E2638 series Modbus holding registers (part 3)
Register addresses are shown 0-based, Addr in hexadecimal, Reg in decimal format.
Modbus holding register numbers MHR are shown in decimal 1-based format, and may be addressed either from 00001 or 40001 base.

Addr

Reg / MHR

RW

Description

Supported values (dec)

Default

0x00DB

219 / 40220 RW

Control logic for relay RE1

0 – none
1 – relay on at high values
2 – relay on at low values
3 – relay on at values within the range
4 – relay on for the values out of the range

0

0x00DC

220 / 40221 RW

Control logic for relay RE2

0 – none
1 – relay on at high values
2 – relay on at low values
3 – relay on at values within the range
4 – relay on for the values out of the range

0

0x00DD

221 / 40222 RW

LOW setpoint for relay RE1

0...65535 (gas units)

see

Specifications

0x00DE

222 / 40223 RW

HIGH setpoint for relay RE1

0...65535 (gas units)

see

Specifications

0x00DF

223 / 40224 RW

LOW setpoint for relay RE2

0...65535 (gas units)

see

Specifications

0x00E0

224 / 40225 RW

HIGH setpoint for relay RE2

0...65535 (gas units)

see

Specifications

0x00FF

255 / 40256 RW

Sensor, analog outputs, LED and buzzer
status

bit[0]=0/1 – sensor present/absent, read-only!
bit[1]=0/1 – analog outputs deactivated/activated,
bit[2]=0/1 – in case the sensor is absent, turn signaling off/on analog output1,
bit[3]=0/1 – in case the sensor is absent, turn on signaling with low current/high
current on analog output1; if bit[2]==0 this bit will be ignored,
bit[4]=0/1 – in case of sensor absent, turn signaling off/on analog output2
bit[5]=0/1 – in case of sensor absent, turn on signaling with low current/high current
on analog output2; if bit[4]==0 this bit will be ignored,
bit[6]=0/1 – current/voltage output detected on output1, read-only!
bit[7]=0/1 – current/voltage output detected on output2, read-only!
bit[8]=0/1 – LED deactivated/activated
bit[9]=0/1 – buzzer deactivated/activated
bit[10]=0/1 – LED is on/off in normal condition
bit[11]=0/1 - 1 Hz (50% on, 50% off) LED signal off/on if relay1 turned on
bit[12]=0/1 - 2 Hz (50% on, 50% off) LED signal off/on if relay2 turned on

user defined

0x0101

257 / 40258

R

Raw gas sensor data

0...4095, ADC units

0x0102

258 / 40259

R

Measured temperature, °C×100

signed integer, -4000...+12500 (-40,00...+125,00 °C)

0x0103

259 / 40260

R

Gas concentration, gas units

0...65535, gas units

0x0105

261 / 40262 RW

0% value for analog output 1

-32000...+32000 (gas unit/°C)

user defined

0x0106

262 / 40263 RW

100% value for analog output 1

-32000...+32000 (gas unit/°C)

user defined

0x0107

263 / 40264 RW

0% value for analog output 2

-32000...+32000 (gas unit/°C)

user defined

0x0108

264 / 40265 RW 100% value for analog output 2

-32000...+32000 (gas unit/°C)

user defined

* – The new value is applied after restart.
** – Broadcast slave ID 0 can be used to assign a new ID to device with unknown ID. When addressing by ID 0 the device shall be

the only Modbus instrument in the network. The device will not respond to Master command when addressed by ID 0.

*** – This value is dynamic and not kept in EEPROM after restart

NOTE 1

 Relay setpoints should be set within 5-95% of the detection

range.

NOTE 2 

Sensor absense signalling (bits from [2] to [5]) is available only

for sensors with digital interface ( e.g.-CO2 10K, -O2-L).
NOTE 3

 LED/buzzer signalization (if activated):

Detectable sensor
absence or malfunction

0.5Hz (90% off, 10% on) light and/or sound
signal

Relay1 turned on

1 Hz (50% on, 50% off) light and/or sound
signal, depending on bit[8], bit[9] and bit[11]

Relay2 turned on

2 Hz (50% on, 50% off) light and/or sound
signal, depending on bit[8], bit[9] and bit[12]

Modbus response

the light signal is modulated with short on-off
pulses, even single Modbus cycle is visible

Normal operating

continuously on/off depending on bit[10]

NOTE 4

 We recommend to set the difference between the upper and

bottom limits of the output scale not narrower than 20% of detection
range (for CO detectors the scales down to 5% of range are
allowed). In any case, do not set the output scale below the tenfold
resolution of the device.

Содержание PluraSens E2638-LEL

Страница 1: ...cal detection range 0 100 LEL 0 100 LEL Resolution digital unit 0 1 LEL 1 LEL Response time T90 ca 60 s 8 s Sensor lifetime 5 years 2 years Calibration interval 12 months 3 6 months Operating conditio...

Страница 2: ...s OUT1 and OUT2 are assigned to gas concentration The device has built in temperature sensor which may be tied to any of the outputs NOTE The built in temperature sensor is intended for temperature co...

Страница 3: ...NOTES E2638 version with relays E2638 version without relays DIMENSIONS CONNECTION DIAGRAMS E2638_UM_EN DRAWINGS AND DIAGRAMS Remote probe Enclosure...

Страница 4: ...may be addressed either from 00001 or 40001 base Addr Reg MHR RW Description Supported values dec Default 0x0001 1 40002 R Hardware version 0x0002 2 40003 R Software version 0x0003 3 40004 R Product s...

Страница 5: ...in MHR 40205 2 0x00CB 203 40204 RW Forced value for analog output 1 0 1000 0 0 100 0 of output scale 0 0x00CC 204 40205 RW Forced value for analog output 2 0 1000 0 0 100 0 of output scale 0 0x00D3 2...

Страница 6: ...is on off in normal condition bit 11 0 1 1 Hz 50 on 50 off LED signal off on if relay1 turned on bit 12 0 1 2 Hz 50 on 50 off LED signal off on if relay2 turned on user defined 0x0101 257 40258 R Raw...

Страница 7: ...o air 0 07 Conversion 1 ppm 0 0818 mg m3 Boiling point 252 88 C Low explosive limit LEL vol in air 4 0 Upper explosive limit UEL vol in air 75 Odour Odourless Hazards Flammable forms explosive mixture...

Отзывы: