36
INSTALLATION
evo HE C -
Installation and Servicing
43 INITIAL LIGHTING
1.
Check that the system has been filled and that the boiler is
not airlocked. Ensure the automatic air vent cap (N) is open.
Note.
It is important the burner is not operated before the system is
fully vented of air. If it is necessary to operate the appliance
pump to assist venting of the air this must be done with the
gas service cock turned off.
2.
Refit the boiler sealing panel. Refer to Frame 50.
3.
Check that the drain cock is closed and that the CH and DHW
isolating valves (T, W and S) are OPEN.
4.
Check that the electrical supply is OFF.
5.
Check that the boiler on/off switch (A) is off.
6.
Check that the gas service cock (H) is OPEN.
7.
Slacken the screw in the inlet pressure test point (G) and
connect a gas pressure gauge via a flexible tube.
8.
Switch the electricity supply ON and check all external controls
are calling for heat.
CENTRAL HEATING
9.
Set the boiler thermostat knob (B) to position 6 and switch
the boiler on/off switch (A) to ON. The boiler control should
now go through its ignition sequence until the burner is
established.
10.
If the boiler does not light after 3 attempts the fault code
will be displayed, Press the reset button (E) and the boiler
will repeat its ignition sequence.
When the burner is established the WHITE 'Burner On' neon
(D) will be illuminated, the LED display will show status
LEGEND
A.
Boiler On/Off switch.
B.
CH thermostat knob.
D.
Burner On neon.
E.
Reset button.
F.
Injector pressure test
point.
G.
Inlet pressure test point.
H.
Gas service cock.
J.
Casing pressure test point.
K.
Overheat thermostat.
M.
Control thermistor (flow).
N.
Automatic air vent.
R.
Pressure gauge.
S.
CH Flow isolating valve.
T.
CH Return isolating valve.
U.
DHW outlet.
W.
DHW inlet
Y.
DHW thermostat knob.
Z.
Spark generator.
THE DISPLAY
The user control has one neon and one display to inform the
user about the status. The display will show the status of the
boiler. The neon will show the status of the flame. If no flame
is detected the neon is blinking. When the flame is detected
the neon will be lit permanently.
Below is a list with display function in normal operation.
Standby, no demand for heat present.
Boiler is active for central heating.
Boiler is active for domestic hot water.
Boiler is heating up the plate heat exchanger.
Note:
Boiler frost protection is activated as follows:
1
Pump runs if temperature is below 5 degrees C
2
Boiler fires if temperature is below 3 degrees C
Boiler is in lockout for a specific error. Display will be
blinking, alternating with a number or letter to show which
error is detected.
Boiler is in lockout for a specific error. Display will be
blinking, alternating with a number or letter to show
which error is detected.
Control Box Servicing Position. See Frame 51.
INST
ALLA
TION