Every Contr
ol S.r
.l. • FK 203T • Sheet 2/2
The instrument shows the indications above flashing.
7
TECHNICAL DATA
7.1 Technical data
Box:
self-extinguishing grey.
Size:
75 x 33.5 x 81 mm (2.95 x 1.31 x 3.18 in) the model with extractable terminal
blocks (standard model), 75 x 33.5 x 62 mm (2.95 x 1.31 x 2.44 in) the model with
screw terminal blocks (by request).
Installation:
panel mounting, panel cut out 71 x 29 mm (2.79 x 1.14 in), with click
brackets (they are supplied by the builder) or screw brackets (by request).
Frontal protection:
IP 65.
Connections:
extractable terminal blocks with pitch 5 mm (0.19 in, standard model)
for cables up to 2.5 mm² (0.38 sq in, power supply, inputs and outputs) or screw termi-
nal blocks with pitch 5 mm (0.19 in, by request) for cables up to 2.5 mm² (0.38 sq in,
power supply, inputs and outputs), 5 poles single line male connector with pitch
2.5 mm (0.09 in, serial port).
Ambient temperature:
from 0 to 55
°
C (32 to 131
°
F, 10 ... 90% of relative humidity
without condensate).
Power supply:
230 Vac, 50/60 Hz, 1.5 VA (standard model) or 115 Vac, 50/60 Hz,
1.5 VA (by request).
Measure inputs:
2 (cabinet and evaporator probe) for PTC or NTC probes.
Working range:
from -50 to 99
°
C (-58 to 210
°
F) for PTC probe, from -40 to 99
°
C
(-40 to 210
°
F) for NTC probe.
Setpoint range:
from -55 to 99
°
C (-55 to 99
°
F).
Resolution:
1
°
F with unit of measure in Fahrenheit, 1
°
C with unit of measure in
Celsius.
Display:
one red LED 3-digit display 13.2 mm (0.51 in) high, output status indicators.
Outputs:
3 relays: one 10 A @ 250 Vac relay for one ½ HP @ 230 Vac compressor
control (NO contact), one 8 A @ 250 Vac relay for evaporator fan control (NO contact)
and one 8 A @ 250 Vac relay for defrost system control (change-over contact).
Kind of defrost:
electric and hot gas defrost.
Defrost control:
defrost interval, defrost end temperature and defrost maximum length
(automatic and by hand).
cabinet
tem-
perature
lower or
upper
tempera-
ture alarm
the cabinet tempera-
ture is outside the limit
you have set with the
parameter A1 or A2
test the temperature
close to the probe
(look at the parameters
A0, A1 and A2)
no effects
Serial port:
TTL with EVCOBUS communication protocol (for the configurer/cloner
system CLONE and supervision system RICS).
F6
0
1
---
0
kind of evaporator fan stop temperature (it is important if /A = 1 and F7 = 3 or 4;
0 = absolute evaporator fan stop temperature, 1 = evaporator fan stop temperature relative
to the cabinet temperature)
(11)
F7
0
4
---
4
evaporator fan action during the normal operation (0 = it will be forced OFF, 1 = it will be
forced ON, 2 = it will work in accordance with the compressor, 3 = it will work in accordance
with F1 and F2, 4 = if the compressor is ON, it will work in accordance with F1 and F2, if the
compressor is OFF, it will be forced OFF)
LABEL MIN. MAX. U.M.
DEF. SERIAL NETWORK (EVCOBUS)
L1
1
15
---
1
instrument address
L2
0
7
---
6
instrument group
L4
0
3
---
1
baud rate (0 = 1,200 baud, 1 = 2,400 baud, 2 = 4,800 baud, 3 = 9,600 baud)
(4)
the unit of measure depends on the parameter /8
(5)
once you have modified the value of the parameter, you will have to switch off the power supply of the instrument
(6)
if the parameter has value 0, the defrost will end by time (parameter d3); if the parameter F7 has value 3 or 4, the evaporator fan will work in accordance with the compressor,
except what you have set with the parameters F4 and F5
(7)
unless the evaporator temperature is below the defrost end temperature you have set with the parameter d2, the defrost will not be activated
(8)
if at the moment of the defrost activation the cabinet temperature is below the value “working se r0” , the instrument will not show temperatures above that value; if
at the moment of the defrost activation the cabinet temperature is above the value “working se r0” , the instrument will not show the increases of the temperature (if
the increase takes place below the value “working se r0” , look at the previous case); the instrument restores the normal operation once the after dripping evaporator
fan delay ends and the cabinet temperature falls below the freeze temperature
(9)
if at the moment of the defrost activation the compressor is ON since a time lower than the one you have set with the parameter, the compressor will be forced ON for a
time such as to finish the time you have set with the parameter
(10) if the temperature alarm does not disappear at the end of the time you have set with the parameter A3, it will further be excluded for the time you have set with the parameter
A6; if the temperature alarm takes place during the defrost and does not disappear at the end of the time you have set with the parameter A7, it will further be excluded for the
time you have set with the parameter A6
(11) the evaporator fan stop temperature is “cabinet temperature - F1” ; you always have to consider the parameter F1 with positive sign.