background image

E2658-C2H4 

Rev 12.03.2021 

The screwless quick connect spring terminals on the E2658 series devices are suitable for

 

 

 

 

 

   

 

 

 

 

 

 

 

a wide range of wires with cross-section 0,5...1,5 mm​

2​

. We recommend to strip the wire

 

 

   

 

 

 

 

 

 

   

 

 

 

end by 8...9 mm and use the wire end sleeves. 

To connect the wire, insert the wire end into the terminal hole. To disconnect, push the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

spring-loaded terminal lever, pull the wire out, and release the lever.  

Use a twisted-pair cable, e.g. LiYY TP 2×2×0.5 mm​

2

or CAT 5, to connect the device to the

   

 

 

 

 

 

 

   

     

 

 

   

 

RS485 network. A and B on the device represent DATA+ and DATA- respectively, polarity

 

   

   

 

 

 

 

 

 

 

 

 

must be respected when connecting to an external RS485 network. 

Both analog outputs can be independently changed between 4-20 mA and 0-10 V type

 

 

 

 

 

 

 

 

 

 

 

   

 

using jumpers J1 (OUT1) and J2 (OUT2). By closing pins on a specific jumper the related

 

 

 

 

 

 

 

 

 

 

   

 

 

 

 

output is 0-10 V, with an open jumper the output is 4-20 mA. Power restart is required after

   

   

   

 

 

 

   

 

 

 

   

 

 

changing the position of the jumpers. 

NOTE! The outputs are not galvanically isolated from the external power supply and share

 

 

 

 

 

 

 

 

 

 

 

 

 

 

a common 0V. Allowed load resistance limits are stated in the Specifications table. To

 

 

 

 

 

 

 

 

   

 

 

 

 

power the instrument from an external power source, connect terminals 0V and +U to the

 

 

 

 

 

 

 

 

 

 

 

 

   

 

source. If the integrated mains power supply module is used, connect terminals L and N to

   

 

 

 

 

 

   

 

 

   

     

the mains. 

NOTE! Actuator short-circuits should be avoided, to protect the instrument relays using

 

 

 

 

 

   

 

 

 

 

 

external fuses or safety switches. 

 

 

12 

Содержание E2658-C2H4-230

Страница 1: ...PluraSens Ethylene Detector Transmitter E2658 C2H4 User Manual...

Страница 2: ...Sensor probe handling 10 Gas sensor replacement procedures 10 Electrical connections 11 Operation 13 Maintenance 13 Calibration 13 Delivery set 14 Order code for E2658 C2H4 options 14 Configuring 15...

Страница 3: ...m 3 Boiling point 103 7 C Low explosive limit LEL vol in air 2 7 Upper explosive limit UEL vol in air 36 0 Odor Faint sweet odor when pure Odor threshold 270 600 ppm so the odor is not an adequate war...

Страница 4: ...assignment OUT1 2 gas OUT2 2 gas Output scale width 10 resolution Recommended 20 100 of the detection range Load resistance R L Us 2 V 22 mA for 4 20 mA R L 250 kOhm for 0 10 V mode Digital interface...

Страница 5: ...4 EN 60079 29 1 2016 EN 60079 29 2 2015 EN 60079 29 3 2014 Operating conditions 20 50 C up to 100 RH 0 9 1 1 atm Explosion safe zones and ATEX Zones 2 and 22 Avoid strong mechanical shock vibrations o...

Страница 6: ...or power supply The version of your detector is marked on the package If the symbol is marked on the equipment consult the documentation for further information Safety requirements Misuse will impair...

Страница 7: ...urther instructions and related information about the installation During the installation of the detector transmitter the following points must be considered Application air quality control or leakag...

Страница 8: ...the sealed area of the device see dimensional drawing Unscrew four lid screws and detach the lid from the detector Fix the detector on the wall and earth the enclosure using an earthing terminal on th...

Страница 9: ...E2658 C2H4 Rev 12 03 2021 Mounting dimensions Front view Bottom view 9...

Страница 10: ...since this may damage the sensor Do not remove the filter as it may cause the device to show incorrect values and or break the sensor The recommended orientation of the sensor probe is vertical with...

Страница 11: ...er supply and of the external devices Without turning on the power plug the power cable and connect the analog relay outputs and or digital interface terminals to the necessary devices according to th...

Страница 12: ...g to an external RS485 network Both analog outputs can be independently changed between 4 20 mA and 0 10 V type using jumpers J1 OUT1 and J2 OUT2 By closing pins on a specific jumper the related outpu...

Страница 13: ...the conformity to IP66 protection class and ATEX requirements Make certain that the device is properly earthed The device is ready to use Maintenance Do not perform any maintenance operation with the...

Страница 14: ...2658 Mounting accessories 2 screws with plastic dowels Order code for E2658 C2H4 options 14 E2658 options Order code Integrated 90 265 V mains power supply module E2658 C2H4 230 Integrated 24 VAC powe...

Страница 15: ...xible setting of analog output scales for each output Output zero and slope adjustment for calibration Free assignment of each of two relays to the chosen parameter Several relay control logic modes S...

Страница 16: ...rameter Permitted values Default Supported baud rates 1200 2400 4800 9600 19200 38400 57600 9600 Data bits 8 8 Parity none odd even none Stop bits 1 2 1 Protocol Modbus RTU Modbus functions 03 Read mu...

Страница 17: ...C 32000 32000 ADC units 0 0x00A6 166 40167 RW Slope adjustment for gas data 1 65535 512 0x00A7 167 40168 RW The change rate limit for gas units s 1 32000 0 no limit 0 0x00A8 168 40169 RW Integrating f...

Страница 18: ...lay RE1 0 1000 s 0 0x00D8 216 40217 RW Switching delay for relay RE2 0 1000 s 0 0x00D9 217 40218 RW Minimal on off time for relay RE1 0 1000 s 0 0x00DA 218 40219 RW Minimal on off time for relay RE2 0...

Страница 19: ...RO bit 1 0 1 analog outputs deactivated activated bit 2 0 1 in case the sensor is absent turn signaling off on analog output1 bit 3 0 1 in case the sensor is absent turn on signaling with low current...

Страница 20: ...0 1 1 Hz 50 on 50 off LED signal off on if relay1 turned on bit 12 0 1 2 Hz 50 on 50 off LED signal off on if relay2 turned on 0x0101 257 40258 R Raw gas sensor data 0 4095 ADC units 0x0103 259 40260...

Страница 21: ...Manufacturer will at its option either repair or replace a product that proves to be defective This warranty is void if the product has been operated in conditions outside ranges specified by the Manu...

Отзывы: