E2648-NH3-E
Rev 22.06.2021
Jumpers
J1
OUT1 type (open: 4-20 mA; closed 0-10 V)
J2
OUT2 type (open: 4-20 mA; closed 0-10 V)
X6
Reset Modbus network parameters to default
X4 terminals
OUT1
4-20 mA / 0-10 V output
OUT2
4-20 mA / 0-10 V output
0V
0 V / 24 VAC Neutral (optional)
A
RS485 A / Data +
B
RS485 B / Data -
+U
+24 VDC / 24 VAC Phase (optional)
X5 terminals (optional)
L
90…265 VAC Phase
N
90…265 VAC Neutral
RE1 NO
Relay 1, normally open terminal
RE1 COM
Relay 1, common terminal
RE2 NO
Relay 2, normally open terminal
RE2 COM
Relay 2, common terminal
The screwless quick connect spring terminals on the E2648 series devices are suitable for
a wide range of wires with a cross-section of 0.2...1.5 mm
2
. We recommend striping the
wire end by 8...9 mm and using wire end sleeves.
To connect the wire, insert the wire end into the terminal hole. To disconnect, push the
spring-loaded terminal lever, pull the wire out, and release the lever.
Use a twisted-pair cable, e.g. LiYY TP 2×2×0.5 mm
2
or CAT 5, to connect the device to the
RS485 network. A and B on the device represent DATA+ and DATA- respectively, polarity
must be respected when connecting to an external RS485 network.
Both analog outputs can be independently changed between 4-20 mA and 0-10 V type
using jumpers J1 (OUT1) and J2 (OUT2). By closing pins on a specific jumper the related
output is 0-10 V, with an open jumper the output is 4-20 mA. Power restart is required after
changing the position of the jumpers.
11