![evoheat EVO COMMAND 140 Скачать руководство пользователя страница 38](http://html1.mh-extra.com/html/evoheat/evo-command-140/evo-command-140_manual_2446565038.webp)
3
6
6.Appendix
6.2Cables specification
(1) Single phase unit
(2) Three phase unit
Nameplate
max. current
Phase line
Earth line
MCB
Creepage protector
Signal line
10A
10~16A
16~25A
25~32A
32~40A
40~63A
63~75A
75~101A
101~123A
123~148A
148~186A
186~224A
2 1.5mm
2
2 2.5mm
2
2 4mm
2
2 6mm
2
2 10mm
2
2 16mm
2
2 25mm
2
2 25mm
2
2 35mm
2
2 50mm
2
2 70mm
2
2 95mm
2
1.5mm
2
2.5mm
2
4mm
2
6mm
2
10mm
2
16mm
2
25mm
2
25mm
2
35mm
2
50mm
2
70mm
2
95mm
2
20A
32A
40A
40A
63A
80A
100A
125A
160A
225A
250A
280A
30mA less than 0.1 sec
n 0.5mm
2
Nameplate
max. current
Phase line
Earth line
MCB
Creepage protector
Signal line
10A
10~16A
16~25A
25~32A
32~40A
40~63A
63~75A
75~101A
101~123A
123~148A
148~186A
186~224A
3 1.5mm
2
3 2.5mm
2
3 4mm
2
3 6mm
2
3 10mm
2
3 16mm
2
3 25mm
2
3 25mm
2
3 35mm
2
3 50mm
2
3 70mm
2
3 95mm
2
1.5mm
2
2.5mm
2
4mm
2
6mm
2
10mm
2
16mm
2
25mm
2
25mm
2
35mm
2
50mm
2
70mm
2
95mm
2
20A
32A
40A
40A
63A
80A
100A
125A
160A
225A
250A
280A
30mA less than 0.1 sec
n 0.5mm
2
When the unit will be installed at outdoor, please use the cable which can against UV.