E2660-CO-NO2
Rev 06.04.2021
Sensor probe handling
The E2660 series devices are available with a remote probe. The remote probe is
connected to the main unit with a shielded cable. The default connection cable length is 3
m.
A)Wall mount remote probe with fixing clamp (default version),
B)Remote probe with rubber flange and three self-tapping screws (on request)
The sensor probes of all types are equipped with a hydrophobic microporous PTFE filter to
protect the sensor from dust, dirt, and water drops. The filter should be replaced if it gets
strongly contaminated. To replace the PTFE filter, unscrew the M25 nut and remove the old
filter. Place a new filter into the nut and tighten it again.
NOTE! Never stab or press the filter near its center where the sensor is located since this
may damage the sensor. Do not remove the filter as it may cause the device to show
incorrect values.
The recommended orientation of the sensor probe is vertical with the sensor tip pointing
downwards. This prevents the possible accumulation of condensed water on the sensor
protection filter.
Gas sensor replacement procedures
1.
Remove the sensor head cap from the device (or the remote probe),
2.
Remove the PTFE filter (if it is not removed within the cap),
3.
Remove the O-ring rubber,
4.
Detach the electrochemical sensor from the device,
5.
Insert the new electrochemical sensor inside,
6.
Put back the O-ring rubber, PTFE filter, and the head cap, respectively.
10