E2630-LEL

Rev 23.03.2021

Operation

During the first ca. 60 seconds after powering on E2630 performs a warming-up and
self-diagnostic routine, indicated by the flashing of each LED. The upper dual-color LED
remains continuously green in normal operation and blinks red in case of device or sensor
fault. The warm-up time depends on the sensor type, unpowered period, and atmosphere.

During the first 30 seconds after powering on you may select the automatic or manual
mode of alarm release. Touch the device with the magnet key on the spot shown in the
drawing below.

A short touch (< 2 s) enables the automatic mode, a touch of 2...10 s — manual mode. The
activation of the automatic mode is followed by a single LED blinking and acoustic signal.
If manual mode is activated, the double acoustic and light signal follows.

If the gas concentration exceeds the LOW alarm setpoint, the bottom red LED starts
flashing at a rate of 1 Hz, and the relay RE1 switches over. The first alarm stops
automatically if the gas concentration drops below 70% of the LOW alarm setpoint.

If the gas level exceeds the HIGH alarm setpoint, the bottom red LED starts flashing and
the buzzer starts beeping at a rate of 2 Hz, and also the relay RE2 switches over.
Depending on the selected release mode, the HIGH alarm stops automatically or can be
stopped with a short touch of the magnet key, if the gas level has dropped below 70% of
the LOW alarm setpoint. Upon contact, the key should activate the reed switch located left
of the sensor inside the device.

Apart from the warming-up period, a 2....10 s touch causes the device to reset and perform
the self-diagnostic routine for testing purposes. To check the visual and acoustic alarm,
touch the device with the magnet key for more than 10 s. This will launch blinking and
beeping (stops as soon as the key is withdrawn).

13

Содержание E2630-LEL

Страница 1: ...Combustible Gas Detector E2630 LEL User Manual...

Страница 2: ...ications 8 Product description 9 Safety requirements 9 Operating conditions 9 Installation guidelines 9 Mounting dimensions 11 Connections 12 Operation 13 Sensor probe handling 14 Maintenance 15 Calib...

Страница 3: ...Ethyne Chemical formula HC CH Molar weight 26 Relative gas density to air 0 90 Conversion 1 ppm 1 06 mg m3 Boiling point 84 C Low explosive limit LEL vol in air 2 3 2 5 Upper explosive limit UEL vol...

Страница 4: ...are referred to as LPG liquefied petroleum gas Chemical formula n butane CH3CH2CH2CH3 iso butane CH3CH CH3 CH3 Molar weight 58 Relative gas density to air 2 0 Conversion 1 ppm 2 38 mg m3 Boiling poin...

Страница 5: ...e electrolysis of aqueous solutions In industrial production the main source of hydrogen is hydrocarbons Chemical formula H2 Molar weight 2 Relative gas density to air 0 07 Conversion 1 ppm 0 0818 mg...

Страница 6: ...Synonyms Marsh Gas Natural Gas Carbon tetrahydride Hydrogen carbide Chemical formula CH4 Molar weight 16 Relative gas density to air 0 55 Conversion 1 ppm 0 65 mg m3 Boiling point 161 49 C Low explosi...

Страница 7: ...r weight 44 Relative gas density to air 1 55 Conversion 1 ppm 1 80 mg m3 Boiling point 42 C Low explosive limit LEL vol in air 1 7 2 1 Upper explosive limit UEL vol in air 9 5 Odor Odorless when pure...

Страница 8: ...ace UART Relay outputs 2 SPDT max 5 A 30 VDC 250 VAC Alarm signaling Buzzer 2 kHz 85 dB red LED LEDs Green red operation fault red gas alarm Enclosure Grey ABS wall mount protection class IP65 Dimensi...

Страница 9: ...ctricity Connection diagrams can be found in the connections section The device might not perform correctly or be damaged if the wrong power supply is connected External circuits connected to the equi...

Страница 10: ...d be accessible for maintenance and repair The aforementioned conditions above will affect the coverage area of the device however the coverage area for a detector is usually between 2 5 to 5 meters r...

Страница 11: ...E2630 LEL Rev 23 03 2021 Mounting dimensions 11...

Страница 12: ...mm2 We recommend to strip the wire end by 5 6 mm and use the wire end sleeves To connect the wire loosen the screw insert the wire end into the terminal hole and tighten the screw The outer diameter...

Страница 13: ...gas concentration exceeds the LOW alarm setpoint the bottom red LED starts flashing at a rate of 1 Hz and the relay RE1 switches over The first alarm stops automatically if the gas concentration drop...

Страница 14: ...lter Place a new filter into the cap and tighten it again NOTE Never stab or press the filter near its center where the sensor is located since this may damage the sensor Do not remove the filter as i...

Страница 15: ...acturer with standard gas mixtures before delivery Provided that the sensor is used under moderate conditions field recalibration is recommended every 12 months Please contact your dealer for more inf...

Страница 16: ...Manufacturer will at its option either repair or replace a product that proves to be defective This warranty is void if the product has been operated in conditions outside ranges specified by the Manu...

Отзывы: