Страница 2: ...HELP Button __________________________________________________________________9 5 2 2 Starting Shutting Down ________________________________________________________________9 5 2 3 Switching Modes____...
Страница 3: ...with these recommendations will invalidate the warranty This manual and all others are available for download on our website The Evo Control Series air to water heat pump is designed for multiple use...
Страница 4: ...3 Evo Control 17 25 Manual 2 2 Dimensions Evo Control 17 Evo Control 25...
Страница 5: ...Quantity 2 Fan Power Input W 120x2 200x2 Fan Rotate Speed RPM 850 750 Noise dB A 56 59 Hot water volume L h 57 Water Pump Input kW 0 2 0 75 Water Head m 13 5 24 Water Connection Inch 1 1 5 Water Flow...
Страница 6: ...off before any work is started on the unit Do not work on the electrical components if water or high humidity is present on site When the unit is being connected ensure that no impurities are introduc...
Страница 7: ...6 Evo Control 17 25 Manual 4 Installation 4 1 Application for Air Con 4 2 Application for Air Con and Super Heater for Hot Water...
Страница 8: ...leakage test must be carried out to ensure that there is no water leaking before the installation can be made The pipe must be tested by pressure separately DO NOT test it together with the unit There...
Страница 9: ...nts and that they are in good order When powering the unit on review the indicator on the controller to see if there is any indication of failure The gas gauge can be connected to the check valve to s...
Страница 10: ...clock or turn the timer on off UP Press this key to select the upwards option or increase the parameter value DOWN Press this key to select the downwards option or decrease the parameter value 5 2 Fun...
Страница 11: ...re At the main interface press the UP or DOWN key to adjust the temperature setting as desired Once complete press the button to save the settings and exit Press the ON OFF button to exit without savi...
Страница 12: ...ss to enter the timer setting interface The process is much the same as adjusting the Clock settings To cancel and return to the previous menu press the ON OFF button 5 2 7 1 Timer Each timer has an O...
Страница 13: ...ere 8am 10am Timer 3 were 1pm 5pm the unit would operate or stop accordingly 5 2 8 Keyboard Lock To lock the controller after adjusting settings at the main interface hold the ON OFF button for 5 seco...
Страница 14: ...oken Check the pressure switch and cold circuit Low pressure 2 protection E22 12 on 1 off The low pressure switch is broken Check the pressure switch and cold circuit Heat source side water flow failu...
Страница 15: ...the temp sensor System 1 2 3 4 high Pressure protection E11 system1 E21 system2 E31 system3 E41 system4 The high pressure switch is broken Check the pressure switch and cold circuit System 1 2 3 4 lo...
Страница 16: ...recharge freon Block on filter or capillary Replace filter or capillary Lack of water flow Clean the water filter and discharge the air in water loop Compressor does not run Power supply failure Chec...
Страница 17: ...illed water Installation Requests 1 The Factory only offers main unit in the legend the other modules which are indispensable fittings are to be provided by the user or installation company 2 The unit...
Страница 18: ...ndle A can return close when the system is full of water 5 Automatic filled water valve needs cleaning in a periodic time and then you must close the tap unscrew the plug D and remove the inside filte...
Страница 19: ...o the electronic boiler or warm net pipe for city accordingly 1 Water chiller and heat pump assistant gas fired boiler 2 Water chiller and heat pump assistant electronic boiler 7 5 Unit Parameters Mea...
Страница 20: ...e input 10 RO 08 Spray valve output 220VAC 31 AI 05 Ambient temperature input 11 RO 09 Alarm system output 220VAC 32 AI 06 System 1 antifreeze temperature input 12 DI DO 1 Mode indicator output 33 AI...
Страница 21: ...put 12 RO 10 Spray valve output 220VAC 38 AI 11 System 4 antifreeze temperature input 13 RO 11 Alarm system output 220VAC 39 AI 12 System 1 suction temperature input 14 DI DO 1 Emergency switch output...
Страница 22: ...23 148A 2 x 50mm2 50mm2 225A 148 186A 2 x 70mm2 70mm2 250A 186 224A 2 x 95mm2 95mm2 280A Three Phase Unit Nameplate maximum current Phase Line Earth Line MCB Creepage Protector Signal Line No more tha...
Страница 23: ...it is restarted Please drain out the water in the super heater of the heat pump unit in winter when the super heater is not used The water loop of the heat pump MUST be protected from freezing in wint...
Страница 24: ...or damage to the product in transit 4 If warranty service is required you should a contact Evo Industries Australia on 1300 859 933 or via our Contact page on our web site b provide a copy of your re...