background image

 

 

Содержание COMMAND-i

Страница 1: ......

Страница 2: ...ater Circuit Diagram 6 4 6 Heating Cooling Water Circuit Diagram 6 4 7 Electrical Connection 6 4 8 Cable Switch 7 4 9 Initial Start Up 7 5 Operation 8 5 1 The Controller 8 5 2 Operating Functions 8 5...

Страница 3: ...ing hotels resort commercial buildings sporting and leisure facilities industrial liquid heating and chilling applications TECHNICAL DATA Command i 40 Command i 90 Command i 210 Hot Water Capacity kW...

Страница 4: ...Series Manual Page 3 2 Dimensions Command i A L B W C H D E F G H 40 1195 980 1900 925 598 517 516 360 Command i A L B W C H D E F G H 90 2170 1150 2130 1590 1098 614 575 164 Command i A L B W C H D E...

Страница 5: ...t cleaning or maintenance switch off and disconnect the power of the unit Do not spray insecticides or flammable sprays around the unit it may cause a fire or damage the unit s cabinet Do not install...

Страница 6: ...tion and other fire hazards A pall is needed in winter to protect the unit from snow There must be no obstacles near the inlet and outlet of the unit The installation location must be protected from s...

Страница 7: ...eter and pressure meter at the water inlet and outlet for easy inspection during running 4 5 Hot Water Circuit Diagram 4 6 Heating Cooling Water Circuit Diagram Flexible Pipe Gate Valve Check Valve Le...

Страница 8: ...age is normal the screws are fastened the wiring is made in line with the diagram and that the earthing is connected Check that the heat pump includes all the screws and components and that they are i...

Страница 9: ...simply press the Power button to turn the unit on or off 5 2 2 Mode Selection From the main menu pressing the Mode button will allow you to select either heating or cooling mode The status bar bottom...

Страница 10: ...e opening time of the unit for each day of the week Press 26 to select the day of the week then 27 to select AM or PM after this press 28 to select the time and finally select 29 to enable or turn off...

Страница 11: ...ter interface for inquiring about relevant parameters 5 2 6 3 Failure When a failure is present the red failure alarm will be flashing on the main menu First press Settings then Failure to view the fa...

Страница 12: ...the unit is next powered on the wire controller will automatically clear the history curve record and the curve recording function will restore to a normal state 5 2 6 6 Electric Heating In the settin...

Страница 13: ...5 Excessively high water outlet temperature Fan 1 Thermal Overload Prot E103 Fan 1 thermal overload Check if fan 1 is running normally Fan 2 Thermal Overload Prot E203 Fan 2 thermal overload Check if...

Страница 14: ...replace the system 1 EVI inlet temperature sensor Syst1 EVI Out Temp Sensor Fault P102 The temperature sensor is open or short circuited Check and replace the system 1 EVI outlet temperature sensor Sy...

Страница 15: ...F101 System 1 fan failed to start Check if the system 1 fan line is normal Fan 1 Zero Speed Prot F102 System 1 fan failed to start Check if the system 1 fan rotor is locked Fan 1 Start IPM Prot F103 S...

Страница 16: ...info evoheat com au 1300 859 933 www evoheat com au Command i Series Manual Page 15 7 Appendix 7 1 Wiring Diagram...

Страница 17: ...No use 78 CN4 System 2 electronic expansion valve small 25 AI DI25 No use 79 CN5 System 1 EVI electronic expansion valve 26 AI DI26 No use 80 CN6 System 2 EVI electronic expansion valve 27 AI DI27 No...

Страница 18: ...2 1 5mm2 20A 30mA less than 0 1 sec n x 0 5mm2 10 16A 2 x 2 5mm2 3 x 2 5mm2 2 5mm2 32A 16 25A 2 x 4mm2 3 x 4mm2 4mm2 40A 25 32A 2 x 6mm2 3 x 6mm2 6mm2 40A 32 40A 2 x 10mm2 3 x 10mm2 10mm2 63A 40 63A 2...

Страница 19: ...unit should be dry clean and well ventilated Make sure there is nothing blocking the airflow of the heater e g Leaf litter Clean the heat exchanger every few months to keep a good heat exchange rate a...

Страница 20: ...ained within the i Costs associated with delivery handling freighting or damage to the product in transit 4 If warranty service is required you should a contact Evo Industries Australia on 1300 859 93...

Отзывы: