E2608-NH3-P

Rev 27.07.2022

Specifications

Sensor type

Pellistor (catalytic bead)

Sampling method

Diffusion

Typical detection
ranges

0...15%vol. (0…100%LEL NH

3

)

Resolution / digital unit

0.1%vol. or 1%LEL

Response time T90

≤10 s

Sensor lifetime

> 3 years

Calibration interval

6 months

Signal update

Every 1 second

Power supply

12...36 VDC (default),

24 VAC or 230 VAC as options

Power consumption

< 2 VA

Load resistance

R

L

< (Us - 2 V) / 22 mA for 4-20 mA

R

L

> 250 kOhm for 0-10 V mode

Digital interface

RS485, Modbus RTU protocol;

No galvanic isolation

Analog outputs

2 × 4-20 mA / 0-10 V, user settable

Outputs assignment

OUT1: Gas; OUT2: Gas

Output scale width

> 10 × resolution

Recommended: 20-100% of the detection range

Analog output scale can be set according to customer's requirement (e.g.

0…4%vol. NH

3

)

Relay outputs

2 × SPST, max 5 A, 30 VDC / 250 VAC

Cable connections

Screwless spring-loaded terminals

Enclosure

Grey ABS, wall mount, protection class IP65

Dimensions

H87 × W82 × D55 mm

CE marking

According to 2014/30/EU and 2014/35/EU, EN 50491-4-1:2012

EN 61000-6-3:2020, EN 61326-1:2013(EMC, emissions)

EN 61000-6-1:2019, EN 61000-6-2:2019(EMC, Immunity)

EN 60079-29-1:2016, EN 60079-29-2:2015 and EN 60079-29-3:2014

Operating conditions

-20…+60 °C, 95% RH non-condensing,

0,9...1,1 atm

4

Содержание PluraSens E2608-NH3-P

Страница 1: ...PluraSens Ammonia Detector Transmitter E2608 NH3 P User Manual...

Страница 2: ...Sensor probe handling 9 Gas sensor replacement procedures 9 Electrical connections 10 Correct and incorrect cabling for 24 VAC 12 Operation 13 Maintenance 13 Calibration 13 Delivery set 14 Order code...

Страница 3: ...emical formula NH3 Molar weight 17 Relative gas density to air 0 59 Conversion 1 ppm 0 70 mg m3 Boiling point 33 3 C Low explosive limit LEL vol in air 15 Upper explosive limit UEL vol in air 28 Odor...

Страница 4: ...olation Analog outputs 2 4 20 mA 0 10 V user settable Outputs assignment OUT1 Gas OUT2 Gas Output scale width 10 resolution Recommended 20 100 of the detection range Analog output scale can be set acc...

Страница 5: ...as Normal ambient oxygen level Avoid strong mechanical shock vibrations or EMI Avoid exposure to corrosive gases or silicone containing products Other options Remote probe Protection IP65 default cabl...

Страница 6: ...to the safety provisions applicable in the country of use Do not perform any maintenance operation with the power on Do not let water or foreign objects inside the device Removal of the PCB from the e...

Страница 7: ...ius For early leakage detection install the sensor as close as possible to the potential leakage sources flanges valves pressure reducers pumps etc taking into consideration other points listed above...

Страница 8: ...E2608 NH3 P Rev 27 07 2022 Mounting dimensions Wall mount version with mounting lugs Duct mount version 8...

Страница 9: ...or head cap and remove the old filter Place a new filter into the cap and tighten it again NOTE Never stab or press the filter near its center where the sensor is located since this may damage the sen...

Страница 10: ...connection diagram below connect the analog outputs and digital interface terminals to the relevant devices according to your tasks Version without PSU Version with PSU Jumpers J1 OUT1 type open 4 20...

Страница 11: ...A and B on the device represent DATA and DATA respectively polarity must be respected when connecting to an external RS485 network Both analog outputs can be independently changed between 4 20 mA and...

Страница 12: ...E2608 NH3 P Rev 27 07 2022 Correct and incorrect cabling for 24 VAC 12...

Страница 13: ...rt on off pulses Normal operating measurement Continuously on or off Make sure that the detector transmitter is properly mounted the external devices connected power LED green on and the control LED r...

Страница 14: ...flange for Remote probe option Fixing clamp for Remote probe option Order code for E2608 NH3 P options E2608 options Order code Remote probe 3 m cable E2608 NH3 P RP33 3 Remote probe 10 m cable E2608...

Страница 15: ...parameter Flexible setting of analog output scales for each output Output zero and slope adjustment for calibration Free assignment of each of two relays to the chosen parameter Several relay control...

Страница 16: ...ple registers 06 Write a single register Error codes 01 Illegal function 02 Illegal data address 03 Illegal data value 04 Slave device failure details of last error 04 can be read from register 0x0008...

Страница 17: ...Description Supported values dec Default 0x00A5 165 40166 RW Zero adjustment for gas data ADC 32000 32000 ADC units 0 0x00A6 166 40167 RW Slope adjustment for gas data 1 65535 512 0x00A7 167 40168 RW...

Страница 18: ...RE1 0 1000 s 0 0x00D8 216 40217 RW Switching delay for relay RE2 0 1000 s 0 0x00D9 217 40218 RW Minimal on off time for relay RE1 0 1000 s 0 0x00DA 218 40219 RW Minimal on off time for relay RE2 0 10...

Страница 19: ...aling off on analog output1 bit 3 0 1 in case the sensor is absent turn on signaling with low current high current on analog output1 if bit 2 0 this bit will be ignored bit 4 0 1 in case of sensor abs...

Страница 20: ...x0107 263 40264 RW 0 value for analog output 2 32000 32000 gas units User defined 0x0108 264 40265 RW 100 value for analog output 2 32000 32000 gas units User defined The new value is applied after re...

Страница 21: ...Manufacturer will at its option either repair or replace a product that proves to be defective This warranty is void if the product has been operated in conditions outside ranges specified by the Man...

Отзывы: