
HOMEDEPOT.COM
13
Please contact 1-844-883-1872 for further assistance.
Troubleshooting
Symptom
Probable Cause
Corrective Action
The motor will not start but
fuses do not blow.
There is no voltage at the fuse box.
Replace blown fuses.
There is no voltage at the pressure switch
Replace the faulty pressure switch.
There is no voltage at the control box
Rewire the supply to the control box.
Cable or splices are bad.
Consult a licensed electrician or serviceman.
The control box is incorrectly wired.
Reconnect the control box correctly (see wiring
diagrams).
The fuses blow or overload
protector trips when the
motor starts.
The fuse or time delay fuse size is wrong.
Check the fuse size against the Recommended Fusing
Data tables in the Wiring section of this manual. Install
the correct fuse or time delay fuse.
The wire size is too small.
Check the wire size against the tables in the Wiring
section of this manual. Install the correct size wire.
The starting capacitor is defective or blown.
Check the control box to see if starting capacitor has
blown out. Replace the starting capacitor.
The voltage is either too low or high.
Check that line voltage is within ±10% of the nameplate
rated voltage while the motor is running. If voltage
variation is greater than ±10%, call the power company to
adjust the voltage.
The cable leads are not correctly connected to
the control box.
Check the control box wiring diagram against the
incoming power hookup. Check drop cable color coding.
Reconnect the drop cable so the cable color code
matches the motor lead color code.
There is a broken wire in the control box.
Examine all connections and wiring in the control box.
Disconnect the power and repair or replace the faulty
wire.
The pump or motor is stuck or binding.
Check for a locked rotor in the pump. If necessary, pull
the pump (make all possible above ground checks first). If
the pump is locked, replace it. Clean the well of all sand
or lime before reinstalling pump.
Fuses blow or overload
protector trips when the
motor is running.
The voltage is either too low or too high.
Check that line voltage is within ±10% of the nameplate
rated voltage while the motor is running. If voltage
variation is greater than ±10%, call the power company to
adjust the voltage.
The ambient (atmospheric) temperature is
high.
Check the temperature of the control box. Do not mount
the control box in direct sunlight.
Control box with wrong voltage or horsepower
rating.
Compare voltage and horsepower on the motor nameplate
with those given on the control box nameplate or on the
circuit diagram inside the control box cover. Replace the
control box if the numbers do not match.
The wire size is too small.
Check the wire size against the table in the Wiring section
of this manual. Install the correct size wire.
Cable splices or motor leads grounded,
shorted, or open.
Consult a licensed electrician or qualified serviceman. Do
not attempt to disassemble the pump or motor.