ...it is restarted Please drain out the water in the super heater of the heat pump unit in winter when the super heater is not used The water loop of the heat pump MUST be protected from freezing in wint...

Страница 24: ...or damage to the product in transit 4 If warranty service is required you should a contact Evo Industries Australia on 1300 859 933 or via our Contact page on our web site b provide a copy of your re...

Отзывы: