E2638_UM_EN. Annex 1. E2638 series Modbus RTU Communication Reference

RS485 communication interface

Databits: 8
Parity: none / odd / even
Stop bits: 1 or 2
Protocol: Modbus RTU

Supported Modbus functions:
03 – read multiple registers 
06 – write single register

Communication parameters

Parameter

Permitted values

Default

Supported
baudrates

1200, 2400, 4800, 9600, 19200,
38400, 57600

9600

Data bits

8

8

Parity

none / odd / even

none

Stop bits

1, 2

1

Protocol

Modbus RTU

Modbus functions

03 – read multiple registers
06 – write single register

Error codes

01 – illegal function
02 – illegal data address
03 – illegal data value
04 –  slave device failure (details of last error 04
can be read from register 0x0008)

E2638 series Modbus holding registers
Register addresses are shown 0-based, Addr in hexadecimal, Reg in decimal format.
Modbus holding register numbers MHR are shown in decimal 1-based format, and may be addressed either from 00001 or 40001 base.

Addr

Reg / MHR

RW

Description

Supported values (dec)

Default

0x0001

1 / 40002

R

Hardware version

-

0x0002

2 / 40003

R

Software version

-

0x0003

3 / 40004

R

Product serial number

1...65535

-

0x0004

4 / 40005

RW

Slave ID (net address) *

1...247 **

1

0x0005

5 / 40006

RW

Baudrate *

1200, 2400, 4800, 9600, 19200, 38400, 57600

9600

0x0006

6 / 40007

RW

Response delay, ms

1...255

10

0x0007

7 / 40008

RW

Stop bits, parity bit *

1 – no parity bit, 1 stop bit (default after factory reset)
2 – no parity bit, 2 stop bits
3 – odd parity, 1 stop bit
4 – even parity, 1 stop bit
NOTE

: 3 and 4 are available starting from the Software version 0x218 (dec. 536)

1

0x0008

8 /40009

R

Last error code

1...255

-

0x0011

17 / 40018

RW

Restarts counter

write ‘42330’ to restart device

-

* – The new value is applied after restart.
** – Broadcast slave ID 0 can be used to assign a new ID to device with unknown ID. When addressing by ID 0 the device shall be

the only Modbus instrument in the network. The device will not respond to Master command when addressed by ID 0.

*** – This value is dynamic and not kept in EEPROM after restart

Содержание PluraSens E2638-LEL

Страница 1: ...cal detection range 0 100 LEL 0 100 LEL Resolution digital unit 0 1 LEL 1 LEL Response time T90 ca 60 s 8 s Sensor lifetime 5 years 2 years Calibration interval 12 months 3 6 months Operating conditio...

Страница 2: ...s OUT1 and OUT2 are assigned to gas concentration The device has built in temperature sensor which may be tied to any of the outputs NOTE The built in temperature sensor is intended for temperature co...

Страница 3: ...NOTES E2638 version with relays E2638 version without relays DIMENSIONS CONNECTION DIAGRAMS E2638_UM_EN DRAWINGS AND DIAGRAMS Remote probe Enclosure...

Страница 4: ...may be addressed either from 00001 or 40001 base Addr Reg MHR RW Description Supported values dec Default 0x0001 1 40002 R Hardware version 0x0002 2 40003 R Software version 0x0003 3 40004 R Product s...

Страница 5: ...in MHR 40205 2 0x00CB 203 40204 RW Forced value for analog output 1 0 1000 0 0 100 0 of output scale 0 0x00CC 204 40205 RW Forced value for analog output 2 0 1000 0 0 100 0 of output scale 0 0x00D3 2...

Страница 6: ...is on off in normal condition bit 11 0 1 1 Hz 50 on 50 off LED signal off on if relay1 turned on bit 12 0 1 2 Hz 50 on 50 off LED signal off on if relay2 turned on user defined 0x0101 257 40258 R Raw...

Страница 7: ...o air 0 07 Conversion 1 ppm 0 0818 mg m3 Boiling point 252 88 C Low explosive limit LEL vol in air 4 0 Upper explosive limit UEL vol in air 75 Odour Odourless Hazards Flammable forms explosive mixture...

Отзывы: