ModuSat® Wiring Connections
The ModuSat® wiring board is located within the ModuSat® itself behind the metal cover
To access the connection board, take off the cover. The retaining screw should be removed and the
cover lifted off. The connection board also has two screws which will need to be removed and the
board can be pulled out from its position. The board is now accessible and all required connections
can be made simply using the clearly labelled screw down terminal connections. Guides for the
various connection applications and requirements are detailed in the wiring principle drawings
shown on pages 24-26.
The Control Board
The control board is located behind the connection board. The control board cover must
not be removed. Doing so may invalidate the warranty.
Connection Terminations
Evinox Energy strongly recommend in accordance with best practice that all wiring
connections to the board, especially the BUS and room controller are terminated using
‘bootlace ferrule’ connectors. These connectors ensure a good connection and that the
whole cross sectional area of the wiring is intact.
5.2.1
RJ45 Connections
If the TCP/IP network is used, instead of the BUS termination the RJ45 can be connected to the
control board. The RJ connection can be found at the side of the control board as shown below with
the red arrow.
Cable glands are fitted at the bottom of the ModuSat® case as shown in below: