48 

 

6.5  Pump Start-up - Wilo PWM Pump 

The Wilo Pulse-width modulation (PWM) pump features dry running protection to eliminate 

burn out and provides compliance with the 2015 pump efficiency regulations. 

 

Description of the pump 

The pump consists of a hydraulic system, a 

glandless pump motor with a permanent 

magnet rotor, and an electronic control 

module with an integrated frequency 

converter. The control module provides speed 

control by a PWM signal from the ModuSat 

control board and indicator LED to display the 

pump operating status. 

 

Please note:

 When the unit is switched over 

to heating mode the pump will run for 2 mins 

prior to the heating PICV opening , this is not 

a fault in the unit but a normal control function 

as the HIU asses the current heating circuit 

flow temperature. 

 

Pump LED – Description of Status 

LED 

Indicators 

Diagnosis 

Status 

Remedy 

Lights green 

Pump in operation  Pump runs 

according 

its setting 

Normal operation 

 

Blinks quick 

green 

PWM model: 

Pump in standby 

Normal operation 

 

Blinks red/ 

green 

 

Pump in function 

but stopped 

Pump restarts by 

itself after the fault 

is disappeared 

1. Low voltage 

U<160 V 

or 

High voltage 

U>253 V 

1. Check voltage 

supply 

195 V < U < 253 V 

 

 

 

2. Module overheating: 

temperature 

inside motor too 

high 

2. Check water and 

ambient 

temperature 

Blinks red 

Pump out of 

function 

Pump stopped 

(blocked) 

Pump does not 

restart by itself due 

to a permanent failure 

Change pump 

LED off 

No power 

No power to pump 

1. Pump is not connected 

to power supply 

1. Check cable 

connection 

 

 

 

2. LED is damaged 

2. Check if pump is 

running 

 

 

 

3. Electronics are 

damaged 

Change pump 

 

 

 

Содержание ModuSat FS 150

Страница 1: ...1 ModuSat FS Unit Installation Manual...

Страница 2: ...sure Independent Control Valves PICV 28 4 PRIMARY AND SECONDARY CIRCUIT 29 4 1 Water treatment 29 4 2 Cleaning 29 4 3 Precautions 30 4 4 Bionibal 31 4 5 Initial opening filling of the unit 32 4 6 Flus...

Страница 3: ...3 6 2 Apartment Circuit Balancing 45 6 3 Use of the commissioning switch 46 6 4 Adjustment of TMV 47 6 5 Pump Start up Wilo PWM Pump 48 6 6 Warranty 49...

Страница 4: ...y thermostat intervention 85 C PT relief valve 7 0 bar 90 C Expansion relief valve setting 6 0 bar Primary heating power 12 kW Primary flow rate Nom 720 l h Storage capacity 80 l Standing heat loss 1...

Страница 5: ...ty thermostat intervention 85 C PT relief valve 7 0 bar 90 C Expansion relief valve setting 6 0 bar Primary heating power 15 kW Primary flow rate Nom 720 l h Storage capacity 150 l Standing heat loss...

Страница 6: ...ty thermostat intervention 85 C PT relief valve 7 0 bar 90 C Expansion relief valve setting 6 0 bar Primary heating power 20 kW Primary flow rate Nom 800 l h Storage capacity 200 l Standing heat loss...

Страница 7: ...ety thermostat intervention 65 C PT relief valve 7 0 bar 90 C Expansion relief valve setting 6 0 bar Primary heating power 29 6 kW Primary flow rate Nom 1300 l h Storage capacity 300 l Standing heat l...

Страница 8: ...y thermostat intervention 65 C PT relief valve 7 0 bar 90 C Expansion relief valve setting 6 0 bar Primary heating power 29 6 kW Primary flow rate Nom 1500 l h Storage capacity 400 l Standing heat los...

Страница 9: ...alidate the warranty and absolves Evinox from any liability Evinox has the right to make any changes or modifications to the products without prior notice 1 2 Symbols Follows a list of symbols used in...

Страница 10: ...10 ModuSat FS 80 ModuSat FS 150 ModuSat FS 200 ModuSat FS 400 ModuSat FS 300 Please note Images shown include the optional factory fitted immersion heater Tank Without immersion heater fitted...

Страница 11: ...External lime scale reducer Optional 6 Blending valve Heating Secondary Side Circuit 7 Heating expansion vessel 8 Pressure sensor 9 Safety relief discharge 10 P T Safety relief discharge 11 Manometer...

Страница 12: ...e scale reducer Optional 6 Blending valve Heating Secondary Side Circuit 7 Heating expansion vessel 8 Pressure sensor 9 Safety relief discharge 10 P T Safety relief discharge 11 Manometer 12 Circulati...

Страница 13: ...ime scale reducer Optional 6 Blending valve Heating Secondary Side Circuit 7 Heating expansion vessel 8 Pressure sensor 9 Safety relief discharge 10 P T Safety relief discharge 11 Manometer 12 Circula...

Страница 14: ...14 2 2 Dimensions ModuSat FS 80 150...

Страница 15: ...15 ModuSat FS 200...

Страница 16: ...16 ModuSat FS 300 400...

Страница 17: ...xt thread Hydraulic characteristics ModuSat FS 80 ModuSat FS 150 Max primary temperature 80 C Max primary pressure 10 bar Optional 16 bar Recommended max apartment circuit cold fill pressure 1 5 bar M...

Страница 18: ...ead DCW inlet ext thread Hydraulic characteristics ModuSat FS 200 Max primary temperature 80 C Max primary pressure 10 bar Optional 16 bar Recommended max apartment circuit cold fill pressure 1 5 bar...

Страница 19: ...Max primary pressure 10 bar Optional 16 bar Recommended max apartment circuit cold fill pressure 1 5 bar Max water supply pressure 12 bar Pressure reducing valve fixed outlet pressure 3 bar Max DHW s...

Страница 20: ...ger power Nom Max kW 12 24 15 32 20 42 30 54 40 65 Continuous DHW flow rate at 45 C l m 5 10 6 13 8 17 12 22 16 26 Pre heat time from 15 C to 60 C Minutes 21 10 31 15 31 15 31 17 31 19 Re heat time to...

Страница 21: ...position still within its packaging and on its pallet to prevent any damage whilst being positioned Once correctly sited the unit should be lifted from pallet and into final position ModuSat 300 400...

Страница 22: ...id upper body bending when holding the appliance and keep the ModuSat FS as close to the body as possible Safety footwear and gloves are recommended PPE should be used when lifting this appliance to p...

Страница 23: ...unit requires a 220 240Volt AC 50Hz supply check the Line and Phase polarity Protect the cables to prevent any damage Make sure that there is an efficient reliable earth connection to protect against...

Страница 24: ...ll in the required position STEP2 Fit the Evinox Flushing Bypass Valve Kit to the rig and then make final connections to the pipework running to the HIU STEP3 Shut off isolation valves pressure test p...

Страница 25: ...e and connection details The relief valve connections should not be altered or used for any other type of connection The incoming cold water supply pipe must be fitted with a stopcock isolation valves...

Страница 26: ...is 9 0m Subtract the resistance for 4 no 22mm elbows at 0 8m each 3 2m Therefore the maximum permitted length equates to 5 8m 5 8m is less than the actual length of 7m therefore calculate the next la...

Страница 27: ...27 Optional Way to Discharge P T Valve...

Страница 28: ...300 400 PICV Valve Model DN20 2 5mm No Presetting DN20 5 5mm High Maximum flow rate 1450 l h 10 1800 l h 10 Start up P 25 kPa 40 kPa Max differential P 800 kPa 800 kPa Valve size DN20 DN20 Thread G1...

Страница 29: ...econdary circuits using suitable water treatment chemicals Typical water quality guidelines are as follows pH this measures the alkalinity of the water neutral alkalinity is pH7 Heating systems requir...

Страница 30: ...her residues may clog the heat meters within the ModuSat units causing errors in the energy consumption calculations WATER TREATMENT IS A STRICT REQUIREMENT AND MUST BE CHECKED IN THE FOLLOWING CASES...

Страница 31: ...in under floor heating working at low temperatures THIRD LEVEL prevents the adherence of suspended particles such as tartar keeping the surfaces clean pumps valves heat meters etc FOURTH LEVEL provide...

Страница 32: ...ure must be carried out by competent qualified installation personnel To fill the DHW tank proceed as follows Fully open incoming mains water supply to the ModuSat Vent tank via the hot water outlet t...

Страница 33: ...sition and bypass is open Turn screw in horizontal position for flushing of primary system Unit in normal operation Open to primary system Isolation valves are opened Handles in vertical position and...

Страница 34: ...spection access Prior to removing the immersion heater or boss please ensure the tank has been drained down fully as per 4 7 Tank draining above Take care not to damage the immersion heater when remov...

Страница 35: ...35...

Страница 36: ...arth wire and connect it to the relevant earth connection Important If immersion is used then this will require its own separate 2 pole switched fused connection with suitable fuse rating Extension co...

Страница 37: ...elf under a removable metal cover To access the wiring board the full front case cover Or front top cover if a 200 300 or 400 litre unit should be removed The connections board will be to your left as...

Страница 38: ...arious connection applications and requirements are detailed in the wiring principle drawings shown on pages 31 32 Evinox strongly recommend in accordance with best practice that all wiring connection...

Страница 39: ...onnection Board Visible once the cover is removed Please Note When connecting external valves or pumps to the control board of the ModuSat it must be ensured that each connection does not exceed 1amp...

Страница 40: ...n the ModuSat please refer to the electrical diagram using a 4x0 35 mm2 screened cable The cable must not be installed adjacent to other 220 240 Volt AC The ModuSat room controller s power is supplied...

Страница 41: ...41 Once the tab has been releasees the cover can be hinged up to access connection Connection terminal with room controller 4 x 0 35 sqmm sheild...

Страница 42: ...5 4 Typical ModuSat Electric Wiring Diagram Single Room Controller Note 3 Pumps valves must have localized power supply Switched neutral connection to be fitted with 1 amp in line fuse on neutral cab...

Страница 43: ...ical ModuSat Electric Wiring Diagram with 2 Zone Control 2 Room Controllers Note 3 Pumps valves must have localized power supply Switched neutral connection to be fitted with 1 amp in line fuse on neu...

Страница 44: ...the connection of any other components i e thermostats probe etc If the pressure is below 1 bar top up the circuit to a cold fill pressure of 1 5 bar as low pressure will stop the pump from running du...

Страница 45: ...irements and current standards and legislation remains the exclusive responsibility of the installer M E contractor and comments provided by Evinox are for guidance advice only Once the initial commis...

Страница 46: ...hen run at a pre set output temperature of 45 C thus providing a safe temperature for UFH circuits and also a gentle warm up of radiator circuits This function will run for a pre set period of approx...

Страница 47: ...ed within 15 seconds and the mixed water temp is approximately 55 C 2 C The default valve setting is 55 C if this needs adjustment this can be done by loosening the top screw and turning the dial to t...

Страница 48: ...ut a normal control function as the HIU asses the current heating circuit flow temperature Pump LED Description of Status LED Indicators Diagnosis Status Remedy Lights green Pump in operation Pump run...

Страница 49: ...ning date This guarantee is strictly limited to the supply free of charge of parts acknowledged as being defective after inspection by our technical departments with the exclusion of labour and transp...

Страница 50: ...he Guarantee The following are not covered by the guarantee a Electric indicators Electric degradation of parts resulting from connection and installation on electricity supply whose voltage measured...

Отзывы: